background image

13

HOTSPOT-X0 Interface-X1

410-2410-011 EN12

COMMISSIONING

6.2 

Wiring of the fire detection system

Depending on the system configuration connect the fire detection system to terminals 1 ... 20 

of the system connection terminal 

(–› Chap. 4.2.3)

.

Also consult 

GTE-manual No. 430-2410-001 

(ADICOS AAB Operating manual)

 and 

GTE-manual No. 430-2410-004 

(ADICOS AAB-L Operating manual)

.

7  Commissioning

DANGER!

ADICOS systems work with electricity that may lead to system damage 

and fire in the case of improper installation. 

 

Prior to switching on, check that all detectors are properly

mounted and wired! 

 

Commissioning may only be performed by qualified 

specialist personnel!

DANGER!

The ADICOS HOTSPOT-X0 Interface-X1is subject to the protection principle 

and/or the ignition protection type 

equipment protection by flameproof 

enclosures „d“

.

 

Firmly close enclosure lid before commissioning!

NOTE!

The ADICOS HOTSPOT-X0 Interface-X1 is a passive component. A separate 

commissioning is not required.

 

Initialize the ADICOS fire detection system according to the 

operating manual of the installed central unit (ADICOS BMZ-30 / 

M-Busmaster)!

Содержание ADICOS HOTSPOT-X0 Interface-X1

Страница 1: ...EN GTE Industrieelektronik GmbH Helmholtzstr 21 38 40 41747 Viersen Germany 49 2162 3703 0 info gte de HOTSPOT X0 Interface X1 Operating manual IR Temperatur Detector ...

Страница 2: ...Helmholtzstr 21 38 40 41747 Viersen GERMANY Support hotline 49 2162 3703 0 E Mail support adicos gte de 2021 GTE Industrieelektronik GmbH This document and all figures contained may not be copied changed or distributed without explicit approval by the manufacturer Subject to technical changes ADICOS and GSME are registered trademarks of GTE Industrieelektronik GmbH ...

Страница 3: ... goal without being suspectable to interference The detector units are connected using the ADICOS M Bus to a central unit which enables voltage supply and parameterization of every individual detector and which stores all sensor data for statistical analyses The ADICOS HOTSPOT X0 Interface X1 is an interface between the ADICOS HOTSPOT X0 Sensor Unit and the fire control panel within potentially ex...

Страница 4: ...ons 5 2 3 Personnel qualification 6 2 4 Handling electrical voltage 6 2 5 Modification 6 2 6 Accessories and spare parts 6 3 Accessories 7 4 Structure 8 4 1 Overview 8 4 2 Connection terminals 9 5 Installation 11 5 1 Selecting the mounting location 11 5 2 Wall mounting 11 6 Wiring 12 6 1 Wiring of ADICOS HOTSPOT X0 Sensor Unit 12 6 2 Wiring of the fire detection system 13 7 Commissioning 13 8 Main...

Страница 5: ... result to be achieved by the subsequent instructions Action objectives are presented in bold font Action instructions Action instructions describe the activities to be performed in order to achieve the action objec tive previously mentioned Action instructions are presented as follows Individual action instruction 1 First of several sequential action instructions 2 Second of several sequential ac...

Страница 6: ...ectly leads to fatal or severe injuries DANGER This information type signals measures that must be implemented for maintaining the explosion protection 1 3 Abbreviations This manual uses the following abbreviations Abbr Meaning ADICOS Advanced Discovery System X0 Ex zone 0 X1 Ex zone 1 1 4 Storing the manual Store this manual easily reachable and in direct vicinity of the detector to enable use as...

Страница 7: ...S systems In this context the operating parameters described in Chap 8 Maintenance must be met Any deviating use requires prior consultation with the manufacturer Compliance with this manual as well as all applicable country specific provisions is also part of the intended use 2 2 Standards and regulations The safety and accident prevention regulations applicable for the specific application must ...

Страница 8: ...ng parameterization and maintenance may only be performed by authorized and respectively trained personnel 2 4 Handling electrical voltage DANGER The electronics of the ADICOS HOTSPOT X0 Interface X1 works with a voltage that can trigger an explosion in potentially explosive atmospheres De energize the entire detector system and secure against unintentional reactivation for all wiring work 2 5 Mod...

Страница 9: ...ories are available for the ADICOS HOTSPOT X0 Interface X1 Art no Description 410 2401 310 HOTSPOT X0 Sensor Unit 83 09 06052 Cable gland for non reinforced and non sealed cables 83 09 06053 Cable gland for reinforced and non sealed cables 83 09 06050 Cable gland for non reinforced and sealed cables 83 09 06051 Cable gland for reinforced and sealed cables ...

Страница 10: ...ture 4 1 Overview No Description Flameproof enclosure Top hat rail with Ex barriers connection terminals and interface circuit board Thread for enclosure lid Enclosure lid Mounting place for additional cable glands Cable gland 2x Mounting bracket 4x 1 2 3 4 6 5 7 ...

Страница 11: ...ically safe circuit 1 Ex barrier 2 sensor power supply intrinsically safe circuit 2 System connection 4 2 1 Sensor communication intrinsically safe circuit 1 No Occupation 9 Cabinet shielding 10 Shield for intrinsically safe cable 11 12 13 Sensor communication B 14 Sensor communication A 15 16 4 2 2 Sensor power supply intrinsically safe circuit 2 No Occupation 1 Sensor power supply 2 Sensor power...

Страница 12: ...N12 4 2 3 System connection terminal No Occupation 1 0 V 2 0 V 3 M Bus A 4 M Bus A 5 Alarm A 6 Fault A 7 LOOP A in 8 LOOP A out 9 Shield 10 Shield 11 24 V 12 24 V 13 M Bus B 14 M Bus B 15 Alarm B 16 Fault B 17 LOOP B in 18 LOOP B out 19 Shield 20 Shield ...

Страница 13: ...pects have to be considered when choosing the mounting location Install device easily accessible and in direct vicinity to the connected sensor but outside of Ex zone 0 The mounting location must satisfy all environmental requirements specified in Chap 10 Specifications The mounting spot must be solid and free of vibrations 5 2 Wall mounting WARNING Improper installation of the ADICOS AABs can lea...

Страница 14: ... must be routed according to DIN EN 60079 14 Only use approved intrinsically safe connection cables provided by GTE Observe minimum bending radius 1 Remove enclosure lid by rotating counter clockwise 2 Open cable gland 3 Insert sensor connection cable through cable gland 4 Connect green wire communication A to terminal 14 of Ex barrier 1 intrinsically safe circuit 1 5 Connect yellow wire communica...

Страница 15: ...amage and fire in the case of improper installation Prior to switching on check that all detectors are properly mounted and wired Commissioning may only be performed by qualified specialist personnel DANGER The ADICOS HOTSPOT X0 Interface X1is subject to the protection principle and or the ignition protection type equipment protection by flameproof enclosures d Firmly close enclosure lid before co...

Страница 16: ...2410 011 EN12 8 Maintenance The ADICOS HOTSPOT X0 Interface X1 does not require maintenance 9 Disposal Return device to the manufacturer after the end of the useful life The manufacturer ensures environmental friendly dispos al of all components ...

Страница 17: ...ion regarding explosion protection Explosion protection class II 2 1 G Ex db ia Ga IIC T4 Gb Temperature class T4 Device group II category 2G Type approval Certificate per 2014 34 EU IECEx certificate IECEx KIWA 17 0007X ATEX certificate KIWA 17ATEX0018 X Electrical properties Uo 1 2 V 17 Io 1 2 mA 271 Po 1 2 W 1 152 Uo 13 14 V 3 7 Io 13 14 mA 225 Po 13 14 mW 206 Ui 13 14 V 30 Ii 13 14 mA 282 CO 1...

Страница 18: ......

Отзывы: