Installation, Commissioning &
Operating Manual
EN54 APPROVED 16 - 32 ZONE CONVENTIONAL
CONTROL PANEL
Approved Document UI-XL32-01 Issue 3.0
810a/08
S o f t w a r e V e r s i o n 4 . 0 & A b o v e
www.acornfiresecurity.com
Страница 1: ...ssioning Operating Manual EN54 APPROVED 16 32 ZONE CONVENTIONAL CONTROL PANEL Approved Document UI XL32 01 Issue 3 0 810a 08 S o f t w a r e V e r s i o n 4 0 A b o v e www acornfiresecurity com www acornfiresecurity com ...
Страница 2: ...hecks as specified in BS 5839 Part 1 It is the responsibility of the system user to ensure it is regularly serviced and maintained in good working order system user to ensure it is regularly serviced and maintained in good working order Disclaimer Disclaimer No responsibility can be accepted by the manufacturer or distributors of this fire alarm panel for any No responsibility can be accepted by t...
Страница 3: ...TIONS 13 GENERAL 13 MOUNTING THE CABINET 13 MAINS CONNECTIONS 14 CONNECTING THE BATTERIES 15 SETUP PROGRAMMING 16 NETWORK PANELS SETUP 16 ZONE INTERFACE FUNCTION 18 LEVEL 3 ENGINEERING MODE 19 LEVEL 3 ENGINEERING OPTIONS INDEX 20 OPERATING 52 PANEL CONTROLS INDICATIONS 52 DISABLE MODE 54 TEST MODE 55 FAULT DIAGNOSIS 56 FUNCTIONALITY DURING A SYSTEM FAULT 57 SERVICE MAINTENANCE 58 THE NEED FOR MAIN...
Страница 4: ...y programmable and there are options to have delays to the outputs The All inputs and outputs are fully programmable and there are options to have delays to the outputs The programming features of the Excel 32 also include 3 different modes to help reduce false alarms Local programming features of the Excel 32 also include 3 different modes to help reduce false alarms Local fire authorities are de...
Страница 5: ...n Commissioning Operating Manual Approved Document Ref UI XL32 01 Issue 3 0 3 ABOUT THIS PANEL CABINET 107mm 130mm 410mm 465mm 450mm 400mm 450mm Fire Detection System www acornfiresecurity com www acornfiresecurity com ...
Страница 6: ... ZONE7 ZONE8 ZONE9 ZONE10 ZONE11 ZONE12 ZONE13 ZONE14 ZONE15 ZONE16 28V 1 2 3 ON 0V INPUTS RS SA PUL CC SW V OUTPUTS RS GD FLT FR TX RX 0V 28V 0V 28V ZONE21 ZONE22 ZONE23 ZONE24 ZONE25 ZONE26 ZONE27 ZONE28 ZONE29 ZONE30 ZONE31 ZONE32 COMS A COMS B 28 V SW ve OUTPUTS 1 2 3 4 5 6 1 2 3 4 ON ADDRESS 1 2 3 4 ENTER RESOUND SILENCE RESET TPCA11 Master PCB TPCA05 Comms PCB TPCA10 LED Display Controls PCB...
Страница 7: ...itored sounder circuits fused 500mA Conventional fire zone circuits current limit max 50mA 4K7 EOL Conventional fire zone circuits current limit max 50mA 4K7 EOL Conventional fire zone circuits current limit max 50mA 4K7 EOL Conventional fire zone circuits current limit max 50mA 4K7 EOL Conventional fire zone circuits current limit max 50mA 4K7 EOL Conventional fire zone circuits current limit max...
Страница 8: ... fault relay contact Clean C O Max 3A 30vdc Unfused Outputs FR fire FLT fault RS reset GD general disablement Switched ve voltage outputs for relay control Overload voltage protected to 52vdc Current limited 680R Max load 40mA Inputs CC PUL SA RS Switched ve inputs connect to 0v to trigger Max input voltage 28vdc Non latching max resistance 100R Protected via 10K Ohm impedance 3v6 zener diode SNDR...
Страница 9: ...18 12B 17 2Ahrs for LPCB approved panels Other equivalent batteries may be used but have not been tested for the purposes of EN54 approval Battery charging voltage 27 3 vdc nominal at 20 deg C Temperature compensated Battery charging output current 5 0A PSU 2A Current limited 2 Amps Battery high impedance fault Batt Hi Z Resistance 1 Ohm 1 hour reporting time Max current drawn from batteries 7 5 A...
Страница 10: ...f 112m2 per device When mounted on a flat ceiling heat detection devices have an individual coverage of 5 3m radius However these radii must overlap to ensure there are no blind spots Therefore individual coverage can be represented by a square measuring 7 5m x 7 5m giving an actual coverage of 56 3m2 per device Call Points A person should not have to travel more than 45m along an escape route to ...
Страница 11: ...h that cable The screen or drain wire of circuits should be bonded to earth at recommended for use with that cable The screen or drain wire of circuits should be bonded to earth at one location only and should be continuous throughout the circuit Drain wires should be terminated in the one location only and should be continuous throughout the circuit Drain wires should be terminated in the cabinet...
Страница 12: ...RAL DETECTION CIRCUIT SCHEMATIC REMOTE INDICATOR RIL58 _ 4K7 OHM END OF LINE RESISTOR ZONE 1 R L1 L1 L2 IN OUT R L1 L1 L2 IN OUT R L1 L1 L2 IN OUT APOLLO S65 BASE 45681 201 APOLLO S65 BASE 45681 201 APOLLO S65 BASE 45681 201 MANUAL CALL POINT MCP1A R 470 1 2 3 4 _ _ 470 www acornfiresecurity com www acornfiresecurity com ...
Страница 13: ...sue 3 0 11 DESIGN CONSIDERATIONS GENERAL SOUNDER CIRCUIT SCHEMATIC 4K7 OHM END OF LINE RESISTOR SNDR1 MOTORISED BELL POLARISED MOTORISED BELL POLARISED ELECTRONIC SOUNDER POLARISED ELECTRONIC SOUNDER POLARISED VE VE VE VE VE VE VE VE www acornfiresecurity com www acornfiresecurity com ...
Страница 14: ...ons of the Act you are therefore requested to take such steps as are necessary to According to the provisions of the Act you are therefore requested to take such steps as are necessary to ensure that any appropriate information about this product is made available by you to anyone concerned ensure that any appropriate information about this product is made available by you to anyone concerned with...
Страница 15: ...nd must be segregated away from mains voltage Any junction boxes used should be clearly labelled FIRE ALARM Any ancillary devices e g door retaining magnets must be powered from a separate power source Any coils or solenoids used in the system must be suppressed to avoid damage to the control equipment The site chosen for the location of the panel should be clean dry and not subject to shock or vi...
Страница 16: ...l using the ring crimp provided Sufficient earth lead should be left to allow Live and Neutral connections to be accidentally pulled from the terminal block while leaving the earth connection intact PSU FAULT C NC NO 0V 0V 0V 30V 28V 0V 28V PSU A PSU B TX RX PSU 5 3 Low voltage detection and sounder circuit wiring Incoming mains wiring PSU PSUINB PSUINA 28V 0V C NC NO C NC NO FIRE FAULT SNDR1 SNDR...
Страница 17: ... If the fault doesn t clear after 1 minute check connections The battery charging voltage is factory calibrated to 28 2vdc 0 2v 0o C This should not normally require adjustment Where battery problems are experienced the following information should be considered a If a battery is disconnected from the charger no voltage will appear on the output leads or terminals due to intelligent battery contro...
Страница 18: ...k is defined by setting a switch on the main PCB In the case of the Excel 32 this is switch 3 on the 3 way DIL switch OFF Stand Alone mode ON Network Repeater mode With this switch in the ON position the panel will automatically recognise operate the Comms PCB TPCA05 Disconnect display board comms ribbon cable Plug Comms PCB into the display comm socket and re connect dispay board ribbon cable to ...
Страница 19: ...B and back to the Master panel again see drawing below This enables the network to still function if there is a break in the cables If replacing an older system where the existing cabling cannot be configured in a loop as above it is possible to change the panel settings to legacy radial circuit comms monitoring See panel wide programming settings code 2 1 2 3 option 6 Change Network Repeater Comm...
Страница 20: ...3 engineering programming to setup any zone for this function however this is simply a shortcut method The function is enabled by setting switch 1 on the 3 way DIL switch located on the main PCB to the ON position With switch 1 in the ON position the last zone becomes 1 1 Non latching Non latching 2 2 Non aux operating Non aux operating ZONE INTERFACE FUNCTION 1 2 3 ON ZONE2 ZONE3 ZONE4 C NC NO NO...
Страница 21: ...Level indicator will pulse to signify that Level 3 access is active Programming throughout the panel is carried out in a sequence where the fire LEDs indicate the options to set and the fault disabled test LEDs indicate the status of these settings Generally button 1 is used to scroll the indications button 3 can also be used to scroll backwards Pressing and holding button 1 for 3 seconds at any t...
Страница 22: ...removal monitoring type for zone Schottky or Zener diode detector bases Sprinkler pump monitoring function 3121 30 Dependancy Mode False Alarm Management Set panel zones to dependancy mode A B or C 2114 2124 2134 34 EN54 Sounder Resound Options Set zones to not resound alarms after an initial fire condition 1114 37 Delays to Outputs Apply delays to outputs in response to selected zones 2323 38 Inp...
Страница 23: ...ENTER button continuously Sounder circuit faults If a sounder circuit fault is displayed pressing and holding the ENTER button will reveal which sounder circuit was at fault This is indicated by the fire LEDs 1 4 as per the table below Repeater faults If a repeater fault is displayed pressing and holding the ENTER button will reveal the following further information The Repeater Fault LED indicate...
Страница 24: ...r circuit output or delay will now be enabled The panel will bleep to acknowledge the reset When finished enter the next programming code or disable the controls and return DIL switch 2 to OFF RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps 2 2 2 4 Set Fault Buzzer Volume RESOUND SIL...
Страница 25: ...SET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps When finished enter the next programming code or disable the controls and return DIL switch 2 to OFF Fire LED pulsing LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 LED 7 Attribute PSU Comms Disable Battery Monitoring Enable Hi Z Monitoring 18Ah Battery 12Ah Batter...
Страница 26: ...pad can be used to activate the panel controls instead of using the key switch The default code is 1 2 3 4 however this can be changed It is also possible to disable the use of a code entry to enable controls forcing the use of the key switch only With the zone 1 fire LED lit press the ENTER button Zone 1 fire LED will pulse to indicate edit mode and the amber fault LEDs will start to rapidly puls...
Страница 27: ... and hold button 1 for 3 seconds to exit programming mode 2 1 2 3 The panel delay time for all outputs is set here To actually apply the delay to the desired outputs see programming code 2 3 2 3 The default setting is 3 minutes but can be changed to between 1 10 minutes With the zone 3 fire LED lit the amber fault LEDs will show the current time set The time is represented by a binary code using L...
Страница 28: ...ing default fault LED 1 ON legacy radial circuit monitoring Press the ENTER button zone 6 fire LED will pulse to indicate edit mode Now use button 2 to change the setting indicated by the amber fault LED ON or OFF as per above When finished press the ENTER button again and the zone 6 fire LED will return to steady view mode Press button 1 to move to next option or hold button 1 for 3 seconds to ex...
Страница 29: ...added or OFF removed Option to inhibit the intermittant beep that still occurs when a fault or fire tone has been muted using the Mute Buzzer button With the zone 8 fire LED lit Press the ENTER button The zone 1 fire LED will pulse edit mode Press button 1 to light the zone 1 fault LED Beeps are now silenced When finished press the ENTER button again and the zone 7 fire LED will return to steady v...
Страница 30: ... Network Alarms Faults For Panel This option prevents any other network panel s alarms or faults from displaying or having any effect on the panel The default setting is ON panel displays all network alarms faults and the outputs respond accordingly If set to OFF alarms faults from other network panels will be ignored Fires faults from this panel will still affect other network panels accordingly ...
Страница 31: ...EDs Use buttons 1 3 1 forward 3 backward to move the pulsing fire LED to the required zone as per above Then use button 2 to Disable or Activate the buzzer indicated by the amber fault LED Fault LED OFF Buzzer Active Fault LED ON Buzzer Disabled Tip You can use button 4 as a shortcut to add or remove all 7 addresses in one go When finished press the ENTER button again and the zone 10 fire LED will...
Страница 32: ...the panel with no sounder operation Priority alarm EN54 Normally a 220R call point will override delays or dependency alarms This option allows turning off the priority alarm feature Detector removal EN54 The detector removal monitoring can be turned off For use with older non compliant detectors Detector removal type Schottky diode or Zener diode type detector bases for conventional zones Does no...
Страница 33: ...ter editing mode The fire zone 1 LED will now pulse to indicate the editing of attribute 1 fire latching for the selected zone Use button 1 to scroll to the attribute that requires editing inidicated by a pulsing fire LED 1 9 as per table below The setting of the attribute is indicated by the amber fault LED ON or OFF Use button 2 to switch the attribute ON or OFF indicated by the amber fault LED ...
Страница 34: ...will not operate Alarm sounder circuits will not operate The indication is non latching Gate valve closed via 470 resistor The panel will operate as per open or short circuit fault except that General Fault LED remains off Fault output routing will not operate Valve out of service via 4K7 EOL only This equates to a quiescent condition and the zone will give no indication Fire pump status monitorin...
Страница 35: ... Zone Function Settings programming mode 3 1 2 1 With the required zone for editing LED lit press the ENTER button to enter editing mode The fire zone 1 LED will now pulse to indicate the editing of attribute 1 fire latching for the selected zone Use button 1 to scroll to pulsing fire LED 8 gate valve fire pump indications Then use button 2 to set the status required for that zone indicated by the...
Страница 36: ...t the control panel but not activate the sounders The first detector alarm will indicate at the control panel but not activate the sounders 2 2 The panel resets and re checks the inhibited zone within 1 4 minutes programmable see code The panel resets and re checks the inhibited zone within 1 4 minutes programmable see code 2 1 3 4 2 1 3 4 1 1 3 3 If an alarm is detected then the panel activates a...
Страница 37: ...ndency mode Pressing ENTER again will de select the zone and the LED will change back to a slow pulse Press and hold button 1 for 3 seconds to save the settings and exit the programming mode Use button 1 to move the pulsing amber LED to the required type as per above and press ENTER to select it The LED will change to a rapid pulse to indicate that it is now the current setting Type C Configuratio...
Страница 38: ...re LED lit the amber fault disabled test LEDs will indicate the current timings set Press the ENTER button to enter edit mode and the fire LED will change to pulsing Now use buttons 1 3 to increase or decrease the time Button 1 increases button 3 decreases When finished press ENTER again to return to view mode The confirmation time 1 is indicated by the amber fault LEDs 1 4 1 4 minutes The auto re...
Страница 39: ...TER button again will toggle the status indicated by a rapid or slow pulsing LED see below Then use Button 1 to move to the next zone If the zone has been set to not resound alarms the LED will be off If kept as default new fire condition will resound alarms then the LED will be on steady Rapid Pulse Zone is under selection and is set to have alarms resound default Slow Pulse Zone is under selecti...
Страница 40: ...s between all sounder circuits all aux outputs or all sounder circuits and all aux outputs The selection is indicated by the Sounder Status LED and the Aux Output Status LED When finished programming for the zone press the ENTER button again to return to the zone selection indicated by a steady fire LED If a delay has been applied to a zone the Delay Status LED will be lit permanently to indicate ...
Страница 41: ...input Use button 1 to move to zone 2 3 or 4 fire LED for setting the function of the PUL RS SA inputs and then back to zone 1 again The current setting for the input will be indicated by the amber fault LEDs as per table below With the required fire LED lit as per above press the ENTER button to enter editing mode The fire zone 1 LED will now pulse to indicate function 1 Class Change Now use butto...
Страница 42: ...as F A R E signal F A R E Fire Alarm Routing Equipment To set either of the miscellaneous options above or to make outputs programmable enter the above code and press ENTER The fire zone 1 LED will now pulse to indicate the setting of attribute 1 fault latching Use button 1 to scroll to the attribute that requires setting inidicated by a pulsing fire LED 1 6 as per table below The setting of the a...
Страница 43: ...n 1 to scroll to the output that requires editing inidicated by a pulsing fire LED 1 4 as per table below The setting of the output is indicated by the amber fault LED ON OFF or PULSING RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps LED 1 LED 2 LED 3 LED 4 LED 5 LED 6 Fire Relay Fau...
Страница 44: ... inidicated by a pulsing fire LED 1 4 as per table below The setting of the sounder circuit is indicated by the amber fault LED ON OFF or PULSING RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps LED 1 LED 2 LED 3 LED 4 SNDR1 SNDR2 SNDR3 SNDR4 RESOUND SILENCE RESET ENTER 1 2 3 4 Disabl...
Страница 45: ...vacuate or 220Ω Evacuate call point Class Change Input Alert Input or during Zone Delays Enter the above code and press the ENTER button The zone 1 fire LED will light This indicates the sounder circuit to be programmed as per the table below Sounder CCT function table RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode...
Страница 46: ...Fault Relay Fire O P Fault O P Use button 2 to change the response for the output as per table above indicated by the amber fault LED ON or OFF Then use button 1 to move to the next function if required Fault relay output default to OFF Press the ENTER button to return back to the output selection indicated by a steady zone fire LED When finished press and hold Button 1 for 3 seconds to save setti...
Страница 47: ...g fire LED to the required circuit then use button 2 to change the response of the circuit indicated by the amber fault LED Each press of button 2 will toggle through the 3 available responses Amber LED ON Sounder circuit activates CONTINUOUSLY for other network panel fires Amber LED PULSING Sounder circuit PULSES for other network panel fires Amber LED OFF Sounder circuit NO RESPONSE for other ne...
Страница 48: ...LED See tables below Use button 1 to move the pulsing fire LED to the required relay or output then use button 2 to change the response indicated by the amber fault LED Each press of button 2 will toggle through the 3 available responses RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamp...
Страница 49: ...ame as with the other outputs and sounder circuits but using the above code I e Use button 1 to select the zone first indicated by a steady fire zone LED press ENTER and then use button 1 to select the output 1 6 to edit indicated by a pulsing fire zone LED 1 6 as per the table below Use button 2 to edit the response indicated by the amber fault LED ON OFF or PULSING LED 1 LED 2 LED 3 LED 4 LED 5 ...
Страница 50: ...er fault LED ON or OFF Then use button 1 to move to the next function if required Press the ENTER button to return back to the output selection indicated by a steady zone fire LED When finished press and hold Button 1 for 3 seconds to save setting and exit programming mode RESOUND SILENCE RESET ENTER 1 2 3 4 Disable Mode Test Mode Mute Buzzer Test Lamps Use button 1 to move the fire LED to the out...
Страница 51: ...n the panel will automatically exit the diagnosis mode Pressing button 2 will reveal the origin of a system fault indication Note After power up the system should be allowed to initialise for 2 3 minutes before using this code otherwise false indications could occur If in doubt re enter the code a second time to check Any differences shown here can then be investigated and corrected either by rest...
Страница 52: ...tem See panel wide settings 2 1 2 3 option 2 Set Number of Repeater Panels on System Addressing Each repeater panel needs to have a seperate address The addressing is done using the 4 DIL switches on each of the Comms PCBs using binary code values see diagram below The address should be set in sequence from 1 8 first repeater address 01 next repeater address 02 etc The control panel should always ...
Страница 53: ...n common fire and o p 2 is set to activate for common fault There are 4 programming options available for the inputs and outputs in the repeater panels Outputs 1 6 activate on common fire Outputs 1 6 activate zonally for zones 1 6 Outputs 1 6 activate zonally for zones 7 12 Change inputs CC PUL to power supply fault inputs It is also possible in this programming mode to disable the controls on rep...
Страница 54: ...four digit code using the keypad The use of a code entry to activate the controls is enabled by default but can be disabled in the Level 3 engineering functions To activate the controls using the key switch Turn the key clockwise to the On position The Access Level indicator LED will light and all buttons on the keypad will now be operational To deactivate the controls turn the key back to the Off...
Страница 55: ...Zones in Fire 1 32 N A Indicates alarm condition in zone Zone Fault Disabled Test 1 32 Indicates zone circuit is disabled or in test mode Indicates a fault in the zone circuit Supply Healthy Indicates mains and or battery supply is present N A General Fire N A Indicates panel is in alarm condition General Fault N A Indicates one or more faults are present General Disablement Indicates one or more ...
Страница 56: ...D Pressing the button once more will move the selection back to Zone 1 again When the desired circuit outputs or delays to be disabled is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the circuit between disabled and enabled Then use Disable Mode button again to move to the next circui...
Страница 57: ...e 1 again When the desired zone to be tested is indicated by a slow pulsing LED use the ENTER button to select it Once selected the indicator LED will change to a rapid pulse Pressing ENTER again will toggle the zone between in and out of test Then use Test Mode button again to move to the next zone Any or all zones can be in test mode simultaneously When at the sounder status position use the ENT...
Страница 58: ...est Mode Mute Buzzer Test Lamps LED Indicator State before pressing ENTER LED Pulsing after pressing ENTER LED Steady after pressing ENTER LED Off or Slow Pulse after pressing ENTER Location Zone 1 Fire LED off Sounder circuit 1 short circuit Sounder circuit 1 open circuit OK Main PCB SNDR 1 Zone 2 Fire LED off Sounder circuit 2 short circuit Sounder circuit 2 open circuit OK Main PCB SNDR 2 Zone ...
Страница 59: ...buzzer sound Main board is halted Fault relay is activated Repeater Comms Board System Fault LED continous and General Fault LED pulsing and Repeater Fault LED continous The Comms Board TPCA05 is halted Fault relay and output are active and repeater panels will cease to function Fire alarms can still be detected and controlled by the panel Power Supply Board System Fault LED pulsing General Fault ...
Страница 60: ...art of BS 5839 THE NEED FOR MAINTENANCE ROUTINE MAINTENANCE TESTING DUTIES OF THE RESPONSIBLE PERSON The system user needs to appoint a single named member of the premises management to supervise all matters pertaining to the fire detection and fire alarm system The role of this person is to ensure that the system is tested and maintained in accordance with the recommendations of BS 5839 Part 1 th...
Страница 61: ...ectrical contractor or fire alarm specialist Inspection servicing visits are normally conducted on a quarterly basis unless such factors as a dirty environment warrant servicing on a more regular basis The maximum period between inspections must not exceed six months Recommendations of BS5839 1 for periodic service visits include Every device on the system should be tested annually The testing of ...
Страница 62: ...STER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System XL32 Installation Commissioning Operating Manual Approved Document Ref UI XL32 01 Issue 3 0 60 www acornfiresecurity com www acornfiresecurity com ...
Страница 63: ...STER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System XL32 Installation Commissioning Operating Manual Approved Document Ref UI XL32 01 Issue 3 0 61 www acornfiresecurity com www acornfiresecurity com ...
Страница 64: ...STER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System XL32 Installation Commissioning Operating Manual Approved Document Ref UI XL32 01 Issue 3 0 62 www acornfiresecurity com www acornfiresecurity com ...
Страница 65: ...STER TIME OF TEST SCHEDULE OF TESTING This Section To Be Used To Record ALL Weekly Tests Of The Fire Alarm System XL32 Installation Commissioning Operating Manual Approved Document Ref UI XL32 01 Issue 3 0 63 www acornfiresecurity com www acornfiresecurity com ...
Страница 66: ...VISITS XL32 Installation Commissioning Operating Manual Approved Document Ref UI XL32 01 Issue 3 0 64 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details www acornfiresecurity com www acornfiresecurity com ...
Страница 67: ...VISITS XL32 Installation Commissioning Operating Manual Approved Document Ref UI XL32 01 Issue 3 0 65 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details www acornfiresecurity com www acornfiresecurity com ...
Страница 68: ...VISITS XL32 Installation Commissioning Operating Manual Approved Document Ref UI XL32 01 Issue 3 0 66 Fault Reason For Call Out Action Taken Date Work Completed Engineer s Details www acornfiresecurity com www acornfiresecurity com ...
Страница 69: ...at has caused the alarm A detector will have a red In the event of a false alarm look for the device that has caused the alarm A detector will have a red LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer LED lit or check to see if a call point glass is broken if so replace the glass or call an engineer 5 5 When fully satisfied that there is no fire...
Страница 70: ...www acornfiresecurity com www acornfiresecurity com ...