background image

Note: This is a control system which must be cleaned and maintained regularly (see Maintenance Guide and Record card included with valve shipment).

5

Guardian Equipment 
1140 N North Branch St 
Chicago, IL 60642

312 447 8100 

telephone

 

312 447 8101 

facsimile 

gesafety.com

rev. 1215 / © 2015  Guardian Equipment

Installation, Operation and Maintenance Guide

G3900LF Series Thermostatic Mixing Valves

Thermostatic Mixing Valve Parts

Checkstop Parts

Repair Kits

Lockable Pointer (su

ffi

x “LTR”)

Notes:
1.  After installing new parts, the 

adjustable high temperature limit 

stop must be reset (see page 2).

2.  All G3900LF and G3950LF valves 

are furnished with lockable 

pointers. 

Repair kit Includes parts to repair both hot and cold checkstops

2

1

3

4

6

8

7

5

9

10

11

12

13

14

16

16

24

25

25

26

26

22

23

TM-36 

 

Pointer Set Screw

17

17

18

18

20

20

21

19

15

Item Part No.

Description

1

57

-

L

Snap Cap

2

TM

-

29/29A

Pointer Screw

3

TM

-

25C

Pointer

4

30

Friction Spring

5

617

Dial Plate

6

TM

-

25D

Stop Screw

7

TM

-

16

Cover Screws (6)

8

TM

-

15B/125

Cover

9

TM

-

21/125

Flange Packing

10

TGM

-

2/125

Thermostat Group

11

TGM

-

1/125M

Port Sleeve Assembly

12

TM

-

3/125M

Port Sleeve Nut Assembly

13

TM

-

8

Coil Sleeve Stud

14

TM

-

28A

Pointer Rod

Item Part No.

Description

15

MU

-

5A

O-Ring

16

03

Lower Stem & Packing

17

011

Spring (Hot Side)

015

Spring (Cold Side)

18

MU

-

5A

O-Ring

19

MU

-

4A

Upper Stem

20

05

Packing

21

02

Bonnet

22

04/125

Swivel

23

09/125

Swivel Nut

24

06

Strainer Cap

25

014

Cap Packing

26

013

Screen

R/125M

 

Repair Kit

2/50M

 

Checkstop Kit

Содержание G3900LF Series

Страница 1: ... be easily cleaned adjusted or repaired 2 Inlets are clearly marked on valve body casting Connect hot water to inlet marked HOT and cold water to inlet marked COLD 3 Included angle checkstops must be installed on both supply lines 4 Use solder or pipe cement sparingly Flush supply pipes before connecting valve Flush outlet pipe and valve once valve is connected Maximum operating pressure is 125 PS...

Страница 2: ...screw Remove snap cap pointer screw washer and pointer 2 Activate emergency fixture 3 Temporarily place pointer on pointer rod and turn handle to the left allowing cold water to flow Then slowly adjust handle to the right until the required maximum temperature is reached Note Temperatures above 90 F are not recommended Consult a medical advisor for correct temperature settings 4 Once maximum tempe...

Страница 3: ...y thermostatic mixing valve on the G3950LF 2 Activate emergency equipment and allow temperature to reach set point 3 Turn primary thermostatic mixing valve to full cold and wait ten seconds 4 Turn primary thermostatic mixing valve to full hot and wait ten seconds 5 Verify outlet temperature does not exceed 90 F 32 C 6 Turn primary thermostatic mixing valve to full cold and wait ten seconds 7 If ne...

Страница 4: ... with non corrosive agent and soft cloth DO NOT USE ABRASIVES Wash parts thoroughly after cleaning and reassemble Install port sleeve with elongated holes nearest the check nut and tighten port sleeve nut against port sleeve assembly DO NOT OVERIGHTEN Tighten check nut against valve body Driving ball on thermostat group should then be inserted into ball socket for final reassembly Figure 1 To Repl...

Страница 5: ...nters Repair kit Includes parts to repair both hot and cold checkstops 2 1 3 4 6 8 7 5 9 10 11 12 13 14 16 16 24 25 25 26 26 22 23 TM 36 PointerSetScrew 17 17 18 18 20 20 21 19 15 Item Part No Description 1 57 L Snap Cap 2 TM 29 29A Pointer Screw 3 TM 25C Pointer 4 30 Friction Spring 5 617 Dial Plate 6 TM 25D Stop Screw 7 TM 16 Cover Screws 6 8 TM 15B 125 Cover 9 TM 21 125 Flange Packing 10 TGM 2 ...

Страница 6: ...YSTEM PRESSURE DROP 5 10 15 20 25 30 35 40 45 PSI L MIN 3 7 1 0 1 4 1 7 2 1 2 4 2 8 3 1 BAR G3900LF G3950LF 1 1 4 1 1 2 3 40 53 64 72 81 90 99 108 117 126 GPM 11 151 201 242 273 307 341 374 409 443 477 L MIN MAXIMUM FLOW CAPACITY Limited Warranty Guardian Equipment warrants the original purchaser that its products will be free from defects in materials and workmanship under normal usage conditions...