background image

6E 6537.a

L

N

4

2

6

10

1

5

9

i

0,1...10A

def

EU 103

set / reset

select

t

t

t

reset memo

t

t

t

reset memo

Lo + Hys

Lo

On

1

Def

2

2

4

6

Def

2

4

6

2

Memo ON 

Memo OFF 

Up

Up - Hys

0

Technical specifications

Programming mode

Electrical characteristics

Current supply: 230V 50/60Hz

Power consumption: 

3VA 

Functional characteristics

Adjustable thresholds:
0.1 to 10A 15V AC and DC

Measures:
Direct: 0.1 to 10A
Via current transformer:
50/5, 100/5, 150/5, 200/5, 250/5, 300/5, 400/5,
600/5

Hysteresis:
5 to 50% of programmed threshold

Time delay when exceeding t1 threshold:
t1 = 0.1 to 12 sec

Time delay starting t2:
t2 = 0.1 to 20 sec

Environment

Operating temperature: -20 °C to +55 °C

Storage temperature: 

-40 °C to +70 °C

Connection capacity

Flexible 0.75 to 4 mm

2

Rigid 1 to 6 mm

2

Pressing simultaneously set and select keys
for 3 seconds makes it possible to enter 
programming mode. 

Prog

signal is displayed

for 1 second when entering this mode..

Set key: used to validate selection 
Select key: used to scroll various options.

Programming sequence is as follows:

Select type of signal 

AC

or 

DC

.

Select direct measuring mode or current

transformer.

Select monitoring operation mode

Overcurrent monitoring (

Up

),

Undercurrent (

Lo

) or Band (

Up Lo

)

Select thresholds

High threshold if 

Up

or 

Up Lo

Low threshold if 

Lo

or 

Up Lo

Define hysteresis

Hys

(Amp)

Select

t1

delay (second)

Select

t2

start delay (second)

Select storage mode

With storage: 

Yes M

Without storage: 

No  M

End.

Confirm programming using set key. Select
key makes it possible to modify the various
parameters (steps 1 to 8).

2

4

6

8A  AC1 250 V

2