17.10 Connecting the ZSI input and output contacts
For zone selectivity on the STD protection and/or the earth fault protection:
Connection to downstream circuit breakers:
STD1: selectivity on the Short time delay protection
GF1: selectivity on the earth fault protection
Cmn1: common
Connection to the upstream circuit breaker:
STD2: selectivity on the Short time delay protection
GF2: selectivity on the earth fault protection
Cmn2: common
hw+ air circuit breakers have 6 ZSI terminal blocks enabling the upstream or downstream
circuit breakers to be connected to deploy zone selectivity (ZSI).
Type of connection
Total number of circuit
breakers
Max. distance between 2 circuit
breakers
Upstream
3
300 m
Downstream
7
300 m
Recommended connection cable: 1 to 1.5 mm
2
twisted cable.
ATTENTION
It is recommended that the Hager Power setup software be used to verify the wiring
between the circuit breakers.