3-1
3
Installing the device
Installing the device in a standard 19-inch rack
WARNING!
To avoid bodily injury and device damage, a minimum of two persons are required to install the
device.
CAUTION:
Ensure a clearance of 1 RU (44.45 mm, or 1.75 in) between the device and walls or other devices for
heat dissipation.
Device dimensions and rack requirements
To mount the device in a rack, make sure the rack meets the requirements described in
Table3-1 Device dimensions and rack requirements
Device dimensions
Rack requirements
•
Height
—88 mm (3.46 in)
•
Width
—440 mm (17.32 in)
•
Total depth
—561 mm (20.09 in)
480 mm (18.90 in) for the chassis
56 mm (2.20 in) for the cable
management bracket at the chassis front
25 mm (0.98 in) for the power supply
handle at the chassis rear
•
A minimum of 0.6 m (1.97 ft) in depth
(recommended).
•
A minimum of 70 mm (2.76 in) between
the front rack posts and the front door.
•
A minimum of 50 mm (1.97 in) between
the front rack posts to the rear door.
•
384 mm (15.12 in) to 591 mm (23.27 in)
from the front rack posts to the rear rack
posts.
Installation methods
Table3-2 Installation methods
Installation methods
Required installation accessories
Installing the device by using the mounting brackets
and slide rails
•
Mounting brackets
•
Slide rails and chassis rails
•
M4 mounting bracket screws
•
M6 rack screws (user supplied)
•
Cage nuts (user supplied)
Installing the device by using the mounting brackets
and a rack shelf
•
Mounting brackets
•
M4 mounting bracket screws
•
M6 rack screws (user supplied)
•
Cage nuts (user supplied)
•
Rack shelf (user supplied)