Installing the Receiver

Use the transmitter to check the range of the receiver 

before permanently mounting it

.

Consider the following when mounting the receiver:

•  Standard receiver cable length is 0 feet (receivers with a longer cable are available as special  
    order items; 

call the GTO Sales Department

).  NEVER splice receiver cable!

•  

Run the cable through PVC conduit to protect it from damage.

 

•  DO NOT run cable through metal conduit because the receiver signal range will be decreased.
•  DO NOT run cable in conduit containing ac wiring.
•  DO NOT mount receiver on a metal fence or post; doing so will decrease signal range.
•  The receiver range can vary from 50 to 00 feet depending upon weather, topography, and
    external interference.

•  

DO NOT

 

mount upside down.

•  

MOUNT

 

so that you have line of sight between remote and antenna.

•  

MOUNT

 

3 feet away from AC voltage.

FCC Regulation

This device complies with FCC rules Part 5.  Operation is subject to the following 
conditions:
. This device may not cause harmful interference.
2. This device must accept an interference that may cause undesired operation.

Transmitter distance may vary due to circumstances beyond our control.  

NOTE:

 

The manufacturer is not responsible for any radio or TV interference caused by 
unauthorized modifications to this equipment. Such modifications could void the 
user’s authority to operate the equipment.

Stall Force Potentiometer

ALWAYS KEEP 

SAFETY

 AT THE TOP OF YOUR LIST WHEN ADJUSTING OR

SERVICING YOUR AUTOMATIC GATE OPENER!

1

  2

  3

  4

O

N

 

OFF

SOFT  START  OFF
WARNING       OFF
OPEN                PULL
SLV    OPEN     DLY.
MODE1               OFF
MODE2               OFF

ON
ON
PUS
SIM
ON
ON

120 MIN

AUTO CLOSE  TIME 

STALL   FO

1

  2

  3

  4

O

N

 

OFF

SOFT  START  OFF
WARNING       OFF
OPEN                PULL
SLV    OPEN     DLY.
MODE1               OFF
MODE2               OFF

ON
ON
PUS
SIM
ON
ON

120 MIN

O CLOSE  TIME

STALL   FO

O

S

M

TO

O

1

  2

O

N

ON
ON

0 MIN

MAX

STALL   FORCE

MIN

MAX

STALL   FORCE

IMPORTANT:

  For safety reasons the 

obstruction setting or 

Stall Force

 on the GTO/

PRO® 2002XL control board comes from 
the factory set at 

MIN

 (minimum). In many 

gate installations this setting will need to be 
adjusted to overcome the weight and size of 
the gates.

The 

Stall Force 

potentiometer on the control 

board operates like a volume control on a radio.  
It controls the obstruction sensitivity (or the amount 
of force the opener will apply to an obstruction) 
before it automatically stops and reverses direction for 
approximately two (2) seconds. 

Use a small slotted screwdriver to turn the arrow in the center of 
the potentiometer. Adjust the sensitivity from the MINIMUM position 
where the gate operates without obstructing from its own weight or the 
wind conditions in your area.

NOTE:  You may need to increase the stall force in cold weather due to 
increased resistance from gate hinges.

Содержание SW-2002XL

Страница 1: ...t or any other legal theory during the course of the warranty or at any time thereafter The installer and or user agree to assume responsibility for all liability and use of this product releasing GTO...

Страница 2: ...locations not servicing the general public in which unauthorized access is prevented via supervision by security personnel The GTO PRO 2002XL Gate Operator is intended for use with vehicular swing gat...

Страница 3: ...he Second Opener page 16 Installation of the Closed Position Stops page 17 Mounting the Control Box page 19 Connecting the Opener Power Cables page 20 Powering the System page 21 Solar Chart page 21 C...

Страница 4: ...op The GTO PRO 2002XL Operator accommodates extra transmitters digital keypads solar panels push buttons automatic gate locks and other access control products These optional accessories see the enclo...

Страница 5: ...tions and warnings in this manual are identified with this warning symbol The symbol identifies conditions that can result in damage to the opener or its components serious injury or death Because GTO...

Страница 6: ...e type and size of gate its frequency of use and the proper class rating 2 Make sure the dual gate has been properly installed and swings freely in both directions Repair or replace all worn or damage...

Страница 7: ...vices such as contact sensors safety edges and non contact sensors photo beams provide additional protection against entrapment 4 If push buttons or key switches are installed they should be within si...

Страница 8: ...h and spray with silicone at least once per month 7 Service the gate and gate opener regularly Grease hinges spray push pull tube with high quality silicone spray and replace the battery every 3 5 yea...

Страница 9: ...nals to the gate opener for entrapment protection functions shall be located where the transmission of the signals are not obstructed or impeded by building structures natural landscaping or similar o...

Страница 10: ...te operation and are required when installing the GTO PRO 2002XL Automatic Gate Operator Furthermore a walk through gate must be installed if pedestrian traffic is expected near the vehicular gate We...

Страница 11: ...SERIES GTO Inc Tallahassee Florida USA Disconnect operator ONLY when the control box power switch is OFF and the gate is NOT moving LISTED US C Product identification and manual operation instruction...

Страница 12: ...5ObS S S e eS 1OPZS 5ObS S S e eS 1OPZS 5ObS 0 OQYSb ab Wd b 0 OQYSb 1cab S Ac b 1O R ab 0 OQYSb 1Z aSR aWbW Ab ZObS E Z GATE OPENER 6OW W 1ZW f 1ZSdWa W f 0 Zb f 0 Zb f 0 Zb f 0 Zb EOaVS QY EOaVS EO...

Страница 13: ...he transformer power supply and the control box See Powering the System on page 21 and the Accessory Catalog PVC conduit If your gate is more than 1000 away from an ac power source you will need to us...

Страница 14: ...mounting point to mounting point Max stroke is 13 Adjustable auto close timer and obstruction sensitivity Power terminal bock accommodates a transformer or solar panels DIP switches simplify setup of...

Страница 15: ...verview Pull to Open Gates Gate Opens into the Property The diagram shown below is an example of a pull to open installation on a chain link fence and dual gates Furthermore if you have push to open g...

Страница 16: ...rust of the opener from pulling the bolts and washers out of the wood NOTE A fence post smaller than 6 in diameter or 6 square should be made of metal instead of wood so that it will remain stable whi...

Страница 17: ...ce post and gate Step 3 IInsert the 3 8 x 2 bolt through the center hole of the post brackets and post pivot bracket as shown Fasten a 3 8 lock washer 3 8 washer and 3 8 nut on the end of the bolt DO...

Страница 18: ...nt clearances With the post pivot bracket in the optimum position for clearance and freedom of movement reattach the opener to the gate bracket in the open position and recheck the gate opener level a...

Страница 19: ...e bolts longer than 8 not supplied must be used Step 10 Mark reference points for bolt holes on the gate cross member through middle of gate bracket slots Drill 3 8 holes into the gate cross member as...

Страница 20: ...cket assembly if necessary SdSZ S Ob 4S QS ab 5ObS 7 S aWbW 3D3 V Wh bOZ Q aa S PS ab 0 OQYSb aaS PZg P ZbSR b TS QS ab 1ZSdWa W 0caVW U O R 6OW W 1ZW 1ZSdWa W 0caVW U O R 6OW W 1ZW 5ObS 0 OQYSb P ZbS...

Страница 21: ...erred to as the SLAVE gate and gate opener Closed Position Stop Plate mounted horizontally on metal post with U bolts SLAVE Gate Frame MASTER Gate Frame TOP VIEW FRONT VIEW Step 1 Attach the horizonta...

Страница 22: ...the closed position stop plate toward the ground stop until they touch Illustration C Once you have moved the stop plate to the correct position tighten its hardware completely NOTE For a push to open...

Страница 23: ...least 3 feet above the ground to protect it from rain splash snow etc and at least 3 feet from an AC power source to prevent electrical interference RED wire to POSITIVE terminal BLACK wire to NEGATIV...

Страница 24: ...if necessary loosen the sealing nut Thread approximately 4 of wire into the control box Retighten strain relief on the black sheath of the power cable until the power cable locks into place Insert the...

Страница 25: ...into which you will plug the transformer Measure the distance from this outlet to the control box following the path where the wire will be laid After you have measured how much wire is needed cut th...

Страница 26: ...of wires A WHT BLU BRN ORG RED BLK GRN WHT BLU BRN ORG RED BLK GRN POWER INPUT LOCK PWR AUX RLY CONTROL OUTPUTS MASTER CABLE SLAVE CABLE GTO 18VOLT TRANSFORMER OR SOLAR GTO LOCK AUX RED BLACK RED BLAC...

Страница 27: ...trol box to discourage insects from entering it and damaging the control board Step 6 Strip 1 2 of insulation from the ends of the low voltage wire Attach these stripped ends to the transformer termin...

Страница 28: ...saves wear and tear on the gate and gate opener system DIP Switch 2 Warning Buzzer ON Buzzer warning enabled factory preset OFF Buzzer warning disabled The Warning Buzzer alerts you when the gate ope...

Страница 29: ...T LIMIT or LEARN SLV LIMIT for 5 seconds or until the buzzer sounds Step 4 Press the transmitter button and allow the gates to return to the fully open position YOUR FIRST GATE S CLOSED POSITION LIMIT...

Страница 30: ...ess and hold the LEARN RMT Learn Remote button on the control board until the buzzer sounds C Release transmitter button The new code is stored in control board memory D Release the LEARN RMT Learn Re...

Страница 31: ...ifications to this equipment Such modifications could void the user s authority to operate the equipment Stall Force Potentiometer ALWAYS KEEP SAFETYAT THE TOP OF YOUR LIST WHEN ADJUSTING OR SERVICING...

Страница 32: ...Connect one of the OPEN EDGE contact sensor wires to the COMMON COM terminal and the other to the OPEN EDGE terminal on the GTO PRO 2002XL control board Connect one of the CLOSE EDGE contact sensor wi...

Страница 33: ...R ALM GTO RCVR BLK COM GRN BLK RED CYCLE SAFETY EXIT SHADOW OPEN EDGE COM CONTROL INPUTS CLOSE EDGE Shadow Loop If not installing a shadow loop skip to next section Wire from Loop Detector RECEIVER AL...

Страница 34: ...RECEIVER ALM GTO RCVR BLK COM GRN BLK RED CYCLE SAFETY EXIT SHADOW OPEN EDGE COM CONTROL INPUTS CLOSE EDGE Free Exit Input The GTO PRO 2002XL can accept NORMALLY OPEN DRY CONTACT free exit entry devi...

Страница 35: ...do not use the lock board with this control board GTO Lock Connection Connect the red and black leads from the lock to the GTO LOCK terminal on the GTO PRO 2002XL control board Connecting GTO Automati...

Страница 36: ...gates are in the closed position 3 8 x 2 Bolt 3 8 Nut Push To Open Bracket optional accessory Post Bracket Post Bracket 3 8 Lock Washer Post Bracket Assembly 3 8 Washer Step 2 After verifying that you...

Страница 37: ...n Limit Step 1 Confirm that the power switch is in the ON position and the gates are in the CLOSED POSITIONS Step 2 Activate your openers by pressing the entry transmitter button Your gates should now...

Страница 38: ...een achieved proceed to step 6 Step 6 Repeat step 3 for the other gate that has not been set in step 3 Step 7 Press the transmitter button and allow the gates to return to the closed position BOTH YOU...

Страница 39: ...shorted to common ground 3 SAFETY Input Activated indicators Alarm None STATUS Led 2 blinks with 2 second pause Idle state only SAFETY input is continuously shorted to common ground 4 EXIT Input Activ...

Страница 40: ...IVER Led blinking or OFF When the RECEIVER led is blinking the controller is receiving GTO scheme 318 MHz signal from the receiver This indicates that the transmitter and receiver are working properly...

Страница 41: ...ent Sensing Obstruction error indicators Error Code 5 Alarm 5 beeps with 2 second pause STATUS Led 5 blinks with 2 second pause Current sensing circuit for detecting obstruction is not working properl...

Страница 42: ...ooting Guide see page 35 2 If you are unable to solve the problem call the GTO PRO Service Department at 800 543 1236 or 850 575 4144 Refer to the serial number located on the right hand side of the c...

Страница 43: ...included Digital Keypad F310 The specially designed digital keypad can be easily installed as a wireless or wired keypad It can be programmed to use up to 25 different personal identification number...

Страница 44: ...or the GTO PRO 2500 GTO PRO 2002XL GTO PRO 3000 GTO PRO 4000 gate operator systems This is the only battery approved for use with the GTO PRO gate operator systems Life expectancy is 3 5 years Low Vol...

Отзывы: