GWS Gas-Fired Water Boilers Скачать руководство пользователя страница 16

GWS

 

Gas-Fired Water Boilers – 

Boiler Manual

16

Part Number 550-110-732/0703

Boiler model

 _______________________________________________________________          

Series 

____________

CP number

 _______________________________________     

Date installed

 _________________________________

Measured Btuh input

 ____________

Installer

 _______________________     ______________________________    ____________________________

                              

(company)

                                           

(address) 

                                              

(phone)

_____________________________________

                    

 

(installer’s signature)

8

Checkout procedure

Boiler and heat distribution units filled with water?

Automatic air vent, if used, open one full turn?

Air purged from system?

Air purged from gas piping? Piping checked for leaks?

Correctly-sized manifold orifices installed? See Table 4,
page 8 to check size and fuel type.

Correctly sized manifold orifices must be used.
Failure to do so will cause severe personal injury,
death or substantial property damage.

Followed Operating Instructions on boiler or in manual,
page 19 for proper start-up?

Proper burner flame observed? See “Verify operation”,
page 15.

Test limit control — While burners are operating, move
indicator on limit control below actual boiler water
temperature. Burners should go off while circulator continues
to operate. Raise setting on limit control above boiler water
temperature and burners should reignite.

Test additional field-installed controls — If boiler has a low
water cutoff, additional high limit or other controls, test for
operation as outlined by manufacturer. Burners should be
operating and should go off when controls are tested. When
controls are restored, burners should reignite.

Test ignition system safety device:

Connect manometer to outlet side of gas valve. Start boiler,
allowing for normal start-up cycle to occur and main burners to
ignite. With main burners on, manually shut off gas supply at
manual main shutoff gas valve. Burners should go off. Open
manual main shutoff gas valve. Manometer should confirm there
is no gas flow. Pilot will relight, flame sensing element will sense

pilot flame and main burners reignite.

Set limit control(s) to system temperature requirements. Adjust
balancing valves and controls to provide design temperature to
system.

For multiple zones, adjust flow so it is about the same in each
zone.

Verify thermostat heat anticipator (if available) set properly? See
wiring diagram label on boiler or in manual, page 18.

Cycle boiler with thermostat — Raise to highest setting and
verify boiler goes through normal start-up cycle. Lower to lowest
setting and verify boiler goes off.

Measure natural gas input:

a.

Operate boiler 10 minutes.

b.

Turn off other appliances.

c.

At natural gas meter, measure time (in seconds) required to use
one cubic foot of gas.

d.

Calculate gas input:

3600 x 1000

number of seconds from step

c

=   Btuh

e.

Btuh calculated should approximate input rating on boiler rating
label.

Check manifold gas pressure by connecting manometer to
downstream test tapping on main gas valve. Manifold pressure
for natural gas should be 3.5" w.c. and for propane gas should
be 10" w.c.

Observe several operating cycles for proper operation.

Set room thermostat to desired room temperature.

Fill in Installation and service certificate below?

Review all instructions shipped with this boiler with owner or
maintenance person. Return instructions to envelope and give
to owner or place in pocket inside front panel in boiler.

†

Installation instructions have been followed.

†

Checkout sequence has been performed.

†

Above information is certified to be correct.

†

Information received and left with owner/maintenance person.

Installation and service certificate

Содержание Gas-Fired Water Boilers

Страница 1: ...t will or can cause minor personal injury or property damage Special instructions on installation operation or maintenance that are important but not related to personal injury or property damage INST...

Страница 2: ...y potential ignition source Monitor and inspect the system and boiler regularly for leakage Repair any leaks immediately to prevent possible accumulation of glycol Never use automotive antifreeze or e...

Страница 3: ...ential garage installations Take the following special precautions when installing the boiler in a residential garage If the boiler is located in a residential garage per ANSI Z223 1 paragraph 5 1 9 M...

Страница 4: ...re personal injury or death GWS boilers can be either direct vent vented or direct exhaust vented They cannot be chimney draft vented See GWS Venting Manual for detailed installation instructions If y...

Страница 5: ...ro fluorocarbons Permanent wave solutions Chlorinated waxes cleaners Chlorine based swimming pool chemicals Calcium chloride used for thawing Sodium chloride used for water softening Refrigerant leaks...

Страница 6: ...ion air provided the boiler room is not subjected to negative pressure due to exhaust fans or other mechanical ventilation devices Refer to the National Fuel Gas Code for dealing with other conditions...

Страница 7: ...7 Part Number 550 110 732 0703 GWS Gas Fired Water Boilers Boiler Manual Figure 2 Provide minimum air openings for GWS boiler installations based on following 1 Prepare boiler location continued...

Страница 8: ...tant gauge pressure has been maintained throughout test Check for leaks Repair if found Leaks must be repaired at once Failure to do so can damage boiler resulting in substantial property damage Do no...

Страница 9: ...r circulator zoning or zone valve zoning Install expansion tank on suction side of system pump Always connect fill line only at the expansion tank never at another point in the system Relief valve Ins...

Страница 10: ...boiler Consult I B R Installation and Piping Guides If boiler is connected to heating coils located in air handling units where they can be exposed to refrigerated air use flow control valves or other...

Страница 11: ...h to allow temperatures to level off It takes a while for the boiler water temperature to rise as the flow changes 3 Bypass valve 2 allows hot boiler outlet water to blend with colder return water rai...

Страница 12: ...s piping of 0 30 w c For additional gas pipe sizing information see ANSI Z223 1 B149 1 or B149 2 for Canadian installations 2 Inlet pressure required at gas valve inlet Maximum 13 w c Minimum 5 w c Ma...

Страница 13: ...s which prohibit installation of fused disconnect or service switch on boiler install a 2 x 4 cover plate on the boiler junction box and mount the service switch remotely as required by the code Wirin...

Страница 14: ...vel to drop Added water will dilute the antifreeze reducing the freeze protection level Fill the system with water 1 Close manual and automatic air vents and boiler drain cock 2 Fill to correct system...

Страница 15: ...iler life Minerals can build up in sections reducing heat transfer overheating cast iron and causing section failure If you discover evidence of any gas leak shut down the boiler at once Find the leak...

Страница 16: ...oiler allowing for normal start up cycle to occur and main burners to ignite With main burners on manually shut off gas supply at manual main shutoff gas valve Burners should go off Open manual main s...

Страница 17: ...stpurge then starts a new cycle b If pilot does light and control module senses flame current spark generator is turned off and main valve opens 4 During main burner operation a Control module monitor...

Страница 18: ...GWS Gas Fired Water Boilers Boiler Manual 18 Part Number 550 110 732 0703 Figure 13 Wiring diagram GWS boilers 9 Sequence of operation continued...

Страница 19: ...itch do not use any phone in your building Immediately call your gas supplier from a neighbor s phone Follow the gas supplier s instructions If you cannot reach your gas supplier call the fire departm...

Страница 20: ...Reported problems Boiler area Air openings Flue gas vent system Pilot and main burner flames Water piping Boiler heating surfaces Burners base and inlet air box Condensate drain system Service Induce...

Страница 21: ...place it in a plastic bag for disposal Wash potentially contaminated clothes separately from other clothing Rinse clothes washer thoroughly NIOSH stated First Aid Eye Irrigate immediately Breathing Fr...

Страница 22: ...connection after turning off power to the boiler 2 Use a bright light to inspect the flue pipe interior and inducer interior 3 Inspect the boiler vent outlet area and heating surfaces by looking thro...

Страница 23: ...boiler temperature Boiler should cycle off Return dial to original setting 2 Inspect and test additional limit controls or low water cutoffs installed on system Expansion tank 1 Expansion tanks provi...

Страница 24: ...sizing Following installation the valve lever must be operated AT LEAST ONCE A YEAR to ensure that waterways are clear Certain naturally occurring mineral deposits may adhere to the valve rendering it...

Страница 25: ...be adjusted by regulator on gas valve Check pressure switch setting Make sure boiler water temperature is 100 F or cooler before starting procedure to obtain appropriate readings 1 See Figure 14 and...

Страница 26: ...GWS Gas Fired Water Boilers Boiler Manual 26 Part Number 550 110 732 0703 12 Troubleshooting continued...

Страница 27: ...27 Part Number 550 110 732 0703 GWS Gas Fired Water Boilers Boiler Manual 12 Troubleshooting continued...

Страница 28: ...GWS Gas Fired Water Boilers Boiler Manual 28 Part Number 550 110 732 0703 12 Troubleshooting continued...

Страница 29: ...29 Part Number 550 110 732 0703 GWS Gas Fired Water Boilers Boiler Manual 12 Troubleshooting continued...

Страница 30: ...GWS Gas Fired Water Boilers Boiler Manual 30 Part Number 550 110 732 0703 12 Troubleshooting continued...

Страница 31: ...31 Part Number 550 110 732 0703 GWS Gas Fired Water Boilers Boiler Manual 12 Troubleshooting continued...

Страница 32: ...GWS Gas Fired Water Boilers Boiler Manual 32 Part Number 550 110 732 0703 12 Troubleshooting continued...

Страница 33: ...15 Section assembly flue collector draft hood and vent damper 13 Replacement parts The boiler contains ceramic fiber and fiberglass materials Use care when handling these materials per instructions on...

Страница 34: ...re 16 Base assembly manifold orifices and burners 13 Replacement parts continued The boiler contains ceramic fiber and fiberglass materials Use care when handling these materials per instructions on p...

Страница 35: ...er Manual Figure 17 Jacket assembly 13 Replacement parts continued The boiler contains ceramic fiber and fiberglass materials Use care when handling these materials per instructions on page 21 of this...

Страница 36: ...GWS Gas Fired Water Boilers Boiler Manual 36 Part Number 550 110 732 0703 Figure 18 Trim assembly 13 Replacement parts continued...

Страница 37: ...37 Part Number 550 110 732 0703 GWS Gas Fired Water Boilers Boiler Manual Figure 19 Gas control assembly 13 Replacement parts continued...

Страница 38: ...ler model number Supply tapping inches NPT Return tapping inches NPT Gas connection size Note 3 inches NPT Gas manifold size Note 3 inches NPT A Air inlet pipe center inches W Jacket width inches GWS...

Страница 39: ...et I B R ratings are based on net installed radiation of sufficient quantity for the requirements of the building and nothing need be added for normal piping and pickup Ratings are based on a piping a...

Страница 40: ...GWS Gas Fired Water Boilers Boiler Manual 40 Part Number 550 110 732 0703 W T 8201 W Calumet Rd Milwaukee WI 53223...

Отзывы: