XL32 Installation, Commissioning & Operating Manual
Approved Document Ref: UI-XL32-01 Issue 3.0
41
SETUP & PROGRAMMING
4
2
4
2
Relay & Output Responses to Selected Zones
Each of the relays and switched -ve outputs on the main circuit board can be independently programmed
to respond in one of three different ways for each zone. The options are ON, OFF or PULSING.
Note:- (Before any programming can be applied to the outputs on the main circuit board, they must
fi
rst be made programmable. See programming option 4-1-4-2).
Enter the code, 4-2-4-2 and press the ENTER button.
The zone 1
fi
re LED will light. This indicates setting how each of the
outputs are to respond for zone 1.
The amber, fault LEDs will show the current output settings for that zone.
See table below
Use button 1 to move to the zone that requires editing.
With the required zone for editing LED lit, press the ENTER
button to enter ‘editing mode’.
The
fi
re zone 1 LED will now pulse to indicate setting the response of the
fi
rst output (
fi
re relay on main
circuit board) for the selected zone.
Use button 1 to scroll to the output that requires editing, inidicated by a pulsing
fi
re LED 1 - 4 as per table
below.
The setting of the output is indicated by the amber, fault LED, ON, OFF or PULSING.
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
LED 1
LED 2
LED 3
LED 4
LED 5
LED 6
Fire Relay
Fault Relay
Fire O/P
Fault O/P
Gen Dis O/P Reset O/P
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Use button 2 to change the response of the output for the selected
zone, ON, OFF or PULSING, indicated by the amber, fault LED, then
use button 1 to move to the next output if required.
Press the ENTER button to return back to the zone selection, indicated
by a steady zone
fi
re LED
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
When
fi
nished, press and hold Button 1 for 3 seconds to save setting and exit programming mode
Enter the next programming code or disable the controls and return DIL switch 2 to ‘OFF’.
Tip - You can use button 4 to change the response of all outputs
simultaneously to ON, OFF or PULSING (for faster programming).
www.acornfiresecurity.com