![Hach FL1500 Скачать руководство пользователя страница 36](http://html2.mh-extra.com/html/hach/fl1500/fl1500_user-manual_3248371036.webp)
Alarms are available for the system and for the channels. The channel alarms are setpoint alarms for
the recorded measurements (channels), such as the pH, level and power supply voltage. The system
alarms are for sensor timeout errors, power issues or digital inputs (digital inputs are available on
advanced model only). The user can set a maximum of 32 alarms. Make sure to configure the data
logging before this task is started.
1.
Push
MENU
.
2.
Select Programming>Alarm Programming.
3.
Add a channel alarm as follows:
a.
Select Channel Alarms>Add New Alarm.
b.
Select the channel, then push
Next
Note: The port number where the sensor connects to the instrument shows in the sensor channel name.
For example, Velocity 2 is the velocity channel name for the sensor that connects to sensor port 2. An IO
number that follows a channel name identifies the analog inputs of the optional I/O module.
c.
Select the type of alarm.
Option
Description
Low/Low
Sets the lowest alarm setpoint and the deadband for the lowest alarm setpoint.
Low
Sets the low alarm setpoint and the deadband for the low alarm setpoint.
High
Sets the high alarm setpoint and the deadband for the high alarm setpoint. Refer to
Figure 18
for an example of a high alarm setpoint.
High/High
Sets the highest alarm setpoint and the deadband for the highest alarm setpoint.
Rate of Change
Sets the alarm setpoint, deadband for the setpoint and the amount of time for the rate
of change (rain only).
d.
Enter the value when the alarm starts (trigger value).
e.
Enter the deadband value. Refer to
Figure 18
.
4.
Select an option, then push
OK
.
Note: More options show when the optional IO9004 module is connected to the IO9004 terminal port.
Option
Description
Log Only
Records the alarm in the alarm log.
Switch Log Interval
Changes the data logging interval to the secondary logging interval during an active
alarm. Refer to
Configure data logging
on page 33.
34
English
Содержание FL1500
Страница 1: ...DOC343 53 80573 FL1500 Flow Logger 07 2017 Edition 1 User Manual...
Страница 2: ......
Страница 11: ...Figure 4 Mounting dimensions English 9...
Страница 46: ...44 English...
Страница 47: ......