Fig.4.15 Parameter window“X
:
Auto.”
Parameter
“
Function automatic
”
The parameter is used to set whether the Auto. Control operation is activated, i.e. the Automatic sun protection
function. Options:
Inactive
Active
If the option
“
Active
”
is selected, the following three parameters will be visible. The communication
objects
“
Enable auto. control
”
,
“
Sun operation
”
,
“
Sun: Shutter position [0
…
100%]
”
and
“
Sun: slat adj. [0
…
100%]
”
also will be visible.
When the object
“
Enable auto. control
”
receives a telegram
“
1
”
, the Auto. Operation is activated. When
the object
“
Enable auto. control
”
receives a telegram
“
0
”
or the user sends a direct movement command (e.g.
UP/DOWN, move to position etc.), the Auto. Operation is deactivated. If the command is not belong to the direct
movement command (e.g. store scene etc.), the Auto. Operation is still activated.
The priority of direct operation and automatic operation is the same, but they cannot occur at the same time.
Note: After the automatic operation is deactivated, only when the object “Enable auto. control” receives a
telegram “1”or the set time for the direct operation to automatic has elapsed (see parameter “Enable auto.
Control after [10
…
6000min]
”
), it can be activated again.
Parameter
“
Object value of
“
Disable auto. Control
”
after bus voltage recovery
”