Model 6 Motor Control Centers
80459-641-01E
Section 6—Maintaining the MCC
10/2012
© 1999–2012 Schneider Electric All Rights Reserved
66
ENGLISH
Insulation Test
Before an MCC is re-energized (after installation or regular maintenance),
take resistance measurements. Use an insulation tester (megohmmeter)
with a potential of 500–1000 V.
Take readings between each phase and from each phase to ground, with
the branch disconnects
off
and
on
. Make sure the main disconnect is
off
during all insulation tests.
Readings from a megohmmeter with all disconnects
off
will typically be
5–20 megohms. On new equipment that has been stored in a damp area,
lower readings may occur during start-up. If the readings are below one
megohm, a few branch units may be energized to help dry out the MCC. If
additional readings are above one megohm, additional units may be
energized. After the equipment has been in operation for 48 hours, readings
should be in the 5–20 megohm range.
When megohmmeter readings are taken with the disconnects
on
(except for the
main), disconnect all devices completing circuits between phases or between
phases and neutral (for example, control transformers). Although readings may
be slightly different, observe the one megohm lower limit during start-up.
DANGER
HAZARD OF ELECTRIC SHOCK, EXPLOSION, OR ARC FLASH
• Apply appropriate personal protective equipment (PPE) and follow safe
electrical work practices. See NFPA 70E or CSA Z462.
• This equipment must only be installed and serviced by qualified
electrical personnel.
• Turn off all power supplying this equipment before working on or inside
equipment.
• Always use a properly rated voltage sensing device to confirm power is off.
• Replace all devices, doors, and covers before turning on power to this
equipment.
Failure to follow this instruction will result in death or serious injury.
NOTICE
HAZARD OF EQUIPMENT DAMAGE
• Do not use a megohmmeter on:
– adjustable speed drives
– solid state soft starters
– surge protection devices (SPDs)
– AccuSine™ active harmonic filter units
– PowerLogic™ Circuit Monitor units
– PowerLogic Power Meter units
– capacitor units
– any devices not designed to withstand megohmmeter voltage.
• Disconnect all solid state devices such as SPDs, drives, soft starts,
capacitors, filters, and circuit monitors before performing megohmmeter
tests on the MCC.
Failure to follow this instruction can result in equipment damage.
Содержание sc200
Страница 5: ...DOC023 53 80040 sc200 Controller 01 2014 Edition 7 User Manual ...
Страница 6: ......
Страница 10: ...Table of Contents 4 ...
Страница 20: ...14 nglisK ...
Страница 23: ... nglisK 17 ...
Страница 53: ......
Страница 56: ...Visit us at www hach com ...
Страница 74: ...20 Installation ...
Страница 90: ...Visit us at www hach com Maintenance ...
Страница 96: ...Visit us at www hach com ...
Страница 100: ...Visit us at www hach com ...
Страница 106: ...Visit us at www hach com ...
Страница 108: ...Visit us at www hach com ...
Страница 110: ...Visit us at www hach com ...
Страница 115: ......
Страница 148: ...Figure 4 5 Transistor Outputs 4 8 ...
Страница 176: ...Figure 8 1 Dimensions 8 2 ...
Страница 195: ......
Страница 256: ......
Страница 257: ......
Страница 258: ......
Страница 259: ......
Страница 265: ...Figure 1 1 Typical ModBUS Network Topography 1 3 ...
Страница 267: ...Figure 1 2 Typical Communications Wiring Scheme 1 5 ...
Страница 268: ...Figure 1 3 Signal Boost Sensor Diagram 1 6 ...
Страница 270: ...Figure 2 1 Typical Communication Cable Wiring for Signal Boost Option 2 2 ...
Страница 271: ...Figure 2 2 Sensor Display Screens 2 3 ...
Страница 290: ......
Страница 292: ......
Страница 348: ...PAGE 54 APPENDIX D MOUNTING 15 APPENDIX D MOUNTING Figure 9 Mounting Detail ...
Страница 351: ......
Страница 352: ...Powerware Series Eaton 9130 UPS 700 3000 VA User s Guide ...
Страница 359: ...TABLE OF CONTENTS Eaton 9130 UPS 700 3000 VA User s Guide S 164201718 Rev 3 www eaton com powerquality iv ...
Страница 395: ...INSTALLATION Eaton 9130 UPS 700 3000 VA User s Guide S 164201718 Rev 3 www eaton com powerquality 36 ...
Страница 433: ...UPS MAINTENANCE Eaton 9130 UPS 700 3000 VA User s Guide S 164201718 Rev 3 www eaton com powerquality 74 ...
Страница 459: ...SPECIFICATIONS Eaton 9130 UPS 700 3000 VA User s Guide S 164201718 Rev 3 www eaton com powerquality 100 ...
Страница 465: ...TROUBLESHOOTING Eaton 9130 UPS 700 3000 VA User s Guide S 164201718 Rev 3 www eaton com powerquality 106 ...
Страница 470: ... 0 5 3 5 6 A B 3 4 ñ 4 9 0 ñ ñ ñ 2 ñ 5 0 1 2 13 4 0 3 5 67 4 6 0 5 8 9 8 9 8 9 0 0 1 2 3 0 41 5 1 0 5 6 3 7 3 4 7 0 ...
Страница 472: ... 0 5 3 5 6 A B 3 4 ñ 4 9 0 ñ ñ ñ 2 ñ 5 7 8 1 5 CB N4 C N4 9 2 2 6 9 E 3 7 2 5 0 0 2 3 2 ...
Страница 473: ... 0 5 3 5 6 A B 3 4 ñ 4 9 0 ñ ñ ñ 2 ñ 5 5 3 0 44 7 3 7 4 2 K 3 50 0 ...
Страница 476: ......
Страница 477: ......
Страница 479: ......
Страница 555: ......
Страница 556: ......
Страница 557: ......
Страница 558: ......
Страница 559: ......
Страница 560: ......
Страница 561: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Страница 562: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Страница 563: ...UNIT HEATERS FOR STEAM OR HOT WATER Rosemex Products HEATING 01 2003 ...
Страница 571: ......
Страница 579: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Страница 584: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 Ƭ ...
Страница 594: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ȋ Ȍ ...
Страница 624: ......
Страница 625: ......
Страница 626: ......
Страница 627: ......
Страница 628: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Страница 636: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Страница 637: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Страница 638: ......
Страница 639: ......
Страница 640: ......
Страница 641: ......
Страница 642: ......
Страница 643: ......
Страница 644: ......
Страница 645: ......
Страница 646: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ǡ ǡ ...
Страница 647: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 Rev J P N 64303001 CONCEPT ...
Страница 649: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 3 CMFK CMFKSS CMTGFT CMFK CMFKSS CMTGFT ...
Страница 650: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 4 M5 9 1 2 3 4 ...
Страница 651: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 5 ...
Страница 653: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 7 3 3 7 7 3 3 ...
Страница 654: ... 2014 Pentair Equipment Protection PH 763 422 2211 hoffmanonline com 87563688 8 1 2 4X 8X 1X ...
Страница 672: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Страница 673: ...Model 6 Motor Control Centers Class 8998 Instruction Bulletin 80459 641 01E 10 2012 Retain for future use ENGLISH ...
Страница 805: ...Notes ENGLISH ...
Страница 806: ...Notes ENGLISH ...
Страница 807: ...Notes ENGLISH ...
Страница 809: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Страница 810: ......
Страница 811: ......
Страница 812: ......
Страница 838: ...Interruptores automáticos con marco M 48049 251 01 02 2006 2003 2006 Schneider Electric Reservados todos los 26 ESPAÑOL ...
Страница 861: ... ǁǁǁ ǁŝůĚƐƚŽŶĞ ĐŽŵ 2 0DLQ 6WUHHW 3K 3HQWLFWRQ D DQDGD 9 ...
Страница 862: ......
Страница 863: ......
Страница 864: ......
Страница 865: ......
Страница 866: ......
Страница 867: ......
Страница 868: ......
Страница 869: ......
Страница 870: ......
Страница 871: ......
Страница 872: ......
Страница 873: ......
Страница 874: ......
Страница 875: ......