AQUASCAN 610
33/41
Version 1.1
5.1
Positioning of Accelerometers
Fig. 48 the
‘A’ Sensor attached to a hydrant spindle
It is critical the accelerometer is positioned in the location that has the
least interference and the clearest leak noise. Moving the sensor 10
mm can make a massive difference to their performance. The listen
function (see chapter 4.3) should always be used on sensor
deployment and the sensor should be positioned so that the highest
frequency noise is heard minimising the effect of electrical and
mechanical noise. If the chambers are deep enough to take the sensor
with antenna then the lid maybe shut (see fig 49) however metallic lids
will attenuate the signal reducing the distance of the radio range.
Fig. 49 the AquaScan Se nsor deployment