hager TRE530 Скачать руководство пользователя страница 2

Button 

J

cfg

cfg

cfg

cfg

cfg

version à pile

version solaire

LED C

Button 

J

Warning   :

This device is to be installed only by a  

professional electrician fitter according to 

local applicable installation standards. 

Test and validation of detection 

zone

Set potentiometer 

2

 to Test mode. 

The Test mode is available for 3 minutes time 

and does not take brightness level into 

account.  

Each detected movement turns LED 

A

 on for 2 

seconds.   

The associated receiver is not under control.

After 3 minutes without detection, the product 

is set back to auto mode. 

Limitation of detection zone  :

You can limit the detection zone using the 

shutters supplied or by inclining the head. 

O

The test mode is available only once the 

product has been configured.

Mounting

Projection or ceiling mount :

-  Fix the wall plate using the supplied screws. 

-  Clip the detector onto the wall plate

-  Tighten the screws to close. 
For angle mounting, the wall fixing plate is  

fitted between the accessory and

the detector.

Precautions for installation

For optimum detection conditions, please fol-

low these recommendations :

-  Keep the detector protected from bad 

weather, as it is sensitive to these conditions. 

-  Maintain 1m distance between the light 

source and the detector and keep the detec-

tor out of the light source.

Product Description and working 

principles

This detector allows remote control of one  

or more receivers for a given time when a 

movement is detected in its detection zone. 

This product can be used in two types of 

configuration: one detector controls one/seve-

ral receiver(s); several transmitters control the 

receiver(s). 

Operation

The receiver(s) is(are) under control as soon as 

the brightness level as set by potentiometer  

2

 is considered too low and a movement is  

adetected. 

Upon detection, the time delay is restarted. 
If LED 

A

 flashes quickly during configuration, 

the position of potentiometer 

1

 is not compa-

tible with the selected function. 

Product factory reset is recommended before 

any new configuration.

 

Factory return

Keep push-button 

J

 depressed until LED  

cfg 

(flashes (>10s), and then release it. 

LED 

cfg 

is turned off when factory return is 

completed.

After factory return, wait 15s before starting 

configuration.

Action

Adjustments 

Potentiometer 

Use Auto (factory) 

settings to set  

automatic lighting 

turn-on for  

a given time.  

Only available when 

a detector’s time 

delay is set.  

Auto Settings

Put the Lux potentiometer on 

auto test

”.

The settings are predefined :
Lux = 

,  

(operating at night only)
time = 3 min,

sensitivity = max

Turn automatic  

lighting on for  

a given time. 

Only available when 

a detector’s time 

delay is set.

 

Installer settings

Test and confirm

detection zone. 

Test mode

Move the potentiometer 

2  

to “

auto test

”. 

Adjust sensitivity.

Allows setting the range

to avoid disturbance.

Configuration (button 

J

 

)

These detectors can be configured in 3 different 

ways :

•    

quick

link

: tool-free configuration (using product 

pushbuttons and LEDs), see User's Instructions 

6T7952 supplied with the product. 

•  TX100/B V2.5.0 or above :   

description of product functions available from 

the Manufacturer.

•  ETS3 or via TR131 : database and description of 

application software available from the 

Manufacturer.

Configuration by TX100 or ETS

Set the product in configuration mode by pressing 

J

 button once during the teaching session of 

TX100 or for addressing with TR131 in ETS.

O

Product factory return is required to change 

the configuration mode.  

Correct Disposal of This product
(Waste Electrical & Electronic 

Equipment).

 (Applicable in the European Union and other European 

countries with separate collection systems).
This marking shown on the product or its literature 

indicates that it hould not be disposed with other 

household wasted at the end of its working life. To 

prevent possible harm to the environment or human 

health from uncontrolled waste disposal, please 

separate this from other types of wastes and recycle 

it responsibly to promote the sustainable reuse of 

material resources.
Household users should contact either the retailer 

where they purchased this product, or their local 

government office, for details of where and how they 

can take this item for environmentally safe recycling.
Business users should contact their supplier and 

check the terms and conditions of the purchase 

contract. This product should not be mixed with other 

commercial wastes of disposal.

   Usable throughout Europe  

å 

and in Switzerland

    

Hager Controls hereby declares that the TRE51., TRE53. 

device complies with the essential requirements and other 

relevant provisions of Directive 2014/53/EU.

The CE declaration is available on the:

www.hagergroup.com

 

6LE003093A

2

Отзывы: