background image

 
 

 

21-3618v1.1 

MONITOR ISM™ / AFx™ Suite Security 4 Zone Keypad Installation   

 

 

CSG Security Corp. / Sécurité CSG Corp.

 

Page 

3

 of 4 

 Guardall
 

5201 Explorer Drive, Mississauga, Ont., Canada.  

L4W-4H1

[email protected]  +1 905.206.8434  |  [email protected]  +1 905.206.8436  |  Fax: +1 905.629.4970

www.guardall.com  |  +1 877.249.9993 

Power and Cable Requirements: 

 

Power Requirements 

 

Each 4 zone keypad’s current draw is 110 mA. Multiple modules cannot be powered direct from the module bus. A 
local power supply must be used. 

 

Power supplies must be located very locally to their 4 zone keypads. 

 

All power supply negatives must be common and connected to the ISM panel module bus negative. 

 

Power supply wiring has to be of a gauge large enough to provide correct voltage at the last module in a run, belonging 
to that power supply. Typically 18 gauge or larger. 18 gauge power cable: Guardall P/N 947-3400. 

 

In a multiple floor, riser installation with a height of 10 feet (3.1 meters)/floor, using 18 gauge power cable with a lead in 
of up to 100 feet (30.5 meters) from power supply to the first module, the power supply will be limited to powering 
seven modules, only. This will ensure 12V at the last module of the group. The next group of 7 modules up in a vertical 
formation, would then need their own power supply, located within 100 feet (30.5 meters) of that next group’s first 
module. 

 

Seven modules will require a minimum 1 AMP power supply. A larger capacity power supply can be used, however, it 
is still limited to seven modules, due to the power loss in the cable. 

 

A 4 zone keypad requires 12 to 13.8 volts DC to function normally. However, under extreme conditions (e.g. primary 
power loss) it can still process activities marginally at 10VDC.   

 

The module communication cable must not carry the power supply current because of the smaller wire gauge. 

 

Both wires in the power cable must be of the same gauge (e.g. 18AWG). 

 

However, the spare wire pair of the communication cable can be used to common the negatives of the various power 
supplies with each other and the ISM module bus 0V negative, which, is required. 

 

Cable Requirements for Module Bus Data A and B  

 

24AWG, 2 twisted stranded pair, shielded, with an impedance value of 120 ohm, low capacitance: 12.5-pF/1 foot (41- 
pF/1 meter), e.g. Belden 9842. Guardall P/N 947-3401 communication cable meets these specifications. 

  The communication cable shield is grounded at the ISM main panel end (e.g. panel ground lug). “B” connected 

together at each module interconnection and cut off, not connected to anything, at the last module in the group. 

 

The maximum module cable distance is 2000 ft (610 meters) per ISM main panel module bus 1 or 2 at the main control 
unit motherboard. Module star wiring configurations cannot be used. Module connections must run on a straight trunk, 
with no straight out, branch offs to another module. You must go out to the module and come back with the cable to go 
to the next module. 

 

For ISM main panel module Bus 1 and 2 should be evenly balanced with up to 30 Suite Security keypads each to equal 
the system capacity of 60. 

 

If more than 30 modules are required to be on a single bus, a SNAPP Expander module should be placed in series with 
the SNAPP bus to split the modules into approximately two equal groups along the length of the SNAPP bus. The 
SNAPP Expander module should be located near a power supply to provide power to the expander as well as the 4 
zone modules. 

 

Special Installation and Servicing 4 Zone Keypad Command Features: 

 

Display a 4 Zone Keypad’s 5-Digit Programming Serial Number:

 

Prevents the need to remove the keypad housing from its base to review the Suite Security programming serial number 
label on the back of the keypad’s printed circuit board.  

1.  Number is displayed for 4 seconds after the 7 second power up delay. 

2. 

If unit is already powered then 

 

 

enter a valid ‘PIN’, 

 

 

select “Status”  

 

 select 

“Other” 

 

 

Display will show the F/W version and unit serial number.

     

 

Содержание MONITOR ISM

Страница 1: ...e Typical Steps cde 1 Read Do s Don ts above ensure all installation instructions are present 2 Unpack and check all items Ensure you have all necessary items including Director software main panel all modules and peripherals sensors all cabling and all related documentation 3 Plan device and sensor locations and run all cables as required To prevent damage run cables before mounting the specific ...

Страница 2: ...ad front to the keypad back The spring compressing should reset the keypad tamper condition Knock outs for rectangular conduit using additional keypad base Keypad Back Keypad Front Circuit board pin connectors insert into fixed terminal blocks on inside of keypad back This allows the keypad to make wire connections in the terminal blocks Terminal Block Terminal Block Tamper Spring Sonalert Cable A...

Страница 3: ... the same gauge e g 18AWG However the spare wire pair of the communication cable can be used to common the negatives of the various power supplies with each other and the ISM module bus 0V negative which is required Cable Requirements for Module Bus Data A and B 24AWG 2 twisted stranded pair shielded with an impedance value of 120 ohm low capacitance 12 5 pF 1 foot 41 pF 1 meter e g Belden 9842 Gu...

Страница 4: ...nge 10 to 93 FCC Compliance Statement This device complies with Part 15 of the FCC Rules Operation is subject to the following two conditions 1 This device may not cause harmful interference and 2 This device must accept any interference received including interference that may cause undesired operation This equipment has been tested and found to comply with the limits for a Class B digital device...

Отзывы: