Construction and characteristics
16
Technical changes reserved
3.4.4
Feeder units
-
Standardized feed options for transformers, terminals and cable feeder are
available
-
Terminal elements for different rated current, direction and conductor
configurations
-
Type-tested terminal elements to Hager unimes H energy distribution system
(connection up to 4000 A)
Connection of unibar H to unimes H
Cable intermediate feeder
Cable intermediate feeder for connection joint between two adjacent straight
busbar elements.
-
The cable intermediate feeder is used to feed busbar elements from a
connection joint.
-
The two busbar elements are fed simultaneously via the cable intermediate
feeder. Independent supply of one side is not possible.
-
Cable intermediate feeder can be used to reduce the voltage drop over long
busbar runs.
-
The maximum current carried is 2000 A for aluminium- and 2500 A for copper
inner conductors in the busbars.