Fan tray failure
Symptom
A fan tray does not operate correctly.
Troubleshooting flowchart
Figure 23 Flowchart for troubleshooting fan tray failure
Solution
To resolve the issue:
1.
Verify that the airflow direction of the fan tray is as configured:
a.
Identify the airflow direction of the fan tray.
You must install two fan trays of the same model for the switch and configure the airflow
direction as that of the fan trays.
[Sysname] display fan
Slot 1
FAN 1
State : FanDirectionFault
Wind Direction :Port-to-Power
Fan tray failure
Display operating state of the fan tray
Is the airflow direction
as configured
Is the fan tray damaged
Reconfigure the
airflow direction
Resolved?
Replace the fan tray
Contact the support
No
Yes
No
Yes
Resolved?
Yes
Yes
No
No
End