6. Trouble Shooting
Fault
Cause
Solution
No Sound
BT
Headphones
not
paired.
Headset Volume control is
too low
BT Headset not charged
Pair Headset.
Increase headset
volume control.
Charge Headset
regularly like a mobile
phone
No Display of
Correlator
Dead batteries
Charge unit
No radio
Connection to
Sensors
Low battery on Sensors
Sensors turned off
Charge sensors using
Car charger
Switch sensors on
Poor
Correlation
spectra
Poor sensor or radio
contact
Reposition the sensors
Clean magnet contact
area
Fit Antenna extension
cable
Corrupt
Display
Memory corruption
Clear memory
Radio
signal
bars strong full
in one sensor
and 1or 2 bars
in the other
Stood next to 1 sensor-
Air couple with 1 sensor
causing interference with
the other
Move half way between
sensors
with
the
Correlator
Correlation
doesn’t
stop
processing
Corr Settings on infinite
Change Corr Settings or
manually
stop
correlation
Centre
Correlation
Sensors on different pipes
Parallel Mains
Move sensors to same
pipe
Result is 0 or
negative
The leak noise is from a
leaking hydrant which the
sensor is on or beyond
the sensor
Fix the Hydrant
Move the sensor to
bring leak in bracket
Leak result is
out by several
meters
Incorrect Velocity- wrong
pipe material or age of
pipe
Perform a velocity check
Leak result on
a Tee section
Leak could be up the
branch of the Tee section
Move sensor to next
section of the Tee