Chapter 6 Specification of Parameters
GK600 User Manual
- 208 -
F0-23
Cutoff FREQ when opposite to
rotary set direction
Range: 0.00Hz~maximum
frequency
Factory default:
50.00Hz
When rotary set direction is forward, while PID output is reverse, the maximum reverse
frequency will be determined by F0-23. When rotary set direction is reverse, while PID output is
forward, the maximum forward frequency will be determined by F0-23.
F0-24 PID computation option
Range: 0~1
Factory default: 0
0: No computation in stop status
1: Computation continued in stop status
Group F1 Multi-step Frequency
F1-00
FREQ set source of
multi-step 0
Range: 0~8
Factory default: 0
0: Digital setting F1-02
1: Digital setting b0-02 + control panel
∧
/
∨
adjustment
2: Digital setting b0-02 + terminal UP/DOWN adjustment
3:AI1
4:AI2
5: EAI (on IO option board)
6: X6/DI pulse input
7: Process PID output
8: Communication
At most 16-step of frequency can be set through the combination of "multi-step frequency
terminals 1~4" of digital input. Multi-step frequency 2~15 are only digital setting while a number
of setting sources can be selected for multi-step frequency 0~1. Parameter value of F1-00
determines command source of step 0.
F1-01
FREQ set source of
multi-step 1
Range: 0~8
Factory default: 0
0: Digital setting F1-03
1: Digital setting b0-04 + control panel
∧
/
∨
adjustment
2: Digital setting b0-04 + terminal UP/DOWN adjustment
3:AI1
4:AI2
5: EAI (on IO option)
6: X6/DI pulse input
7: Process PID output
8: Communication