➀
➁
➂
➃
➄
➅
➆
➈
6E 6537.a
L
N
4
2
6
10
1
5
9
i
0,1...10A
def
EU 103
set / reset
select
t
t
t
reset memo
t
t
t
reset memo
Lo + Hys
Lo
On
1
Def
2
2
4
6
Def
2
4
6
2
Memo ON
Memo OFF
Up
Up - Hys
0
➇
Technical specifications
Programming mode
Electrical characteristics
●
Current supply: 230V 50/60Hz
●
Power consumption:
≤
3VA
Functional characteristics
●
Adjustable thresholds:
0.1 to 10A 15V AC and DC
●
Measures:
Direct: 0.1 to 10A
Via current transformer:
50/5, 100/5, 150/5, 200/5, 250/5, 300/5, 400/5,
600/5
●
Hysteresis:
5 to 50% of programmed threshold
●
Time delay when exceeding t1 threshold:
t1 = 0.1 to 12 sec
●
Time delay starting t2:
t2 = 0.1 to 20 sec
Environment
●
Operating temperature: -20 °C to +55 °C
●
Storage temperature:
-40 °C to +70 °C
Connection capacity
●
Flexible 0.75 to 4 mm
2
●
Rigid 1 to 6 mm
2
Pressing simultaneously set and select keys
for 3 seconds makes it possible to enter
programming mode.
Prog
signal is displayed
for 1 second when entering this mode..
Set key: used to validate selection
Select key: used to scroll various options.
Programming sequence is as follows:
➀
Select type of signal
AC
or
DC
.
➁
Select direct measuring mode or current
transformer.
➂
Select monitoring operation mode
Overcurrent monitoring (
Up
),
Undercurrent (
Lo
) or Band (
Up Lo
)
➃
Select thresholds
High threshold if
Up
or
Up Lo
Low threshold if
Lo
or
Up Lo
➄
Define hysteresis
Hys
(Amp)
➅
Select
t1
delay (second)
➆
Select
t2
start delay (second)
➇
Select storage mode
With storage:
Yes M
Without storage:
No M
➈
End.
Confirm programming using set key. Select
key makes it possible to modify the various
parameters (steps 1 to 8).
2
4
6
8A AC1 250 V
2