Exit
¤¤
Proc. -1999...4000
Dev. -1000...1000
Band 0...1000
2. level
3. level
Setting the PID operating properties.
Adjusting
input filter.
of
SPLo
SPHi
<
SPHi
SPLo
>
YLo
YHi
≤
Yhi
Ylo
≥
Operating time counter.
It measures the
state time in hours
On
A
B
C
H
F
H
F
G
G
E
E
*
=2
,3
,4
,5
*
= 2, 3, 4, 5
0....6
0....13
D
B
A
D
¤
¤
¤
¤¤¤
Current output: 35(+) and 36 terminals
Voltage output: 36(+) and 37 terminals
C
1. level
Enter
Present set-point (read only)
Present control output % (in auto mode read only)
The ordinals of patterns
see model
identification
The hysteresis of the ALARM*
in unit of SP
Limits
Symmetric
0...1000
Asymmetric -1000...1000
B.
T
able
[3]=0
The value of the ALARM
*
in unit of SP
Limits
G.
T
able
[7]=1
Deleting of the maximum difference (PV-SP) from memory
Set the value from 0 up to 100 and exit with
key
The minimal control deviation since the last delete. Read only.
The maximal control deviation since the last delete. Read only.
Under the SP
Above the SP
Exits from configuration mode
Enters in the 2. level at GAin menu item
keys in configuration
when a menu item is
flashing, returns here
pressing the
Gain in %-ban (The attribute: p. Limits 0.0-100.0%)
The proportional band of the control loop in the unit of SP: P=100/p%
For ON-OFF control: GAin=0.0
¤¤
Setting the a
ON-OFF control
symmetrical hysteresis for
Reset time [s]
Limits 0 to 1000 s
Derivative time [s]
Limits 0 to 1000 s
Manual reset to eliminate the PD control (int=0) offset
For PD control int=0
For Asymmetric hysteresis
int=1 GAin=0 dZon=0
¤¤
Limits : ±1000
Return
Returns to the 1. level at menu item SP
Dead zone for valve positioning motor, or symmetrical
hysteresis for ON-OFF control (in SP unit)
Limits:
0...1000
Enters in the 3. level at inP menu item
Types of input. Setting the decimal point and filter.
The offset of PV, in the unit of SP
(For lead resistant compensation and calibration)
Limits: ±1000
Scale low
(A. table *****11* inputs only)
Setpoint low
See
A. Table
Setpoint adjust disable. E-HL error disable. User input selecting.
The properties of output actuators. See
B. Table
Limits: -1999...4000
Limits: -1999...4000
Scale high
(A. table *****11* inputs only)
Limits: -1999...4000
Setpoint high
Limits: -1999...4000
Cycle time of control output (Y) in seconds.
Valve travel time from open to close.
Below Yd’ the motor does not start to rotate (recommended: 1-5)
Limits: 0...255 s
The maximal value of Y (%) if EPid[2]=1
Yt=1 for SSR
Below YLo the Y=0. Limitation of the control output
Limits: 0...100 (1. level/Y shows the unlimited value!)
Over YHi the Y=100. Limitation of the control output
Limits: 0...100 (1. level/Y shows the unlimited value!)
The properties of the analogue output
The low value of linear output
(E.g. for 0 mA » 0 °C)
The high value of linear output
(E.g. for 20 mA » 1000 °C)
Reset the factory settings.
There is not a linear output if LiLo=LiHi
Current output: 35(+) and 36 terminals
Voltage output: 36(+) and 37 terminals
The properties of ALARM ( relay, or *OPC ).
See
* *
E. Table
Communication
See
G. Table
Detailed in Communication Manual
Logical OR or AND of ALAM2 and ALARM3 to
ALARM4 and ALARM5. See
F. Table
MODBUS address
0...255
Master address : 255
Properties of patterns
See
H. Table
Return
Returns to the 2. level at menu item GAin
1. page
ME160-5
Notation
Refers to a menu item or setting: e.g. 1.p/3.level/LiLo
first page, 3.level, LiLo menu item
®
Refers to a table: e.g. 1.p/out[54]=01
®
1. page, B. table, 5 and 4 switches are in 01 state
*
is instead of a number
and
refers to the coherent menu items and settings
The EDS notations :
= 00110011 (1=ON, 0=OFF)
• How to tune.
Make an impulse on the 8-9 terminals. The controller tunes the parameters at the SP.
If the overshot may damage the process limit the output (Y) in 1.p/3.level/Yd’ and set 1.p/EPid[2]=1.
Let ALARM3 1.p/A3d[****3210]=****1010 and let the value of 1.p/1.level/A3 a little higher than the expect-
able biggest overshot.
There are two tuning method for motorized valve control. If 1.p/3.level/Yt<15 the tuning do not use the
travel time. If
the controller uses the travel time written in
1.p/3.level/Yt>15
1.p/3.level/Yt.
¤
Shows the maximal and minimal values of the control deviation. Its useful for very long pro-
cesses like as cold-store, brooder house etc.
¤¤¤
There is a modulated sound at place of the relay or loudspeaker which can be acknowledged
and stoped by pushing the START botton.
¤
•
Cascade control. See
C. Table
See
D. Table
Cascade types.
dLin
LiLo
LiHi
SP
inP
GAin
Y
PrFL
SHFt
int
dEr
nrES
SPLo
dZon
SPHi
CnF
out
EPid
Yt
A*
Yd
A h
*
YLo
Pid -
YHi
-End
A d
*
A23L
con
Adr
-rEt
dE-r
dE L
dE H
rEt
PuHi
PuLo
dPrG
Ontc
Advance in profile with push-button
Reverse ALARM action
7
6 5 4 3 2
1 0
H. Table
EDS
dPrG
1
1
1
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
0
0
1
1
1
1
1
1
0
0
0
0
0
0
1
1
1
1
1
1
0
0
0
1
1
1
0
0
0
1
1
1
0
0
0
1
1
1
0
0
0
1
1
1
ALARM (relay) is active in soak and may be: PROC, DEV, BAND
Asymmetrical ALARM hysteresis: + upper, - lower
symmetrical
(0
)
ALARM is active in (±) RAMP
1. (
RAMP
±)
2. (±) RAMP
3. (±) RAMP
4. (±) RAMP
ALARM is active in waiting for SOAK (hidden FrEE)
1. waiting for SOAK (hidden FrEE)
2. waiting for SOAK (hidden FrEE)
3. waiting for SOAK (hidden FrEE)
4. waiting for SOAK (hidden FrEE)
ALARM is active in SOAK
1. SOAK
2. SOAK
3. SOAK
4. (±) RAMP
0
0
1
1
1
1
1
1
1
0
0
1
1
1
1
1
1
1
1
0
0
0
0
0
0
0
0
Active in
state only
On
Operational
feature
of the ALARM
Instrument
events
Events
by
the
type
of
profile
step
The
e
vents
(activated
relay)
a
re
valid
in
the
p
rogram
steps
named
on
the
left.
1
1
ALARM is active at the End command for 1s
ALARM is active when the controller is
(control mode) state
On
ALARM is active when the controller is
or START delay state
On
ALARM is active when the controller is in START delay state
Profile with 4 program-steps
The START delay value will be erased at its end.
Shows the remaining time when polling. (0
elapsed)
®
Changing the data of profile is prohibited in
state
On
Time base HH:MM (hour:minute), measured in unit/hour
Increasing (+) RAMP enable only
1
0
0
1
0
0
1
ALARM is valid in profile
(in profiles 0 and even also)
I
II
I
and
R2
»
2 relay
R3
»
3 relay
AL
ALARM
*
*
»
1
Model identification:
0
***
Model
identification:
1
***
Model
identification:
2
***
0
0
0
0
1
1
1
1
0
0
0
1
0
1
1
7 6 5 4 3 2
1 0
C. Table
EPid
EDS
0
1
1
1
1
PID-A D is formed from control deviation (x = PV - SP)
e
PID-B
(PV)
D is formed from process value
PID
PI automatic switching at small control deviation
®
Output is limited by 3.level/A3d. Value in 3.level/Yd’
The effect in the 3.level/inp[3] selected filter decreases.
R2 = AL2 without function
R3 = AL3 without function
R2 = AL2 or AL4 or AL5
R3 = AL3 or AL4 or AL5
R2 = AL2 or AL4
R3 = AL3 or AL4
R2 = AL2 or AL5
R3 = AL3 or AL5
R2 = AL2 and AL4
R3 = AL3 and AL4
R2 = AL2 and AL5
R3 = AL3 and AL5
R2 = AL2 or (AL4 and AL5)
R3 = AL3 or (AL4 and AL5)
R2 = AL2 and (AL4 or AL5)
R2 = Sign, may stop by START
R3 = AL3 and (AL4 or AL5)
7
7
6
6
5
5
4
4
3
3
2
2
1
1
0
0
E. Table
ALARM2
Bool functions of
0
0
0
0
0
0
0
0
0
0
1
1
0
0
1
1
0
0
0
0
1
1
1
1
1
1
0
0
0
0
1
1
0
0
1
1
1
1
1
1
0
0
1
1
1
1
1
1
E. Table
ALARM3
Bool functions of
1
1
R3 = Sign, may stop by START
Default input filter 14s
if EPid[7]=1 than 0s
Strong input filter
24s
if EPid[7]=1 than 7s
0
0
0
0
0
0
0
0
0
0
0
0
1
1
1
1
1
1
1
1
1
1
1
1
0
0
0
0
1
1
1
1
0
0
0
0
0
1
1
1
1
1
6
5 4
3 2 1 0
A. Table
inp EDS
PV without rounding
PV rounding to
5
1
0
Temperature unit CELSIUS
Temperature unit FAHRENHEIT
Decimal Point Positioning: none
Decimal Point Positioningt ***.*
Decimal Point Positioning **.**
Decimal Point Positioning *.***
T
J
K
S
Pt100/385 (DIN)
KTY thermistor (accessory)
0-20 mA
0-2000 Ohm 0-200 mV
4-20 mA
7
(Cu-CuNi)
(Fe-CuNi)
(NiCr-Ni)
(PtRh10-Pt)
-50......850
-40......200
0....2000
0....2000
-50......900
-50....1000
-50....1300
-50....1760
for temperature inputs only
scaleable
1
Shaded sensors are valid
-50.... 840
-40.... 150
-50......400
-50......900
-50....1300
-50....1600
(NiCr-CuNi)
(Fe-CuNi)
(NiCr-Ni)
(PtRh13-Pt)
JPt100/392
Ni100
PV rounding to 10
PV rounding to 50
for scaleable inputs only
L
N
R
E
Thermocouples
0
0
1
1
0
1
0
1
7 6 5 4 3 2
1 0
B. Table
out EDS
1
1
1
0
1
Changing the data of profile is prohibited
E-HL error message enabled when SPLo-5%
PV
SPHi+5%
≥
≥
Starts the Auto-tune
see foot-note
•
The A and A h do not appear in the 1. level, but their values are valid
*
*
Reverse action (for heating)
Direct action (for cooling)
1
1
1
1
0
0
0
0
Changing control relays 1
3 (for SSR recommended)
»
Control with relay
Valve positioning control 1. type
Described on the 2. page
User inputs
Valve positioning control 2. type
Program START with push-button
Program START and STOP with push-button
0
1
0
1
1
0
1
1
1
1
0 1
7 6 5 4 3 2
1 0
D. Table
dLin
EDS
4-20 mA (1-5 V, 2-10 V) analogue output range
0-20 mA (0-5 V, 0-10 V) analogue output range
Process value (PV) on the analogue output
Control output value (Y) on the analogue output
Set-point value (SP) on the analogue output
Factory default settings reset
All of profile data erasing
1
Indefinite soak enabled (S=On)
The
resets and restores 0000
1
0 1
0
(They operates in OFF state only)
7 6 5 4 3 2
1 0
E. Table
A d
EDS
*
PROCESS type ALARM action
DEVIATION type ALARM action
BAND type ALARM action
ALARM is active when an error message is on
ALARM is active during the tune
ALARM is valid in profile
(in profiles 1 and odd also)
II
ALARM is valid in profile and
(in all profiles also)
I
II
7
6 5 4 3 2
1 0 G. Table
EDS
(
con
543210 in Communication Manual)
dE-r dE L dE H menu items are enabled (see in 1. level)
Waiting for SOAK (hidden FrEE) disabled
1 pc profile
1 pc profile
2 pc profiles
Profile with 4 program-steps
Profile with 8 program-steps
Profile with 4 program-steps
1 pc profile
Profile with 8 program-steps
2 pc profiles
Profile with 16 program-steps 1 pc profile ( )
I II
Profile with 4 program-steps
14 pc profiles
Profile with 8 program-steps
7 pc profiles
Profile with 16 program-steps ( )
I II
3 pc profiles
Time base MM:SS (minute:second), measured in unit/minute
Increasing (+) RAMP and decreasing
enable
(-) RAMP
Normal broadcast communication for multichannel master
Cascade control-master device
Delta
cascade-control
device
T
master
0
1
0
1
1
Cascade control MASTER
0
0
Thermocouples
I
H
G
A
R