2
6T 6094.a
Hager 03.2006
User instructions
GB
6T 6094.a
Technical Data
- Supply voltage:
230 V AC 50/60 Hz
- Bus KNX/EIB:
30V DC TBTS
- Max. power uptake:
50W
- Bus power consumption:
< 10mA
- Standard fuse:
T 2A
- Max. number of actuators:
13
- Dimensions (mm) H/W/L:
70 x 75 x 302
- Safety class:
II
- Protection type:
IP20
- Connection :
Flexible capacity:
0,5 —> 1,5 mm
2
Rigid capacity:
1 —> 1,5 mm
2
- Operating temperature:
-5 °C —> +40 °C
- Storage temperature:
-20 °C —> +60 °C
Safety Instructions
- Before opening the basis always switch the
system off.
- To clean the unit use a dry towel only.
- Never clean the unit with water or other
solvents (e.g. spirit, acetone).
In case of emergency
Immediately remove the plug from the mains.
Network connection / Connection
of actuators
- Each actor requires its own connection to
the main power supply.
- Possibility to connect up to a maximum of
13 actuators to the basis.
1. Press the wires into the
cable grip so that the
sheath is flush with the
top edge.
2. Insert die end of the
lines into the terminals.
Observe the color coding
of the connections.
3. A maximum of 4
actuators can be
connected to each channel.
Changing the fuse
1. Fuse indicator lit.
The unit must be checked
by a qualified specialist.
2. Pull out fuse casing.
3. Spare fuse is located in
transparent cover.
4. Change the fuse type T 2A.
Commissioning
1. Use the correct
connections on the
basis.
2. Fit transparent cover.
Orientation of screws must
be parallel with junction
unit.
3. Cover locks into place by
turning the screws. Basis is
now ready for operation.
4. Connect transformer to the
power outlet.
onto the wall (Ø for screws
2,5 mm).
or
To allow wiring to be routed
behind install the base unit with
spacers.
Installation on mounting bracket
1. Simple installation on mounting
bracket (EN 50022).
2. Attach mounting bracket using
the 2 screws of the delivery
contents.
3. Clip the base unit onto the
mounting bracket.
4. To remove the base from the rail,
use a screwdriver as shown.
KNX/EIB connection
1. Insert both ends of
the KNX/EIB cable into
the KNX/EIB terminal.
Installation
Mounting on the wall
1. To lift the transparent cover
from the junction unit,
loose the screws.
2. Prepare the device for
installation by seperating
all pieces.
3. Install the base unit directly
Description
Indicator lights
- Power light
illuminates when unit is
connected to power.
- Fuse indicator
illuminates when fuse is
blown. System needs to be
checked by a qualified specialist.
- Indicator
illuminates, when zone is
operating.
TX 206H
Physical adressing push-button
24 V system
Maximum of 13 actuators
Function indicators
Main 230 V AC
power source
TX 206H
Actionneur de chauffage 6 canaux
Heating Actuator 6 channels
Heizungsaktor 6 Kanal KNX/EIB
Verwarmingsaandrijving met 6 kanalen
F
GB
D
NL
RF
TP
230V~
Bus
30 V
tebis
/
Configuration
●
TX 100 V1.6.3 or higher: detailed description
is included in User’s Instructions supplied
with the configurator
●
ETS : application software TL 206D,
database and description available from the
manufacturer.
- This device must be installed only by
a qualified electrician.
- Conform to TBTS installation rules.
Application and description
The TX 206H is a 6 channels heating actuator.
It becomes heating information from room
thermostats and control thermal actuators.
This system is adapted to residential applica-
tions as well as various types of service
buildings and facilities.
It is suitable for installation in heat circulation/
distribution system and is equipped with Triacs
to ensure silent switching operations.
Bus KNX/EIB