ASP-R Installation, Commissioning & Operating Manual
Approved Document Ref: UI-ASP-R-01 Issue 3.0
16
SETUP & PROGRAMMING
Addressing
Each repeater panel needs to have a seperate address. The addressing is done using the 4 DIL switches
on each of the Comms PCBs using binary code values, see diagram below.
The address should be set in sequence from 1 - 8, first repeater address 01, next repeater address 02 etc.
The control panel should always be address 0 (all switches off).
1
2
3
4
ON
ADD 01
1
2
3
4
ON
ADD 02
1
2
3
4
ON
ADD 03
1
2
3
4
ON
ADD 04
1
2
3
4
ON
ADD 05
1
2
3
4
ON
ADD 06
1
2
3
4
ON
ADD 07
1
2
3
4
ON
ADD 08
2
1
2
3
Panel Wide Settings
There are 6 general, panel wide, settings available.
Enter the above code and press the ENTER button. The 6 programmable
options are represented by fire zone LEDs 1 - 6, Option 2 being the, ‘set
number of repeater panels’ setting.
Use button 1 to move to option 2
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
RESOUND
SILENCE
RESET
ENTER
1
2
3
4
Disable
Mode
Test
Mode
Mute
Buzzer
Test
Lamps
Fire LED Programming Option
1
Change / remove keypad access code
2
Set number of repeater panels on system
3
Set output delay time (1 - 10 minutes)
4
Turn off battery monitoring
5
Set up internal PCB configuration (add extension zone
card or repeater comms PCB)
6
Change repeater comms monitoring
2. Set Number of Repeater Panels on System
With the zone 2 fire LED lit, the amber, fault / disabled / test LEDs will show the current quantity of
repeaters set 0 - 8. (1 LED lit = 1 repeater, 2 = 2 etc..).
Press the ENTER button, zone 2 fire LED will pulse to indicate ‘edit mode’.
Now use buttons 1 & 3 to increase or decrease the quantity. Button 1 increases, button 3 decreases.
When finished press the ENTER button again and the zone 2 fire LED will return to steady ‘view mode’.
Press button 1 for 3 seconds to exit programming mode 2-1-2-3.
To set the number of repeater panels at the main control panel use: