GTO LOOPDT1 Скачать руководство пользователя страница 2

1)  DIP SWITCH SETTING:

a)  DIP 1: PRESENSE TIMER

OFF (Factory default): The loop will automatically re-tune if an object is present for more than 1 
hour.
ON: Automatic retune as described above is disabled.

b)  DIP 2: SAFE/SECURE

OFF: Fail-safe mode. When the controller detects a fault (shorted or open loop) the output relay 
is activated. Typically, the normally open output relay is connected to the ‘FREE EXIT’ input on 
the gate’s controller that would hold the gate open.
ON: Fail-secure mode. When the controller detects a fault (shorted or open loop) the output 
relay is NOT activated.

c)  DIP 3: ENTER/LEAVE

OFF: The output relay is activated when a vehicle enters the loop.
ON: The output relay is activated when a vehicle is leaves the loop.

d)  DIP 4: CONTINUOUS/PULSE

OFF: Continuously activates the output relay when a vehicle is detected. 
ON: Momentarily activate the output relay when a vehicle is detected.

e)  DIP 5: INSTANT/DELAY

OFF: Instantly activate the output relay when a vehicle is detected. 
ON: Delay for 2 seconds before activating the output relay when a vehicle is detected. If the 
vehicle is moved in less than 2 seconds relay will not be activated.

f)  DIP 6,7,8: SENSITIVITY 

g)  DIP 9,10: FREQUENCY SELECT 

These two switches provide four selectable loop frequencies. This allows multiple loops of the same 
design to co-exist in close proximity without interference with each other. The actual frequency is 
dependent on the loop inductance.

DIP 6 

DIP 7 

DIP 8 

Inductance 

Vehicle

 

 

 

change 

size

OFF 

OFF 

OFF 

2% 

Larger

OFF 

OFF 

ON 

1% 

OFF 

ON 

OFF 

.5% 

OFF 

ON 

ON 

.25% 

ON 

OFF 

OFF 

.125% 

ON 

OFF 

ON 

.06% 

ON 

ON 

OFF 

.04% 

ON 

ON 

ON 

.02% 

Smaller

GTO/PRO Loop Detector Settings and Layout

Содержание LOOPDT1

Страница 1: ...GTO Inc 3121 Harts eld Road Tallahassee Florida 32303 1 800 543 GATE 4283 www gtoinc com Technical Support 800 543 1236 RWLOPPRO rev 4 5 06 Digital Loop Detector...

Страница 2: ...loop d DIP 4 CONTINUOUS PULSE OFF Continuously activates the output relay when a vehicle is detected ON Momentarily activate the output relay when a vehicle is detected e DIP 5 INSTANT DELAY OFF Insta...

Страница 3: ...1 4 8 26 Vac Vdc positive input ii TB1 5 8 26 Vac Vdc negative input Relay output Normally Open Relay output Common Relay output Normally Close Power supply input 8 26 Vac dc Loop wire use for loop sh...

Страница 4: ...for loop installation 1 Make sure the pavement surface in the area that the loops are to be installed is dry and free of debris 2 Design the loop geometry considering the area of detection the type o...

Страница 5: ...continue around the loop for the number of turns required and nally return to the lead in termination Leave the lead in wire out of the slot so that it may be twisted together before being laid in th...

Страница 6: ...the SHADOW LOOP terminal Connect one of the relay output wires from the detector to the COMMON COM terminal and the other to the SHADOW LOOP terminal Wires from relay output on detector RECEIVER COM C...

Страница 7: ...O SL2000 Connect one of the relay output wires from the detector to the GREEN GRN terminal and the other to the BLUE BLU terminal ON ALARM ACCESSORY RCVR SEQ1 SEQ2 LEARN BLU ORG WHT GRN R B G Wires fr...

Страница 8: ...aired or replaced at the manufacturer s option at no charge to the customer if returned freight prepaid to GTO Inc 3121 Harts eld Road Tallahassee Florida USA 32303 IMPORTANT Call 850 575 4144 or Fax...

Отзывы: