68
Expert PDU Energy 8311
© 2021 GUDE Systems GmbH
Specifications
Device Resource
Start
End
Function
Info Bereich
0x000 0x005
see table
CPU Sensor values
0x080 0x083
see table
Externe Sensoren
0x100 0x1ff
see table
Fan Level
0x200 0x20f
0 (aus) bis 3 (maximal)
Line Energy Sensors
0x400 0x39ff
see table
Port Energy Sensors
0x3a00 0x81ff
see table
Bank Energy Sensors
0x8200 0x823f see table
Power Source Sensors
0x8240 0x827f see table
Residual Current Monitor 0x8280 0x82cf see table
Info Area
Address
Width
Information
0
16-bit
Number of Ports (Relay)
1
16-bit
Number of Ports (Outlets) with
Energy Measurement
2
16-bit
Number of Banks
3
16-bit
Number of Line-In
4
16-bit
Phases per line
5
16-bit
Number of Inputs
Sensor Type Description
Address
Width
Information
0x080 to 0x083
16-bit (signed
CPU Sensor values
0x100 to 0x1ff
16-bit (signed)
external Sensors
0x400 to 0x39ff
32-bit (signed)
Line Energy Sensors
0x3a00 to 0x81ff
32-bit (signed)
Port Energy Sensors
0x8200 to 0x823f
16-bit (signed)
Bank Energy Sensors
0x8240 to 0x827f
16-bit (signed)
Power Source Energy Sensors
0x8280 to 0x82cf
16-bit (signed)
Residual Current Monitor
CPU Sensor Values
Offset
Sensor Field
Unit
0
Vsystem
0.01 V
1
Vaux
0.01 V
2
Vmain
0.01 V
3
CPU Temperature
0.1 °C
External Sensors:
The measured value of the external sensors are coded as fixed point arithmetic. For a
factor of e.g. 0.1 in the unit the value must be divided by 10 in order to reach the real
measured value. A value of 0x8000 means that no sensor is plugged into the corres-
ponding port, or the corresponding field in the sensor is not available. The formula for
the address is (the port numbers start at zero):
0x100 + Port * 8 + Offset
In the Expert Sensor Box 7213 / 7214 the internal sensor corresponds to the
value Port = 0, and is coded Port = 1 for Sensor 2 and Port = 2 for Sensor 3.
Содержание Expert PDU Energy 8311 Series
Страница 1: ...Expert PDU Energy 8311 Series Manual 2021 GUDE Systems GmbH Manual Ver 1 5 0 from Firmware Ver 1 5 ...
Страница 2: ...2 Expert PDU Energy 8311 2021 GUDE Systems GmbH ...
Страница 5: ...Device Description ...
Страница 12: ...Operating ...
Страница 22: ...Configuration ...
Страница 44: ...Specifications ...
Страница 75: ...Support ...
Страница 80: ...80 Expert PDU Energy 8311 2021 GUDE Systems GmbH Index Timer 34 Timer Configuration 34 TLS 53 ...
Страница 81: ...81 Expert PDU Energy 8311 2021 GUDE Systems GmbH Expert PDU Energy 8311 2021 GUDE Systems GmbH 11 18 2021 ...