48
49
oPeratIon
oPeratIon
Programming
Programming
parameter modification
>
Example :
Modify network nominal voltage from 400 to 230 V.
>
Menu setup :
1 2
Press
to access first digit (blinking)
Press 2x
to display 2 (blinking)
Press
to access second digit (blinking)
Press 3X
to display 3 (blinking)
Press
to validate
parameters characteristics
LCD
Denomination
Definition
Setting range
Default
values
1 2
type of
network*
Number of active conductors of controlled network
(refer to annexes)
1BL, 2BL, 2NBL,
3NBL, 4NBL,
41 NBL
4NBL
1 2
Network
nominal voltage
Phase-Neutral voltage for 1BL & 41NBL
Phase-Phase voltage for others
from 100 V to
400 V
400 V
1 2
Network
nominal
frequency
Network nominal frequency
50 Hz or 60 Hz
50 Hz
1 2
Genset start
signal state
Normally opened or closed
NO or NC
NO
1 2
Network priority
selection
Keypad selection (1 or 2)
Also possible via external contact using option
0: no network has priority
1, 0 or 2
( or )
1( )
1 2
Manual
Retransfer
Activation of the feature
Yes or No
No
1 2
type of control
logic selection
Impulse, contactor or breaker.
It might be necessary for some breakers not to set up
OMR and OMF timers to 0 (2 sec. for exemple).
Imp, con, brE
Imp
1 2
Number of
auxiliary contact
Depending on the number if available auxiliary contacts
(switch, contactor, breaker)
0, 2, 3
2
1 2
Parameter
1, return in
position 0
Allows to go to position 0 in case of voltage or frequency
outage (out if the defined U, f range)
Yes ou No
No
1 2
Parameter
2 return in
position 0
Allows to go to position 0 in case of voltage or frequency
outage (out if the defined U, f range)
Yes ou No
No
1 2
Number of 1
2 permutation
counter Reset
Allows source
➡
source automatic sequences counter
reset
Yes ou No
No
1 2
Programming
code
modification
Possible to change the programming code
from 0000 to 9999 1000
* Refer to annexes