Conventional Sounder Circuit Responses to Selected Zones
Each of the conventional sounder circuits on the main circuit board can be independently programmed to
respond in one of three different ways for each zone, ON, OFF or PULSING.
Enter the above code and press the ENTER button.
The zone 1
fi
re LED will light. This indicates setting how each of the
sounder circuits are to respond for zone 1.
The amber, fault LEDs will show the current sounder circuit settings for
that zone. See table below
Use button 1 to move to the zone that requires editing.
With the required zone for editing LED lit, press the ENTER
button to enter ‘editing mode’.
The
fi
re zone 1 LED will now pulse to indicate setting the response of the
fi
rst sounder circuit (SNDR1 on
main circuit board) for the selected zone.
Use button 1 to scroll to the sounder circuit that requires editing, inidicated by a pulsing
fi
re LED 1 - 4 as
per table below.
The setting of the sounder circuit is indicated by the amber, fault LED, ON, OFF or PULSING.
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
LED 1
LED 2
LED 3
LED 4
SNDR1
SNDR2
SNDR3
SNDR4
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Use button 2 to change the response of the sounder circuit for the
selected zone, ON, OFF or PULSING, indicated by the amber, fault
LED, then use button 1 to move to the next output if required.
Press the ENTER button to return back to the zone selection, indicated
by a steady zone
fi
re LED
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
When
fi
nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 2 to ‘OFF’.
Tip - You can use button 4 to change the response of all sounder
circuits simultaneously to ON, OFF or PULSING (for faster
programming).