background image

 

 

 

 

Page 13 of 21

 

 

 

Figure 13

 

6.2

 

Adding a Line Card 

The HC-228S Master Station is supplied with at least 

one number

 Line Card.  There are 2 lines per 

Line Card.   

Before adding a Line Card, ensure that the HC-228S Master Station is not powered. If the HC-228S 
Master Station is powered, then power down the HC-228S Master Station (see 5.9).  

To fit the Line Card: 

1.

 

Place Line Card in the next available space on the Exchange PCB and secure using 
the supplied screw.   

2.

 

Remove the line terminal and connect the field wiring.  

3.

 

Push the terminal into the correct position on the Line Card.  

4.

 

Set the dipswitch on the Display PCB (see 6.1) to enable Line Card monitoring.   

Once the Line Card is securely fitted, power up the HC-228S Master Station (see 5.8).  

6.3

 

Removing a Line card 

Before removing a Line Card, ensure that the HC-228S Master Station is not powered. If the HC-228S 

Master Station is powered, then power down the HC-228S Master Station (see 5.9).  
 

To remove the Line Card: 

1.

 

Remove all line terminals from the Line Card that is to be removed. 

2.

 

Remove the securing screw. 

3.

 

Remove the Line Card from Exchange PCB. 

4.

 

Set the dipswitch on the Display PCB (see 6.1) to disable Line Card monitoring. 

Once the Line Card has been removed, the HC-228S Master Station may be powered (see 5.8). 

7.

 

System Menus 

 

7.1

 

Login Procedure 

For access level 2 (User) the code is 1664, for access level 3 (Engineer) the code is 1812. Enter the 

relevant code using the numbered buttons 1-8, as each button is pressed the user LED will flash 
cyan/magenta faster until the required code is entered, at which point LEDs 1-3 will illuminate cyan for 

User mode and LEDs 1-5 will illuminate magenta for Engineer mode.  

7.2

 

Fault Accept 

Before accepting faults, the fault must be noted in the logbook, along with the time the fault was 
reported.    
To accept the fault, enter either the access level 2 (code: 1664) or access level 3 (code: 1812) menu, 

then press zone button 1.   The buzzer will silence, and the general fault LED will now go steady.  
Press zone button 8 to exit this menu and to return to the menu options. 

The buzzer will resound on each new fault and after 8 hours. 

Содержание Haescomm HC228-S

Страница 1: ...Page 1 of 21 Haescomm HC228 S EVCS Master Station Installation and Commissioning Manual Version 1 May 2022...

Страница 2: ...5 9 Powering down procedure 11 6 Set up procedure 11 6 1 HC 228S Master Station Display PCB Dipswitch Settings 12 6 2 Adding a Line Card 13 6 3 Removing a Line card 13 7 System Menus 13 7 1 Login Proc...

Страница 3: ...ty Fire telephone systems are recommended for all public buildings and multi story buildings over four floors that require phased evacuation as per BS 9999 2017 Disabled Refuge systems are required in...

Страница 4: ...UNIT MUST BE EARTHED Warning NO USER SERVICEABLE PARTS Each HC 228S Master Station requires local isolation with verification as per the Electricity at Work Regulations 1989 returning to a B6A breaker...

Страница 5: ...Use the 2 5mm AF Hex Key supplied to open the right hand front cover Verify the following items are present Correct number of Line Card depending on configuration c w 2 way line connectors 1 number 3...

Страница 6: ...are 14 knockouts on the top and 2 slotted entries with a dedicated mains supply entry at the rear If a knockout is removed by mistake fill the hole with a good quality cable gland Figure 3 Unused knoc...

Страница 7: ...stations and must use enhanced grade cabling throughout for all wiring including the mains supply to the HC 228S Master Station 5 3 2 Disabled Refuge EVC System For buildings less than 30m in height o...

Страница 8: ...at Work Regulations 1989 returning to a B6A breaker clearly marked EMERGENCY VOICE COMMUNICATION SYSTEM DO NOT TURN OFF 5 5 Battery Information In the event of mains failure BS 5839 9 2021requires bat...

Страница 9: ...ne number Dual line card One outstation per line output can be connected If no outstation is connected to the line output then an end of line 10k resistor should be fitted The dipswitch located on the...

Страница 10: ...ock in the controller and the earth stud in the Type A outstation 5 6 2 Type B outstation Figure 7 Note The Earth screen should be sleeved and connected to the terminal block in the controller and the...

Страница 11: ...Call emergency assistance alarm systems continuing to operate Calls from Type B outstations automatically time out after approximately 30 minutes It is advised that this feature is not used as the sys...

Страница 12: ...Line 1 2 Line 3 4 Line 5 6 Line 7 8 NA NA NA Reserved Remarks NA NA NA Line card 1 fitted NA NA NA Line card 1 2 fitted NA NA NA Line card 1 2 3 fitted NA NA NA Line card 1 2 3 4 fitted Figure 11 Dips...

Страница 13: ...ard 1 Remove all line terminals from the Line Card that is to be removed 2 Remove the securing screw 3 Remove the Line Card from Exchange PCB 4 Set the dipswitch on the Display PCB see 6 1 to disable...

Страница 14: ...delay period the relay will not operate and the timer will cease The above function works identically with the Assist Call emergency assistance system Enter the access level 3 code 1812 then press but...

Страница 15: ...t back to requesting a call and the zone LED will flash red to indicate this The call MUST be ended at the outstation 8 4 Putting a call on hold To put a call on hold press the zone button to select o...

Страница 16: ...ound on each new fault 8 8 Panel Indicator Test To test the panel indicators enter either the access level 2 code 1664 or access level 3 code 1812 menu then press zone button 2 All LEDs will illuminat...

Страница 17: ...logged in Magenta Engineer logged in Flashing green Call connected Flashing Red Green Call on hold Solid Yellow Master handset short circuit Figure 16 9 4 Zone indicator summary Zone Indicator Status...

Страница 18: ...be performed when the system is complete and the building has normal background noise levels The intelligibility test requires two personnel One person should be present at the master station the oth...

Страница 19: ...ntre above the display PCB the outstation zone template can be inserted here The template is in Word format and can be downloaded at www haes tech com Go to downloads section This can be completed pri...

Страница 20: ...Page 20 of 21 Notes...

Страница 21: ...re radial 1mm or 1 5mm Distance 500m from master station OUTPUTS Number 2 Fault In use Fault Relay 1 Volt free NC Com 30V DC 1A In Use Relay 1 Volt free NO Com 30V DC 1A CONTROLS AND INDICATIONS Butto...

Отзывы: