ASP-R Installation, Commissioning & Operating Manual
Approved Document Ref: UI-ASP-R-01 Issue 3.0
18
OPERATING
PANEL CONTROLS & INDICATIONS
8 Button Keypad For Controls
And Programming
Status Indicator LEDs
Activate Controls Key Switch
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
General Disablement
Test Mode
Sounder Status
Aux Output Status
Power Supply Fault
System Fault
Delay Status
Access Level
Repeater Fault
On
Off
Supply Healthy
General Fire
General Fault
Activate
Controls
Zones in Fire
Zone Fault / Disabled / Test
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Zones In Fault, Zones Disabled or
Zones In Test Indicator LEDs
Zonal Fire Indicator LEDs
Activate Controls
In normal standby mode the keypad controls are inactive to protect from unauthorised operation. Controls
can be activated by using the ‘Activate Controls’ key switch or by entering a four digit code using the
keypad.
The use of a code entry to activate the controls is enabled by default but can be disabled in the Level 3
engineering functions.
To activate the controls using the key switch;
turn the key clockwise to the ‘On’ position. The ‘Access
Level’ indicator LED will light and all buttons on the keypad will now be operational. To deactivate the
controls, turn the key back to the ‘Off’ position and the ‘Access Level’ indicator LED will extinguish.
If the key switch is in the ‘On’ position the keypad will remain active.
NOTE :
It is not possible to remove the key in the ‘On’ position.
To activate the controls using the keypad;
first push button 1 or button 2 to initialise the code entry
mode. The ‘Access Level’ indicator will pulse rapidly. After 30 seconds, if the code has not been entered,
the panel will return to standby mode.
With the ‘Access Level’ indicator pulsing, enter the four digit code using buttons 1 - 4. The factory default
code is 1-2-3-4 but can be changed in the engineering functions. After entering the four digit code press
the ‘ENTER’ button. The ‘Access Level’ indicator LED will change to steady and all buttons on the keypad
will now be operational.
If the wrong code has been entered the ‘Access Level’ indicator will continue to pulse. Enter the code
again and press the ‘ENTER’ button. If after 30 seconds the correct code has still not been entered the
panel will return to standby and button 1 or 2 will need to be pushed again to initialise code entry mode.
After activation by code entry, controls will automatically deactivate again after 2 minutes and the panel
will return to standby mode.
The test lamps and mute buzzer functions are operational without the need to activate controls.