H3C S3100-26T P-EI-W Скачать руководство пользователя страница 35

Quick Start (For Soliton) 
H3C S3100 Series Ethernet Switches 

Chapter 3  Installation

 

3-9 

 

  Note: 

z

 

No guide rails are delivered with the device. 

z

 

Ensure a clearance of 1U (44.45 mm, namely, 1.75 inches) 
between devices for the purpose of heat dissipation. 

 

3.1.2  Desk Mounting 

When a 19-inch standard cabinet is not available, you can simply 

place the switch on a clean desk. When doing so, you should ensure 
that: 

z

 

The desk is stable and well grounded. 

z

 

A clearance about 10 cm (3.9 in) is reserved around the 
switch for heat dissipation. 

z

 

No heavy object is placed on the switch. 

z

 

S3100-SI and S3100-TP-EI-W Series Ethernet Switches are 
designed with no fan. Therefore, you should install them in a 
drafty environment, and keep at least a vertical distance of 
1.5 cm (0.6 in) between devices if you need to stack 
switches one upon another. 

3.1.3  Wall Mounting 

You can mount some models of S3100 Series Ethernet Switches 

on concrete walls or wood walls. Table 3-3 lists the models that 
support wall mounting. 

Содержание S3100-26T P-EI-W

Страница 1: ...H3C S3100 Series Ethernet Switches Quick Start For Soliton Hangzhou H3C Technologies Co Ltd http www h3c com Manual Version T2 08011H 20080410 C 1 00...

Страница 2: ...nnoVision and HUASAN are trademarks of Hangzhou H3C Technologies Co Ltd All other trademarks that may be mentioned in this manual are the property of their respective owners Notice The information in...

Страница 3: ...S3100 Series Ethernet Switches Command Manual For Soliton It is used for assisting the users in using various commands H3C S3100 Series Ethernet Switches Installation Manual For Soliton It is used for...

Страница 4: ...Series Ethernet Switches Conventions The manual uses the following conventions I Symbols Convention Description Warning Means reader be extremely careful Improper operation may cause bodily injury Cau...

Страница 5: ...9 1 3 2 Auto Sensing 10 100BASE TX Ethernet Port Status LED 1 10 1 3 3 1000 Mbps Uplink Port Status LED 1 12 1 4 Technical Specifications 1 12 1 5 SFP Modules Supported by S3100 Series Ethernet Switc...

Страница 6: ...er Cord 3 16 3 2 2 Connecting DC Power Cable 3 17 3 2 3 Connecting Grounding Cable 3 19 3 3 Connecting Optical Fiber 3 24 3 4 Connection of Console Cable 3 25 3 4 1 Console Cable 3 25 3 4 2 Connecting...

Страница 7: ...ntelligent Ethernet switches which support wire speed Layer 2 switching Table 1 1 lists the models of H3C S3100 Series Ethernet Switches Table 1 1 Models of H3C S3100 Series Ethernet Switches Model Po...

Страница 8: ...console port Each SFP port and the corresponding 10 100 1000BASE T Ethernet port form a Combo port For each Combo port either the SFP port or the corresponding 10 100 1000BASE T Ethernet port can be...

Страница 9: ...net switch 1 2 3 1 AC power socket 2 RPS DC power socket 3 Grounding screw Figure 1 2 Rear panel of an S3100 26TP EI W Ethernet switch III Power system S3100 26TP EI W Ethernet switches can adopt AC i...

Страница 10: ...FP ports and one console port Each SFP port and the corresponding 10 100 1000BASE T Ethernet port form a Combo port For each Combo port either the SFP port or the corresponding 10 100 1000BASE T Ether...

Страница 11: ...hows the rear panel of an S3100 16TP EI W Ethernet switch 1 2 1 AC power socket 2 Grounding screw Figure 1 4 Rear panel of an S3100 16TP EI W Ethernet switch III Side panel Each S3100 16TP EI W Ethern...

Страница 12: ...of an S3100 16TP EI W Ethernet switch Note If the left screw hole above the security slot is used the security slot cannot be used IV Power system S3100 16TP EI W Ethernet switches z Rated voltage ran...

Страница 13: ...one console port The SFP port and the 10 100 1000BASE T Ethernet port form a Combo port Either the SFP port or the 10 100 1000BASE T Ethernet port can be used at a time Figure 1 6 shows the front pane...

Страница 14: ...shows the rear panel of an S3100 8TP EI W Ethernet switch 1 2 1 AC power socket 2 Grounding screw Figure 1 7 Rear panel of an S3100 8TP EI W Ethernet switch III Side panel Each S3100 8TP EI W Etherne...

Страница 15: ...e range 100 VAC to 240 VAC 50 60Hz z Input voltage range 90 VAC to 264 VAC 47Hz to 63Hz V Cooling system S3100 8TP EI W Ethernet switches cool off naturally 1 3 Introduction to Front Panel LEDs 1 3 1...

Страница 16: ...E TX Ethernet port of S3100 series They indicate the active link duplex and speed statuses of the port In addition there are an A L LED and a D S LED on each model of S3100 series These two LEDs indic...

Страница 17: ...reen LED right OFF The port is not connected or is incorrectly connected ON The port operates in the full duplex mode Yellow LED left OFF The port operates in the half duplex mode ON The port rate is...

Страница 18: ...ncorrectly connected BLINKING The port is in the active state and there is traffic on the port 1000 Mbps uplink port active LED ACT OFF The port is in the active state but there is no traffic on the p...

Страница 19: ...bo port Number of management port 1 x console port Power system S3100 16TP EI W S3100 8TP EI W Ethernet switches support only AC input S3100 26TP EI W AC powered switches support AC input and RPS DC i...

Страница 20: ...90 Caution Only the recommended 12V RPS DC power supply can be used for S3100 26TP EI Ethernet switches 1 5 SFP Modules Supported by S3100 Series Ethernet Switches The front panel of S3100 Series Eth...

Страница 21: ...SM1310 A SFP stack module SFP STACK Kit 100 Mbps bidirectional BIDI module z SFP FE LX SM1310 BIDI z SFP FE LX SM1550 BIDI SFP module 1000 Mbps BIDI module z SFP GE LX SM1310 BIDI z SFP GE LX SM1490...

Страница 22: ...switch might be damaged severely in case of a fall z Keep the switch room drafty and the switch ventilation hole free of obstruction z The switch can operate normally only under correct voltage input...

Страница 23: ...the normal operation and working life of your switch If the humidity in the equipment room is too high for a long time it may decrease the insulation attribute of insulating material or even cause ele...

Страница 24: ...ements on dust content and particle diameter in the equipment room are shown in the following table Table 2 1 Requirements on dust content in the equipment room Physical active substance Unit Content...

Страница 25: ...r line signaling line and transmission line Therefore you should pay attention to the following z If AC supply system is TN system AC power socket should be a single phase three line power socket with...

Страница 26: ...ating it is prohibited to stare into the optical interface because the laser beam emitted from the optical fiber takes high energy and may hurt your retina Caution Staring at the laser beam inside the...

Страница 27: ...mission of the local agent before you can open the chassis Otherwise you will be responsible for irreversible damages caused by your operations 3 1 Installing a Switch 3 1 1 Cabinet Mounting You can i...

Страница 28: ...ting ears and a tray Use front mounting ears and guide rails S3100 26TP EI W S3100 16TP EI W S3100 8TP EI W I Introduction to mounting ear Figure 3 1 shows the appearance of a front mounting ear 1 2 L...

Страница 29: ...f mounting ear for S3100 Series Ethernet Switches Model Physical dimensions H x W x D Configuration type of front mounting ear S3100 26TP EI W 43 6 x 440 x 260 mm 1 7 x 17 3 x 10 2 in Standard S3100 1...

Страница 30: ...the cabinet 2 Take out the screws which are packed together with the front mounting ears and fix one end of mounting ears to the switch as shown in Figure 3 2 Figure 3 2 Fix front mounting ears 1 3 P...

Страница 31: ...ndard cabinet 1 Wear an ESD preventive wrist strap to check the grounding and stability of the cabinet 2 Fix the delivered tray horizontally in a proper position 3 Take out the screws which are packed...

Страница 32: ...hole position according to the position of the switch Cooling hole Used for heat dissipation between switch and cabinet Slotted hole 2 Used to fix the guide rail to the front bracket Figure 3 4 Appea...

Страница 33: ...the front mounting ears to the switch as shown in Figure 3 2 3 Install guide rails on the brackets on both sides of the cabinet with M5 self tapping screws Figure 3 5 is for reference only Figure 3 5...

Страница 34: ...ars and guide rails 5 Fix the other end of front mounting ears to the front brackets of the cabinet with M6 screws and captive nuts and ensure that the front mounting ears and guide rails have fixed t...

Страница 35: ...e that z The desk is stable and well grounded z A clearance about 10 cm 3 9 in is reserved around the switch for heat dissipation z No heavy object is placed on the switch z S3100 SI and S3100 TP EI W...

Страница 36: ...es Models supporting wall mounting Hole distance mm S3100 8TP EI W S3100 Ethernet switches S3100 16TP EI W 170 mm 6 69 in I Introduction to screw and anchor kit Figure 3 8 and Figure 3 9 show the reco...

Страница 37: ...6 69 in Note Drill two holes according to the sizes of anchor kits and screws so that anchor kits could go into the holes only the edges could remain outside the wall and the screws could be fixed on...

Страница 38: ...nstallation holes at the bottom of the switch with these two screws to hang the switch Caution When mounting the switch keep the Ethernet ports of the switch facing downwards and the two sides with ve...

Страница 39: ...ssories are needed for each S3100 switch 1 2 1 Permanent magnet 2 M3 6 countersunk head screw Figure 3 11 Magnets and countersunk head screws II Installation procedure Follow these steps to complete m...

Страница 40: ...the firmness of installation be sure to use four permanent magnets to secure each S3100 switch 2 Attach the magnet mounted device to the specified location Take care not to get your fingers stuck betw...

Страница 41: ...or equipment damage may occur in case of a falloff z Avoid frequently moving the desk mounted device because such movements may damage the surface coating z Keep the front panel of the device facing d...

Страница 42: ...uilding must be well grounded Normally the neutral point of the power supply system in your building has already been grounded during the construction and wiring but you should make sure this is the f...

Страница 43: ...d is properly connected Caution Before powering on the switch you should properly connect the grounding cable 3 2 2 Connecting DC Power Cable I 12V RPS DC power cable connection for S3100 26TP EI W AC...

Страница 44: ...r filter from the 12V RPS DC power socket In the case of no 12V RPS DC power supply re install the air filter 2 1 1 Air filter 2 Fastening screw Figure 3 15 12V RPS power socket for an S3100 26TP EI W...

Страница 45: ...d Caution z Before powering on the switch you should properly connect the grounding cable z The DC power cable should be less than 3 meters long z Only the recommended 12V RPS DC power supply and powe...

Страница 46: ...on site attach one end of the yellow green grounding cable of the switch to the grounding screw on the grounding strip and fasten the captive nut Note that the fire main and lightning rod of your buil...

Страница 47: ...e and the jointing point being processed against erosion 1 Power input 2 Grounding screw 3 Grounding cable 4 Earth 5 Angle steel Figure 3 18 Grounding the switch by burying the grounding body into the...

Страница 48: ...le 5 3 core cable for AC power input 6 Ethernet switch Figure 3 19 Grounding the switch through AC PE cable z For a DC powered switch 48 VDC if none of the first two conditions is available ground it...

Страница 49: ...Chapter 3 Installation 3 23 1 AC DC power cabinet 2 48V strip 3 48V 4 RTN strip 5 RTN 6 PGND strip 7 Grounding to the earth 8 Grounding cable 9 screw 10 Ethernet switch 11 DC power input Figure 3 20...

Страница 50: ...use to keep the optical connector clean z Be sure to cover the protective cap if an optical port has no optical connector attached z Place the protective caps in a safe place when an optical port has...

Страница 51: ...45 connector to be connected to the console port of the switch at the other end of the cable is a DB 9 female connector to be connected to the 9 core pin serial port on the console terminal See the fo...

Страница 52: ...ese steps to connect a terminal device a PC for example to the switch Step 1 Connect the DB 9 female connector of the console cable to the serial port of the PC or the terminal device used to configur...

Страница 53: ...mmended to disconnect the DB 9 connector of the console cable from the PC after disconnecting the RJ45 connector from the switch 3 5 Installation Verification After completing the installation check t...

Страница 54: ...pped with the switch You should purchase it by yourself if needed If an outdoor AC power cord should be directly led to the switch please serially connect the lightning arrester for AC power Socket St...

Страница 55: ...ronglyconnected Pleasecheckthepow ersupplycircuit Pow ersw itch N orm aloperationindicator green O nm eansthatthearresterw orksnorm ally O therw ise it m eansthattheprotectioncircuithasbeendam aged M...

Страница 56: ...locate the problem whether it is caused because the ground cable of the arrester is not well grounded or because the live and zero cables are connected in reverse direction You may check that in the f...

Страница 57: ...this case Caution Lightning arrester for network port will not be provided along with the switch and you should purchase it by yourself if needed If an outdoor network cable should be led to the swit...

Страница 58: ...g its ground cable to the grounding screw of the switch Step 3 Use the multimeter to measure whether the ground cable of the arrester contacts well with the grounding screw of chassis Step 4 According...

Страница 59: ...Installation precautions Fully consider the following items in the installation process otherwise the performance of the lightning arrester for network port will be affected z Lightning arrester for n...

Страница 60: ...tection of the Switch 4 7 z The lightning arrester for the network port is not installed completely If the switch has more than one network ports to interconnect with other devices via cables outdoor...

Отзывы: