beeper mode show
linesensor {line_num} {energy_sensor} maxval set
{float}
sets maximum value for line meter
linesensor {line_num} {energy_sensor} maxval
show
shows maximum value for line meter
linesensor {line_num} {energy_sensor} minval set
{float}
sets minimum value for line meter
linesensor {line_num} {energy_sensor} minval
show
shows minimum value for line meter
linesensor {line_num} {energy_sensor} hyst set
{float}
sets hysterese value for line meter
linesensor {line_num} {energy_sensor} hyst show shows hysterese value for line meter
linesensor {line_num} {energy_sensor} publish
mode set {NONE=0|INTERVAL=1|DELTA=2|
INTERV_DELTA=3}
sets publish mode
linesensor {line_num} {energy_sensor} publish
mode show
shows publish mode
linesensor {line_num} {energy_sensor} publish
mqtt retain set {OFF=0|ON=1}
sets mqtt retain
linesensor {line_num} {energy_sensor} publish
mqtt retain show
shows if mqtt retain set
linesensor {line_num} {energy_sensor} publish
timer set {num_secs}
sets publish time interval
linesensor {line_num} {energy_sensor} publish
timer show
shows publish time interval
linesensor {line_num} {energy_sensor} publish
delta set {float}
sets publish delta value
linesensor {line_num} {energy_sensor} publish
delta show
shows publish delta value
linesensor {line_num} events set {OFF=0|ON=1}
LEGACY - enables events on/off
L
linesensor {line_num} events show
LEGACY - shows if events are enabled
L
linesensor {line_num} events type set
"{EVT_SYSLOG=0,EVT_SNMP=1,EVT_EMAIL=2
,EVT_SMS=3,EVT_GSMEMAIL=4,EVT_BEEPER
=5,EVT_DISPLAY=6,EVT_CONSOLE=7,EVT_M
QTT=8}"
LEGACY - enables different event types
L
linesensor {line_num} events type show
LEGACY - shows what event types are enabled
L
linesensor {line_num} maxval set {float}
LEGACY - sets maximum value for line meter
L
linesensor {line_num} maxval show
LEGACY - shows maximum value for line meter
L
linesensor {line_num} minval set {float}
LEGACY - sets minimum value for line meter
L
linesensor {line_num} minval show
LEGACY - shows minimum value for line meter
L
linesensor {line_num} hyst set {float}
LEGACY - sets hysterese value for line meter
L
linesensor {line_num} hyst show
LEGACY - shows hysterese value for line meter
L
linesensor beeper set {OFF=0|ON=1}
enables beeper for line meter alarms
linesensor beeper show
shows if beeper for line meter alarms is enabled
modbus
enters cmd group "modbus"
modbus enabled set <off=0/on=1>
enables Modbus TCP support
modbus enabled show
shows if Modbus is enabled
modbus port set <ip_port>
sets Modbus TCP port
modbus port show
shows Modbus TCP port
mqtt
enters cmd group "mqtt"
mqtt {broker_idx} enabled set {OFF=0|ON=1}
enable mqtt
mqtt {broker_idx} enabled show
shows if mqtt enabled
mqtt {broker_idx} server set "{dns_name}"
sets broker name
mqtt {broker_idx} server show
shows broker name
mqtt {broker_idx} tls enabled set {OFF=0|ON=1}
enable TLS
mqtt {broker_idx} tls enabled show
shows if TLS enabled
mqtt {broker_idx} port set {ip_port}
set broker TCP/IP port
mqtt {broker_idx} port show
shows broker TCP/IP port
mqtt {broker_idx} user set "{username}"
sets username
mqtt {broker_idx} user show
shows username
mqtt {broker_idx} passwd set "{passwd}"
sets password
mqtt {broker_idx} passwd hash set "{passwd}"
sets hashed passwd
mqtt {broker_idx} client set "{name}"
sets client name
mqtt {broker_idx} client show
shows client name
mqtt {broker_idx} qos set {QOS0=0|QOS1=1}
sets QoS level
mqtt {broker_idx} qos show
shows QoS level
mqtt {broker_idx} keepalive set {num_secs}
sets keep-alive time
mqtt {broker_idx} keepalive show
shows keep-alive time
mqtt {broker_idx} topic set "{name}"
sets topic prefix
mqtt {broker_idx} topic show
shwos topic prefix
mqtt {broker_idx} console enabled set {OFF=0|
ON=1}
permit console cmds
mqtt {broker_idx} console enabled show
shows if console cmds allowed
mqtt {broker_idx} device data timer set
sets telemetry interval
Содержание Expert PDU Energy 8340 Series
Страница 2: ...2 Expert PDU Energy 8340 8341 2021 GUDE Systems GmbH...
Страница 5: ...Device Description...
Страница 12: ...12 Expert PDU Energy 8340 8341 2021 GUDE Systems GmbH Device Description...
Страница 13: ...Operating...
Страница 21: ...Configuration...
Страница 43: ...Specifications...
Страница 76: ...Support...
Страница 81: ...81 Expert PDU Energy 8340 8341 2021 GUDE Systems GmbH Index Timer 33 Timer Configuration 33 TLS 53...