background image

1

6LE000377A

TYB6.2F

Output 2gang 6A / 1gang shutter/blind, 
flush mounted
Input 2gang + output 2gang 6A / 1gang 
shutter/blind, flush mounted

TXB6.2F

Output 2gang 6A / 1gang shutter/blind, 
flush mounted
Input 2gang + output 2gang 6A / 1gang 
shutter/blind, flush mounted

z

07/2014 - 6LE000377A

Hager Controls S.A.S., 33 rue Saint-Nicolas, B.P. 10140, 67703 SAVERNE CEDEX, France - www.hager.com

Bn,.:  

M

  

`

Safety instructions

Electrical equipment may only be installed and 

assembled by a qualified electrician in accor-

dance with the relevant installation standards, 

guidelines, regulations, directives, safety and 

accident prevention regulations of the country.
Failure to comply with these installation in-

structions may result in damage to the device, 

fire or other hazards.
Hazard due to electric shock. Disconnect be-

fore working on the device or load. Take into 

account all circuit breakers that supply

dangerous voltages to the device or load. 
Hazard due to electric shock. The device is not 

suited for safe disconnection of the mains sup-

ply.
Hazard due to electric shock on the SELV or 

PELV installation. Do not connect any loads for 

low voltage SELV, PELV or FELV together.
Connect one motor only. If several motors are 

connected, motors or device might be destro-

yed.
Use drives with mechanical or electrical final 

position switches only. Check final position 

switches for correct adjustment. Observe

motor manufacturer‘s data. The device can be 

damaged.
Observe the motor manufacturer‘s data

regarding change-over time and max. switch-

on time (ED).
These instructions are an integral component 

of the product and must be retained by the end 

user.

Design and layout of the device

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

(1)

(2)

(3)

Fig. 1: example device variant with inputs

(1) Illuminated button for manual operation/

programming button

(2) Connection of load(s)
(3) KNX bus connection cable/

connection inputs

Function

System information

This device is a product of KNX system and corre-

sponds to the KNX guidelines. Detailed specialised 

knowledge obtained from KNX training courses is 

required for understanding. The planning, installa-

tion and commissioning of the device is carried out 

with the help of KNX-certified software. 

Systemlink commissioning

The function of the device is software-dependent. 

The software is to be taken from the product 

database. You can find the latest version of the 

product database, technical descriptions as well as 

conversion and additional support programmes on 

our website.

Easylink commissioning

The function of the device is configuration-depen-

dent. The configuration can also be done using 

devices developed specially for simple setting and 

start-up.
This type of configuration is only possible with 

devices of the easylink system. Easylink stands for 

easy, visually supported start-up. Preconfigured 

standard functions are assigned to the in/outputs 

by means of a service module.

Functional description

The device receives telegrams from sensors or 

other controllers via the KNX installation bus and 

switches electrical loads with its relay contact.

Correct use

- Switching of electrical loads AC 230 V with po-

tential-free contact.

- Switching electrically operated motors of 230 V 

AC for blinds, shutters, awnings and similar 

hangings.

- Installation into wall box according to DIN 

49073 (use deep box) or junction box surface-

mounted/flush-mounted.

Product characteristics

- Manual activation of the outputs on the device 

possible, building site operation.

- Status display of the outputs on the device.

- Scene function.

- Forced position by higher-level controller.

Functions in switch operation

- Time switching functions.

Functions in roller shutter/blind operation

- Position can be started directly.

- Slat position directly controllable.

- Feedback of operating state, shutter position 

and slat adjustment.

- 3 Alarms.

Functions of the inputs

- ON/OFF.

- Dimming.

- Up/down.

- Slat angle/Stop.

- Alarm.

- Scene.

- Mandatory control.

- Time switching operation.

Information for electricians
Installation and electrical connection

DANGER!
Touching live parts can result in an 

electric shock!
An electric shock can be lethal!
Disconnect the connecting cables 

before working on the device and 

cover all live parts in the area!

ç

Connecting and installing the device

CAUTION!
Impermissible heating if the load of 

the device is too high!
The device and the connected cables 

may get damaged in the connection 

area!
Do not exceed the maximum current 

carrying capacity!

ç

CAUTION!
When connecting the bus/extension 

units and mains voltage wires in a 

common wall box, the KNX bus cable 

might come into contact with the 

mains voltage.
The safety of the entire KNX 

installation is at risk. Persons could 

also get an electric shock even on 

remote devices.
Do not place bus/extension units and 

mains voltage terminals in a common 

terminal compartment. Use a wall box 

with a firm partition or separate boxes 

(Figure 2).

ç

CAUTION!
Risk of destruction if parallel circuit of 

several motors!
Final position switches could fuse 

together. Motors, hangings and the 

device may be destroyed!
Connect one motor only! 

ç

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

SELV

FELV

230 V AC

Figure 2: installation with separate terminal com-

partment

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

Bus 

30 V DC

L

N

10 A

In 1

In 2

Com

Figure 3: connection of switching loads

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

Bus 

30 V DC

L

N

10 A

In 1

In 2

Com

Figure 4: connection of motors

Observe installation regulations for SELV voltage. 

Maintain a minimum distance of 4 mm between 

mains voltage and bus wires.
The installation circuit must be protected via circuit 

breaker 10 A.
Do not connect different phases (outer conductors) 

to the device.

z

Connect bus cable via connecting terminal.

z

Connect loads (figure 3/4) to the load connec-

ting terminals (2).

z

Place device into the installation box.

Connect inputs

green

white

yellow

red

black

In 1

Com

In 2

KNX+

KNX-

Table 1: connection assignment of the control line

z

Connect potential-free contacts to the inputs.

Start-up

Systemlink: loading physical address and 

application software

z

Switch on bus voltage.

z

Press programming button (1). 
The button lights up.
 If the button does not light up, no bus voltage is 

present.

z

Load the physical address into the device. 
Status LED of the button goes out.

z

Load application software. 

z

Note down the physical address on the device.

Easylink

Information on the system configuration can be 

taken from the extensive description of the service 

module Easylink.

Start up the device

z

Switch on mains voltage on the outputs.

Switch test mode on/off

The device is connected. Bus voltage and swit-

ching voltage are present.

z

Keep button (1) pressed > 5 s with a pointed 

object until it flashes green. 
The device is in test mode.

Or with test mode switched on

z

Keep button (1) pressed > 5 s until it flashes 

green 3 times. 
The device is in normal operation.
After approx. 5 min. without any further operati-

on, the device exits test mode automatically.

Operating output in test mode

Operation takes place by briefly pressing a button 

repeatedly (1).
The device is in test mode. The button flashes 

green until the first operation.

z

Press the button (1) for a short time.
The output changes its switching state.
The switching takes place according to the 

following sequence:

S1 closed - S1 open - S2 closed - S2 open. 

Resetting the device to the factory settings

z

The device provides the possibility of restoring 

the factory setting via a programming button. 
The programming is lost after resetting to the 

factory setting. Activation via the bus is no 

longer possible.

z

Hold down the button (1) for (> 10 s) until it 

flashes red.

P

P

P

P

Appendix
Technical data

Supply voltage KNX

21…32 V DC SELV

Breaking capacity

µ 6 A AC1 230 V~

Switching current at cos Φ = 0.8 

max. 6 A 

Minimum switching current 

10 mA 

Operating altitude

max. 2000 m

Degree of contamination

2

Surge voltage

4 kV

Degree of protection of housing

IP20

Impact protection

IK 04

Overvoltage class

III

Operating temperature

-5°C…+45°C

Storage/transport temperature

-20°C … +70°C

Maximum switching cycle rate

at full load

20 switching cycle/minute

Connection capacity

0.75 mm²…2.5 mm²

max. tightening torque 

0.5 Nm

Cross-head design

PZ1

Installation type flush-mounted installation switch/

flush-mounted electronic/

flush-mounted/surface-mounted junction box

Standards

EN 50491-3 ; EN 60669-2-1

Dimensions

44 x 43 x 22.5 mm

Own consumption on the KNX bus:

typical 

7 mA

in standby

5 mA

Incandescent lamps 

500 W

HV halogen lamps

500 W

Conventional transformer

500 VA

Electronic transformer

500 W

Fluorescent lamps

- without ballast

500 W

- with electronic ballast

6 x 48 W

Energy-saving lamps

5 x 13 W

LED lamps

5 x 13 W

Change-over time for  

change of direction

software-dependent

Variant with inputs

Number of inputs

2

Input type

potential-free

Total length of extension unit cable

max. 9.9 m

Scanning voltage 

extension unit inputs

12 V DC/1mA

Troubleshooting

Test mode not possible. Red programming LED 

lights up.

Cause: push-button (1) was pressed too short.

Short press on push-button, red LED goes out. 

Press push-button again (> 5 s).

Bus operation is not possible

Cause 1: bus voltage is not present.

Check bus connection terminal for correct 

polarity.
Check bus voltage by briefly pressing the pro-

gramming button (1), red LED lights up if bus 

voltage is present.

Cause 2: device was reset to the factory setting.

Repeat programming and start-up.

z

1

6LE000377A

TYB6.2F

Output 2gang 6A / 1gang shutter/blind, 
flush mounted
Input 2gang + output 2gang 6A / 1gang 
shutter/blind, flush mounted

TXB6.2F

Output 2gang 6A / 1gang shutter/blind, 
flush mounted
Input 2gang + output 2gang 6A / 1gang 
shutter/blind, flush mounted

z

07/2014 - 6LE000377A

Hager Controls S.A.S., 33 rue Saint-Nicolas, B.P. 10140, 67703 SAVERNE CEDEX, France - www.hager.com

Bn,.:  

M

  

`

Safety instructions

Electrical equipment may only be installed and 

assembled by a qualified electrician in accor-

dance with the relevant installation standards, 

guidelines, regulations, directives, safety and 

accident prevention regulations of the country.
Failure to comply with these installation in-

structions may result in damage to the device, 

fire or other hazards.
Hazard due to electric shock. Disconnect be-

fore working on the device or load. Take into 

account all circuit breakers that supply

dangerous voltages to the device or load. 
Hazard due to electric shock. The device is not 

suited for safe disconnection of the mains sup-

ply.
Hazard due to electric shock on the SELV or 

PELV installation. Do not connect any loads for 

low voltage SELV, PELV or FELV together.
Connect one motor only. If several motors are 

connected, motors or device might be destro-

yed.
Use drives with mechanical or electrical final 

position switches only. Check final position 

switches for correct adjustment. Observe

motor manufacturer‘s data. The device can be 

damaged.
Observe the motor manufacturer‘s data

regarding change-over time and max. switch-

on time (ED).
These instructions are an integral component 

of the product and must be retained by the end 

user.

Design and layout of the device

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

(1)

(2)

(3)

Fig. 1: example device variant with inputs

(1) Illuminated button for manual operation/

programming button

(2) Connection of load(s)
(3) KNX bus connection cable/

connection inputs

Function

System information

This device is a product of KNX system and corre-

sponds to the KNX guidelines. Detailed specialised 

knowledge obtained from KNX training courses is 

required for understanding. The planning, installa-

tion and commissioning of the device is carried out 

with the help of KNX-certified software. 

Systemlink commissioning

The function of the device is software-dependent. 

The software is to be taken from the product 

database. You can find the latest version of the 

product database, technical descriptions as well as 

conversion and additional support programmes on 

our website.

Easylink commissioning

The function of the device is configuration-depen-

dent. The configuration can also be done using 

devices developed specially for simple setting and 

start-up.
This type of configuration is only possible with 

devices of the easylink system. Easylink stands for 

easy, visually supported start-up. Preconfigured 

standard functions are assigned to the in/outputs 

by means of a service module.

Functional description

The device receives telegrams from sensors or 

other controllers via the KNX installation bus and 

switches electrical loads with its relay contact.

Correct use

- Switching of electrical loads AC 230 V with po-

tential-free contact.

- Switching electrically operated motors of 230 V 

AC for blinds, shutters, awnings and similar 

hangings.

- Installation into wall box according to DIN 

49073 (use deep box) or junction box surface-

mounted/flush-mounted.

Product characteristics

- Manual activation of the outputs on the device 

possible, building site operation.

- Status display of the outputs on the device.

- Scene function.

- Forced position by higher-level controller.

Functions in switch operation

- Time switching functions.

Functions in roller shutter/blind operation

- Position can be started directly.

- Slat position directly controllable.

- Feedback of operating state, shutter position 

and slat adjustment.

- 3 Alarms.

Functions of the inputs

- ON/OFF.

- Dimming.

- Up/down.

- Slat angle/Stop.

- Alarm.

- Scene.

- Mandatory control.

- Time switching operation.

Information for electricians
Installation and electrical connection

DANGER!
Touching live parts can result in an 

electric shock!
An electric shock can be lethal!
Disconnect the connecting cables 

before working on the device and 

cover all live parts in the area!

ç

Connecting and installing the device

CAUTION!
Impermissible heating if the load of 

the device is too high!
The device and the connected cables 

may get damaged in the connection 

area!
Do not exceed the maximum current 

carrying capacity!

ç

CAUTION!
When connecting the bus/extension 

units and mains voltage wires in a 

common wall box, the KNX bus cable 

might come into contact with the 

mains voltage.
The safety of the entire KNX 

installation is at risk. Persons could 

also get an electric shock even on 

remote devices.
Do not place bus/extension units and 

mains voltage terminals in a common 

terminal compartment. Use a wall box 

with a firm partition or separate boxes 

(Figure 2).

ç

CAUTION!
Risk of destruction if parallel circuit of 

several motors!
Final position switches could fuse 

together. Motors, hangings and the 

device may be destroyed!
Connect one motor only! 

ç

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

SELV

FELV

230 V AC

Figure 2: installation with separate terminal com-

partment

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

Bus 

30 V DC

L

N

10 A

In 1

In 2

Com

Figure 3: connection of switching loads

S1 S2

KNX+ /RD

KNX- /BK

In 1 /GN

Com /WH

In 2 /YE

Bus 

30 V DC

L

N

10 A

In 1

In 2

Com

Figure 4: connection of motors

Observe installation regulations for SELV voltage. 

Maintain a minimum distance of 4 mm between 

mains voltage and bus wires.
The installation circuit must be protected via circuit 

breaker 10 A.
Do not connect different phases (outer conductors) 

to the device.

z

Connect bus cable via connecting terminal.

z

Connect loads (figure 3/4) to the load connec-

ting terminals (2).

z

Place device into the installation box.

Connect inputs

green

white

yellow

red

black

In 1

Com

In 2

KNX+

KNX-

Table 1: connection assignment of the control line

z

Connect potential-free contacts to the inputs.

Start-up

Systemlink: loading physical address and 

application software

z

Switch on bus voltage.

z

Press programming button (1). 
The button lights up.
 If the button does not light up, no bus voltage is 

present.

z

Load the physical address into the device. 
Status LED of the button goes out.

z

Load application software. 

z

Note down the physical address on the device.

Easylink

Information on the system configuration can be 

taken from the extensive description of the service 

module Easylink.

Start up the device

z

Switch on mains voltage on the outputs.

Switch test mode on/off

The device is connected. Bus voltage and swit-

ching voltage are present.

z

Keep button (1) pressed > 5 s with a pointed 

object until it flashes green. 
The device is in test mode.

Or with test mode switched on

z

Keep button (1) pressed > 5 s until it flashes 

green 3 times. 
The device is in normal operation.
After approx. 5 min. without any further operati-

on, the device exits test mode automatically.

Operating output in test mode

Operation takes place by briefly pressing a button 

repeatedly (1).
The device is in test mode. The button flashes 

green until the first operation.

z

Press the button (1) for a short time.
The output changes its switching state.
The switching takes place according to the 

following sequence:

S1 closed - S1 open - S2 closed - S2 open. 

Resetting the device to the factory settings

z

The device provides the possibility of restoring 

the factory setting via a programming button. 
The programming is lost after resetting to the 

factory setting. Activation via the bus is no 

longer possible.

z

Hold down the button (1) for (> 10 s) until it 

flashes red.

P

P

P

P

Appendix
Technical data

Supply voltage KNX

21…32 V DC SELV

Breaking capacity

µ 6 A AC1 230 V~

Switching current at cos Φ = 0.8 

max. 6 A 

Minimum switching current 

10 mA 

Operating altitude

max. 2000 m

Degree of contamination

2

Surge voltage

4 kV

Degree of protection of housing

IP20

Impact protection

IK 04

Overvoltage class

III

Operating temperature

-5°C…+45°C

Storage/transport temperature

-20°C … +70°C

Maximum switching cycle rate

at full load

20 switching cycle/minute

Connection capacity

0.75 mm²…2.5 mm²

max. tightening torque 

0.5 Nm

Cross-head design

PZ1

Installation type flush-mounted installation switch/

flush-mounted electronic/

flush-mounted/surface-mounted junction box

Standards

EN 50491-3 ; EN 60669-2-1

Dimensions

44 x 43 x 22.5 mm

Own consumption on the KNX bus:

typical 

7 mA

in standby

5 mA

Incandescent lamps 

500 W

HV halogen lamps

500 W

Conventional transformer

500 VA

Electronic transformer

500 W

Fluorescent lamps

- without ballast

500 W

- with electronic ballast

6 x 48 W

Energy-saving lamps

5 x 13 W

LED lamps

5 x 13 W

Change-over time for  

change of direction

software-dependent

Variant with inputs

Number of inputs

2

Input type

potential-free

Total length of extension unit cable

max. 9.9 m

Scanning voltage 

extension unit inputs

12 V DC/1mA

Troubleshooting

Test mode not possible. Red programming LED 

lights up.

Cause: push-button (1) was pressed too short.

Short press on push-button, red LED goes out. 

Press push-button again (> 5 s).

Bus operation is not possible

Cause 1: bus voltage is not present.

Check bus connection terminal for correct 

polarity.
Check bus voltage by briefly pressing the pro-

gramming button (1), red LED lights up if bus 

voltage is present.

Cause 2: device was reset to the factory setting.

Repeat programming and start-up.

z

s

Appendix

Technical data

Supply voltage KNX  

21 

 32 V 

s

 SELV

Breaking capacity  

μ 6 A AC1 230 V~

Switching current at cos 

φ

 = 0.6 

 max. 6 A

Minimum switching current  

10 mA

Operating altitude 

 max. 2000 m

Degree of contamination  

2

Surge voltage  

4 kV

Degree of protection of housing  

IP20

Impact protection  

IK 04

Overvoltage class  

III

Operating temperature  

-5 °C 

➡ 

45 °C

Storage/transport temperature   -20 °C 

 +70 °C

Maximum switching cycle rate

at full load  

20 switching cycle/minute

Connection capacity  

0.75 mm² 

➡ 

2.5 mm²

max. tightening torque 

 0.5 Nm

Upstream protection 

 circuit breaker 10 A

Communication Media 

 TP

Confi guration mode   S mode - Easy link controller

Cross-head design  

PZ1

Installation type fl ush-mounted installation switch/

 

fl ush-mounted electronic/

 

fl ush-mounted/surface-mounted junction box

Dimensions  

44 x 43 x 22.5 mm

Own consumption on the KNX bus:

typical 

 7 mA

in standby  

5 mA

Incandescent lamps 

 500 W

HV halogen lamps  

500 W

Conventional transformer  

500 VA

Electronic transformer 

 500 W

Fluorescent lamps

-without ballast  

500 W

-with electronic ballast 

 6 x 48 W

Energy-saving lamps  

2 x 13 W

LED lamps 

 2 x 13 W

Change-over time for

change of direction  

software-dependent

Variant with inputs

Number of inputs  

2

Input type  

potential-free

Total length of extension unit cable  

max. 9.9 m

Scanning voltage

extension unit inputs  

12 V 

s

 1mA

Correct Disposal of this product (Waste Electrical & 

Electronic Equipment).

(Applicable in the European Union and other European 

countries with separate collection systems).

This marking shown on the waste or its literature indicates that it 

should not be disposed with other household wasted at the end 

of its working life. To prevent possible harm to the environment or 

human health from uncontrolled waste disposal, please separate 

this product from other types of wastes and recycle it responsibly 

to promote the sustainable reuse of material resources.

Household users should contact either the retailer where they pur-

chased this product, or their local government office, for details of 

where and how they can take this device for environmentally safe 

recycling.

Business users should contact their supplier and check the terms 

and conditions of the purchase contract. This product should not be 

mixed with other commercial wastes of disposal.

 Usable in all Europe

å

and in Switzerland

s

6LE000377C

2

Отзывы: