K-BUS
○
R
KNX/EIB
Switch Blind Actuator
43
www.video-star.com.cn
Tel.
:(
8620
)
39338986
Fax
:(
8620
)
39338465
5
Output X
Flashing function
1bit
C,W
1.001 DPT_Switch
When select “flashing ” in the parameter “Type of time function”, the object will be activated, then the flashing switch function will be
activated via the object.
5
Output X
Staircase function
1bit
C,W
1.001 DPT_Switch
When select “staircase ” in the parameter “Type of time function”, the object will be activated, then the staircase lighting function
will be activated via the object.
6
Output X
Operation hours counter
2byte/4byte
C,R,W,T,U
7.001 pulses/12.001 counter pulses
This communication object is used to report load working time, it displays when the parameter "function of “ operation hours
counter" select "enable" ,the data type of report value can be set in the parameter "Object datatype of “operation hours counter".
7
Output X
Scene
1byte
C,W
18.001 DPT_SceneControl
It is able to recall or save the scene when sending an 8-bit command by this object, which will be enabled when enabling the scene
function. The definition of the 8-bit command will be described below:
Assuming an 8-bit command (binary coding) as: FXNNNNNN
F: recall the scene with “0”; save the scene with “1”;
X: 0
NNNNNN: scene number (0-63).
1-64 in the parameter setup corresponds to the scene number 0-63 received by the communication object “Scene”. For example,
scene 1 in the parameter setup has the same output result as scene 0 in the communication object “Scene”. As follow:
Object value
Description
0
1
2
…
63
Recall scene 1
Recall scene 2
Recall scene 3
…
Recall scene 64
128
129
130
…
191
Store scene 1
Store scene 2
Store scene 3
…
Store scene 64
8
Output X
Forced output
1bit/2bit
C,W
1.003 DPT_Enable /2.001 DPT_Switch
This object will be enabled after enabling the forced function.
If 1bit, Enable the forced operation with “1”, and the device behaviors will be ignored except the forced function; cancel the forced
operation with “0”. The contact position of force operation can be set via a parameter.