background image

H2flow Controls 

FlowVis®

12

Installation

8.1  General Installation Guidance

IMPORTANT INSTALLATION NOTE:

 Before installing the FlowVis, 

please refer to the preceding section regarding chlorine feeders.

Installation of FlowVis

®

 should be in accordance with the following 

instructions.

Normal plumbing procedures such as cleaning, priming and gluing of fixtures 

should be followed in order to avoid leaks. If you are not familiar with plumbing 

procedures, it is recommended that you employ the skills of a qualified plumber.

Unlike other flow meters, the majority of FlowVis

®

 models are not affected by 

flow stream disturbances caused by its proximity to pumps, elbows, tees, valves, 

etc. FlowVis

®

 can be installed either horizontally or vertically. Straight pipe 

requirements are addressed in the table on page 19.

Pay particular attention to the system’s direction of flow and make sure that 

the arrow on the lid of the FlowVis

®

 is pointing in the correct direction. For 

the FV-3, FV-3-L, FV-4, FV-4-L, FV-6, FV-6-L, FV-8 and FV-8-L versions, the 

Tee / Saddle-clamp will feature an additional arrow label. In the event that the 

FlowVis

®

 is inadvertently installed into the plumbing in the wrong direction, 

simply remove the (8) screws holding the lid in place and rotate the entire lid 

assembly by 180

°

.

IMPORTANT NOTES:

a. 

For all models 2.5” and smaller, always remove the FlowVis lid assembly 

prior to gluing in the valve body.

b. 

When selecting a physical location to install FlowVis, be sure to allow 

accessibility to read the scale on the lid.

c. 

Due to the possibility of excessive turbulence, models FV-3, FV-3-L, FV-4, 

FV-4-L, FV-6, FV-6-L, FV-8 and FV-8-L should not be installed directly after 

the pump.

d. 

FlowVis models are designed for the specific pipe Schedule stated at the 

bottom of the flow scale label. While it is important to comply with the 

specific Schedule of pipe, the accuracy stated within this manual can be 

maintained if a short length (3-6 inches / 75-150mm), of the correct pipe

8. installation

Содержание FlowVis FV-J-R-15

Страница 1: ...Instruction Manual English FlowVis Flow Meter...

Страница 2: ...General Installation Guidance 12 8 2 Certified NSF 50 Accuracy and Assoc pipe Configs 13 8 3 Pipe Configs other than those used by NSF for Testing 14 8 4 NSF 50 Accuracy Levels 14 8 5 Installation of...

Страница 3: ...l also exists for Flotation Tanks and where the Specific Gravity has been raised to 1 25 by adding Epsom Salts Using a design that is based on mass flow principles FlowVis flow meters provide many ben...

Страница 4: ...e valve body tee pipe A calibrated scale on the valve s lid provides a highly accurate reading of the flow rate and velocity 3 resources Thank you for purchasing the H2flow FlowVis flow meter If you w...

Страница 5: ...arm for all models except FV C S and FV C Saline 1 x pivot pin FV SK CAR for all 3 4 6 and 8 models comprising 1 x o ring 1 x spring 1 x spring pulley pivot pin 1 x spring pulley to flapper pulley wir...

Страница 6: ...saddle clamps do not possess this feature Fig 1 4 5 3 Tygon Tubing For models FV 3 FV 3 L FV 4 FV 4 L FV 6 FV 6 L FV 8 and FV 8 L the Tygon tubing feature shown Fig 1 5 and Fig 1 6 is installed to ass...

Страница 7: ...ut are not limited to SVRS and Automatic Pump Shut Off systems Special consideration must be made when installing a FlowVis to such applications Several of these systems do not allow the use of Check...

Страница 8: ...R FVJ R 15 L FVJ R L FVH R 15 L FVH R L FVP R 15 L FVP R L FV 15 FV 15 L FV 2 FV 2 L FV 25 FV 25 L FV 3 FV 3 40 FV 3 L FV 4 FV 4 L FV 6 FV 6 L FV 8 FV 8 L FV 15 U FV 2 U FV C S FV C S L FV C Saline F...

Страница 9: ...A 38 416 70 240 N A 70 240 N A N A 165 908 150 460 N A N A 568 1740 300 1000 N A N A 1136 3785 600 1800 N A N A 2271 6814 10 90 N A 10 110 N A 30 110 N A N A 110 400 20 100 N A N A 80 400 30 190 N A C...

Страница 10: ...ons there is virtually no possibility of damage being caused to the FlowVis unit by these devices Therefore the primary installation consideration is where will the unit provide the greatest benefit t...

Страница 11: ...n to fail and release high concentrations of chlorine or even chlorine gas into the surrounding filtration system When this occurs any equipment that comes into contact with these abnormal levels of c...

Страница 12: ...on the lid of the FlowVis is pointing in the correct direction For the FV 3 FV 3 L FV 4 FV 4 L FV 6 FV 6 L FV 8 and FV 8 L versions the Tee Saddle clamp will feature an additional arrow label In the e...

Страница 13: ...ions A Zero straight pipe before of after FlowVis Can be installed in any orientation horizontal vertical up or vertical down B Straight horizontal pipe of 11 before FlowVis C Straight horizontal pipe...

Страница 14: ...NSF 50 Accuracy Levels The NSF 50 Standard for flow meters has five levels of accuracy L1 L5 that are expressed as follows Level 1 L1 Average of absolute values of all single point deviations must be...

Страница 15: ...rade to enable the flow reading to be read remotely NOTE Models FV 8 and FV 8 L include FlowVis Digital as standard 3 Do not damage the external pipe area around the drilled hole Surface damage will r...

Страница 16: ...the standard FlowVis valve body and 2 Where the user wishes to uninstall the FlowVis during cold winter months As with all Union style fittings it is essential that accurate measurements are taken bef...

Страница 17: ...the two locking rings onto each pipe end before gluing on the union flanges The amount of pipe to be removed is shown in Fig 2 0 Fig 2 1 NOTE The lid assembly from the standard valve body cannot be t...

Страница 18: ...steel screws but do not tighten at this stage 5 Using a hand Phillips head screwdriver slowly tighten the screws in a diagonal pattern per the sequence shown in Fig 2 2 Do not fully tighten one screw...

Страница 19: ...avoid so called parallax error it is important to position your eye so that you are looking squarely at the tip of the indicator arm To achieve this simply move your head so that you just lose sight o...

Страница 20: ...n the Recreational Water industry that the velocity of water traveling through a pipe shall not exceed six feet per second on the suction side of a pump or eight feet per second on the discharge side...

Страница 21: ...ange 6 ft s on the suction side and 8 ft s on the discharge side of the pump This area of the scale denotes the schedule pipe that the FlowVis model has been calibrated to Schedule 40 for 1 5 2 2 5 an...

Страница 22: ...STANDARD C Reference Dimension A 8 75 B 5 50 C Schedule 40 2 Slip D 4 63 E 5 72 WEIGHT 2 lbs Models FV 2 U ENGLISH STANDARD B A 165 1 mm B 149 23 mm C Schedule 40 DN40 D 34 93 mm E 117 6 mm F 92 25 m...

Страница 23: ...Dimension A 165 1 mm B 149 23 mm C Schedule 40 DN50 Slip DN65 with coupling D 34 93 mm E 117 6 mm F 92 25 mm WEIGHT 0 544 kg Models FV M DN50 FV M DN65 METRIC A F D D E B C A D F Reference Dimension A...

Страница 24: ...e 80 168 86 mm DN150 B 152 65 mm C 318 45 mm D 107 51 mm E 191 32 mm WEIGHT 2 27 kg Models FV M DN150 METRIC A B E D C A D F C Reference Dimension A 9 5 B 9 75 C Schedule 80 4 D 2 25 E 5 25 F 5 0 WEIG...

Страница 25: ...y Leak around lid seal O Ring Failure Replace O Ring Leak from lid Cracks in lid Order new lid from supplier Higher flow reading than normal Broken or weak spring Replace spring Lower flow reading tha...

Страница 26: ...Valve Body Check Valve Flapper Flapper Seal Non Check Valve Flapper Indicator FV 15 to FV 25 Indicator FV 3 to FV 8 Magnet Carriage Flapper Pulley Spring Pulley Flapper to Indicator Link Connecting W...

Страница 27: ...ycarbonate Hasteloy c 276 Viton 316 Stainless Steel Hasteloy c 276 Armalex Armalex Armalex CPVC CPVC PPEPS Viton ABS ABS ABS N52 Neodymium ABS ABS ABS and Stainless Steel sleeve ABS 316 Stainless Stee...

Страница 28: ...40 F 60 C FV 15 U 98 7 FV 2 FV 2 L FV M DN50 99 4 FV 2 U 99 0 FV 25 FV 25 L FV M DN65 99 2 FV C S FV C S L 98 0 FV C Saline 97 5 FV 3 FV 3 L FV M DN80 98 9 FV 3 40 99 2 FV 4 FV 4 L FV M DN100 99 6 FV...

Страница 29: ...Pipe Before x Pipe Diameters Straight Pipe After x Pipe Diameters FV 15 FV 15 L FV 15 U FV 2 FV 2 L FV 2 U FV 25 FV 25 L 0 x0 0 x0 FV 3 FV 3 40 FV 3 L 11 01 x3 67 0 x0 FV 4 FV 4 L 17 x4 25 0 x0 FV 6 F...

Страница 30: ...duct return policy Any product returned for warranty repair must be accompanied by a full fault report specifying the symptoms and the conditions under which the fault occurs Should H2flow Controls In...

Страница 31: ...d to ship the product to the customer in the first instance Any damage resulting from the use of inadequate packaging will nullify H2flow Controls Inc s obligations under this warranty Should the cust...

Страница 32: ...H2flow Controls Inc 3545 Silica Road Unit F Sylvania OH 43560 USA Tel 888 635 0296 Fax 419 517 9900 www h2 ow net FV manual NA Rev 6 1 01 23...

Отзывы: