background image

 

D1130 

- Switch / Proximity Detector Repeater Relay Output 

G.M. International ISM0048-8 

D1130 series are isolated Intrinsically Safe Associated Apparatus installed into standard EN50022 T35 DIN Rail located in Safe Area/Non Hazardous Locations or Zone 2, Group IIC, 
Temperature Classification T4, Class I, Division 2, Groups A, B, C, D, Temperature Code T4 and Class I, Zone 2, Group IIC, IIB, IIA Temperature Code T4 Hazardous Area/Hazardous  
Locations (according to EN/IEC60079-15, FM Class No. 3611, CSA-C22.2 No. 213-M1987, CSA-E60079-15) within the specified operating temperature limits Tamb -20 to +60 °C, and 
connected to equipment with a maximum limit for AC power supply Um of 250 Vrms. 

Non-incendive field wiring is not recognized by the Canadian Electrical Code, installation is permitted in the US only. 
For installation of the unit in a Class I, Division 2 or Class I, Zone 2 location, the wiring between the control equipment and the D1130 associated apparatus shall be accomplished 
via conduit connections or another acceptable Division 2, Zone 2 wiring method according to the NEC and the CEC. 
Not to be connected to control equipment that uses or generates more than 250 Vrms or Vdc with respect to earth ground. 
D1130 series must be installed, operated and maintained only by qualified personnel, in accordance to the relevant national/international installation standards 
(e.g. IEC/EN60079-14 Electrical apparatus for explosive gas atmospheres - Part 14: Electrical installations in hazardous areas (other than mines), BS 5345 Pt4, VDE 165, 
ANSI/ISA RP12.06.01 Installation of Intrinsically Safe System for Hazardous (Classified) Locations, National Electrical Code NEC ANSI/NFPA 70 Section 504 and 505, 
Canadian Electrical Code CEC) following the established installation rules, particular care shall be given to segregation and clear identification of I.S. conductors from non I.S. ones. 
De-energize power source (turn off power supply voltage) before plug or unplug the terminal blocks when installed in Hazardous Area/Hazardous Locations or 
unless area is known to be nonhazardous. 

Warning: substitution of components may impair Intrinsic Safety and suitability for Division 2, Zone 2. 
Warning: de-energize main power source (turn off power supply voltage) and disconnect plug-in terminal blocks before opening the enclosureto avoid electrical shock 
when connected to live hazardous potential. 
Explosion Hazard: to prevent ignition of flammable or combustible atmospheres, disconnect power before servicing or unless area is known to be nonhazardous. 

Failure to properly installation or use of the equipment may risk to damage the unit or severe personal injury. 
The unit cannot be repaired by the end user and must be returned to the manufacturer or his authorized representative. Any unauthorized modification must be avoided. 

 

Warning 

Operation 

 

D1130 accepts as an input from Hazardous Area/Hazardous Locations a proximity sensor or voltage free electrical contact and repeats their status to Safe Area/Non Hazardous 
Locations by a voltage free SPDT relay contact. Presence of supply power and status of output (energized or de-energized), as well as integrity or fault condition of sensor and 
connecting line are displayed by signaling LEDs (green for power, yellow for status and red for fault condition). D1130D (dual channel type) has two independent input channels and 
actuates the corresponding output relay SPDT contact; two actuation modes can be independently DIP switch configured for each input channel: 
Normally open input / Normally energized relay  or 

Normally close input / Normally energized relay. 

Contact or proximity sensor and its connection line short or open circuit fault detection is also DIP switch configurable. Fault detection can be enabled (in case of fault de-energizes the 
corresponding output channel relay and turns ON the fault LED) or be disabled (in case of fault the corresponding output channel relay repeats the input line open or close status as 
configured). D1130S (single channel type) has one input channel and two output relays; the unit has two DIP switch configurable operating modes: 
A) Input channel actuates in parallel output relays SPDT contacts (providing a DPDT type of output). Relays actuation can be independently configured for each output in two modes: 
Normally open input / Normally energized relay  or 

Normally close input / Normally energized relay. 

B) Input channel actuates output relay (A) SPDT contacts configurable in two modes as above. Output relay B operates as fault output (in case of input fault, relay B actuates and the 
fault LED turns on while relay A repeats the input line as configured). Actuation can be configured in two modes: 
No input fault / Energized relay (it de-energizes in case of fault) or No input fault / De-energized relay (it energizes in case of fault). 
Note: use of voltage free electrical contacts with fault detection enabled requires, near the switch at the end of the line, a 1 K

 series connected resistor and a 10 K

 parallel connected 

resistor in order to allow the fault detection circuit to distinguish between a condition of contact close/open and a line open/short circuit fault. 

 

D1130 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

FM Approved under Entity Concept,

or third party approval

Hazardous (Classified) Locations

Class I, Division 1, Groups A, B, C, D

Class II, Division 1, Groups E, F, G

Class III, Division 1

Class I, Zone 0, Group IIC, IIB, IIA

Intrinsically 

Safe Equipment

Must not use or generate

more than 250 Vrms or Vdc

Control 

Equipment

Unclassified Locations

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D

Class II, Division 2, Groups E, F, G

Class III, Division 2

Class I, Zone 2, Group IIC, IIB, IIA

FM Approved under non-incendive field

wiring (permitted only for US installations),

or third party approval

13
14

1
2

+

-

Power Supply

3 L/+

4 N/-

16

15

-

+

Intrinsically 

Safe Equipment

Unclassified Locations or

Hazardous (Classified) Locations

Class I, Division 2, Groups A, B, C, D, T-Code T4

Class I, Zone 2, Group IIC, IIB, IIA, T-Code T4

Unclassified Locations

Must not use or generate

more than 250 Vrms or Vdc

8

Control 

Equipment

7

6

5

+

Non-incendive

Equipment

Non-incendive

Equipment

+

-

-

1

13

16

15

14

7

6

5

8

2

Control 

Equipment

Power Supply

Control 

Equipment

D1130 Associated Apparatus

FM Approved

under Entity Concept

and non-incendive field wiring

3 L/+

4 N/-

Содержание D1130D

Страница 1: ...D1130 Switch Proximity Detector Repeater Relay Output ISM0048 8 D1130S D1130D INSTRUCTION MANUAL INSTRUCTION MANUAL Switch Proximity Detector Repeater Relay Output DIN Rail Models D1130S D1130D ...

Страница 2: ...channels D1130D 1 9 W for 1 channel D1130S Isolation Test Voltage I S In Out 2 5 KV I S In Supply 2 5 KV Out Supply 2 5 KV Out Out 2 5 KV Input switching current levels ON 2 1 mA OFF 1 2 mA switch current 1 65 mA 0 2 mA hysteresis Fault current levels open fault 0 2 mA short fault 6 8 mA when enabled both faults de energize channel relay with dual channel unit D1130D or actuate fault relay with si...

Страница 3: ...ut for fault detection on single channel version Three port isolation Input Output Supply EMC Compatibility to EN61000 6 2 EN61000 6 4 In field programmability by DIP Switch ATEX IECEx UL C UL FM FM C Russian and Ukrainian Certifications Type Approval Certificate DNV and KR for marine applications High Reliability SMD components High Density two channels per unit Simplified installation using stan...

Страница 4: ... Normally Opened NO 2 L Power Supply 115 230 Vac 3 N Power Supply 115 230 Vac 4 Output Ch 2 Common 5 Output Ch 2 Relay Normally Opened NO 6 Output Ch 2 Relay Normally Closed NC 7 Output Ch 1 Relay Normally Closed NC 8 D1130S Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact HAZARDOUS AREA SAFE AREA Input Ch 1 for Proximity or Input Ch 1 for Voltage free Contact 13 14 Output Ch 1 A Co...

Страница 5: ...pparatus Parameters Ci Ci device C cable Li Li device L cable Li Ri device and L cable R cable IIC A B Co Ca 2 23 µF Co Ca 15 6 µF Co Ca 69 µF IIB C IIA D IIC A B Lo La 172 mH Lo La 689 mH Lo La 1379 mH IIB C IIA D IIC A B Lo Ro 930 µH Ω Lo Ro 3720 µH Ω Lo Ro 7440 µH Ω IIB C IIA D NOTE for USA and Canada IIC equal to Gas Groups A B C D E F and G IIB equal to Gas Groups C D E F and G IIA equal to G...

Страница 6: ...NE 2 GROUP IIC T4 NON HAZARDOUS LOCATIONS CLASS I DIVISION 2 GROUPS A B C D T Code T4 CLASS I ZONE 2 GROUP IIC T4 MODEL D1130D 13 14 3 L 4 N 8 NC 2 NO 1 COM Supply 115 230 Vac Out 1 In 1 15 16 7 NC 6 NO 5 COM In 2 Out 2 voltage free Contact Proximity Proximity Common positive connection _ voltage free Contact MODEL D1130S 13 14 8 NC 2 NO 1 COM Out 1 A In 1 7 NC 6 NO 5 COM Out 1 B voltage free Cont...

Страница 7: ...ult condition of sensor and connecting line are displayed by signaling LEDs green for power yellow for status and red for fault condition D1130D dual channel type has two independent input channels and actuates the corresponding output relay SPDT contact two actuation modes can be independently DIP switch configured for each input channel Normally open input Normally energized relay or Normally cl...

Страница 8: ...50022 D1130 unit can be mounted with any orientation over the entire ambient temperature range see section Installation in Cabinet and Installation of Electronic Equipments in Cabinet Instruction Manual D1000 series for detailed instructions Electrical connection of conductors up to 2 5 mm are accommodated by polarized plug in removable screw terminal blocks which can be plugged in out into a powe...

Страница 9: ...tection ON IN OUT Operation NO NE or NC ND NO ND or NC NE ON 1 OFF 4 4 3 3 Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resistor ON 13 2 OFF NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND 13 NO 14 1 2 8 NE OR NC 13 14 1 2 8 ND Side A Panel View Input Output Input Output Output Input Output Input CH2 Setting Line fault detection ON IN OUT Operation NO NE or NC ND...

Страница 10: ...led proximity sensor or contact with terminating line resistor Out B Out A 1 2 8 5 6 7 Out A 1 2 8 Out B 5 6 7 No Fault 5 6 7 5 6 7 NE NE NE ND ND NE No Fault D1130D Configuration Summary Table Channel IN OUT Operation NO NE or NC ND NO ND or NC NE SW2 OFF SW4 OFF ON 1 2 Channel Line fault detection Disabled contact proximity sensor Enabled proximity sensor or contact with terminating line resisto...

Отзывы: