| Functions
Temperature Switch TS 1000
FuncTIon “heIzen” (heaTIng)
This function is activated if the programmed switching ON temperature is the
smaller than the switching OFF temperature. The LED “
heizen
” will indicate
the function. The relay is switched on if the measured temperature is smaller or
equal to T EIN (ON). The relay is switched off if the temperature is higher or
equal to T AUS (OFF).
For example:
A switching ON temperature of 25°C is programmed and a
switching OFF temperature of 23°. The device recognizes that this is a heating
mode and shows this by switching on the ”Heizen” LED.
FuncTIon “kühlen” (coolIng)
This function is activated if the programmed switching ON temperature is the
higher than the switching OFF temperature. The LED “
kühlen
” will indicate
the function. The relay is switched ON if the measured temperature is higher or
equal to T EIN. The relay is switched OFF if the temperature is lower or equal
to T AUS.
For example:
a switching ON temperature of 23°C is programmed and a swit-
ching OFF temperature of 25°C. The device recognizes that this is a cooling
mode and shows this by switching on the ”Kühlen” LED.
oFFSeT correcTIon
The offset correction is used to compensate sensor tolerances or the line balan-
ce of the connected sensor cable. The menu for the offset correction consists of
two menu items and can be entered by the following steps:
1.
Switch the device off.
2.
Press and hold both the
pq
buttons at the same time.
3.
Switch the device on.
4.
The LED display will show the message “
oFFt
”
5.
Release the
pq
buttons.
6.
Press the button
SeT
. You can now see the offset value for the temperature.
This value can be changed by pressing the buttons
pq
. Adjustment tole-
rance: –50° to +50°C. After the required value has been input pressing the
“Set” button will confirm and save the value.
(
noTe:
the offset value is added/deducted from the shown value)
7.
The LED display will show the message “
oFFt
”
8.
Press the button
SeT
. Here you can enter the offset value for the resistance
of the connected sensor cable. This value can be changed by pressing the
buttons
pq
. Adjustment tolerance: 0 to 50 Ohm. After the required value
has been input pressing the
SeT
button will confirm and save the value.
9.
The device will return to standard working mode.
7. FuncTIonS
The device can execute the following functions, depending on pro gramming:
FuncTIon “ThermomeTer”
This function is activated if the programmed switching ON temperature is
identical to the switching OFF temperature. The three LEDs and the relay are
switched off. The device has no activation function.
temperature
T oFF
T on
heaTIng
switch-ON-point
switch-OFF-point
time
temperature
T on
T oFF
coolIng
switch-ON-point
switch-OFF-point
time
e.g. 25°C
e.g. 25°C
e.g. 23°C
e.g. 22°C