background image

1. 

TURN OFF POWER AT THE BREAKER OR FUSE PANEL. 

 

TURNING OFF POWER AT THE WALL SWITCH IS NOT SUFFICIENT SAFETY PRECAUTION 

2. 

Double check the rating of the lamp (120-277VAC) matches the voltage of the current circuit

3. 

Check to see if the fixture has shunted, or non-shunted lampholders

4. 

Take out old bulbs and remove the ballast cover

5. 

Disconnect all wires attached to the ballast as close to the ballast as possible. It is best 

 

practice to leave the ballasts in place after doing this. 

6. 

For Non-Shunted Lampholders:

                  - Connect one wire from each lampholder at only one end of the fixture to the back wire. 
 

       Separately connect the neutral wire (white) to the lampholder after. 

 

• 

At the opposite end of the fixture cut all wires that connect to that lampholder.

 

• 

ENSURE THIS FIXTURE REMAINS GROUNDED AFTER THE RETROFIT PROCESS.

7. 

For Shunted Lampholders:

 

    - Connect one black wire to one lamp holder on one side of the light. Connect the neutral 

 

    (white) wire to a lamp holder on the opposite side of light. Do this for each bulb in light fixture. 

8. 

Replace any removed wiring covers or ballast covers. 

9. 

Install GT-2PK-T8-SLH bulbs into the new fixture

Assembly & Installation: GT-2PK-T8-SLH  |  T8 LED Bulb (2pk) Ballast Bypass

WARNING:

TO AVOID RISK OF ELECTRICAL SHOCK,

SHUT OFF POWER BEFORE

INSTALLING OR SERVICING THIS FIXTURE

Complete LED Lighting Solutions

Question/Comment/Missing Part?

Contact GT-Lite 1-800-865-6799

www.GTLEDLIGHTING.com

BALLAST BYPASS RETROFIT INSTRUCTIONS:

DIAGRAM 2

Содержание GT-2PK-T8-SLH

Страница 1: ...e bulbs if you are not properly qualified Risk of Electric Shock or Fire Risk of Electric Shock or is present when working with electrical components Do not drill holes in the fixture that could affect the internal wiring Prevent Electric Wire Abrasions Do not expose wiring to edges of the fixture or other sharp objects This can cause abrasion and damage the wiring greatly increasing risk of elect...

Страница 2: ...interference to radio equipment and should not be installed near maritime safety commmunications equipment or other critical navigation or communication equipment operating between 0 45 30MHZ CAUTION 1 TURN OFF POWER ATTHE BREAKER OR FUSE PANEL TURNING OFF POWER ATTHE WALL SWITCH IS NOT A SUFFICIENT SAFETY PRECAUTION 2 Double check the rating of the lamp 120 277VAC matches the voltage of the curre...

Страница 3: ...l wire white to the lampholder after At the opposite end of the fixture cut all wires that connect to that lampholder ENSURE THIS FIXTURE REMAINS GROUNDED AFTER THE RETROFIT PROCESS 7 For Shunted Lampholders Connect one black wire to one lamp holder on one side of the light Connect the neutral white wire to a lamp holder on the opposite side of light Do this for each bulb in light fixture 8 Replac...

Страница 4: ...t the form at http gtledlighting com contact us Owner must provide proof of purchase and return lamp to GT Lite to be considered for replacement or refund of original purchase price REPLACEMENT OR REFUND IS YOUR SOLE REMEDY EXCEPT TO THE EXTENT PROHIBITED BY APPLICABLE LAW ANY IMPLIED WARRANTIES ARE LIMITED IN DURATION TO THE DURATION OF THIS WARRANTY LIABILITY FOR INCIDENTAL OR CONSEQUENTIAL DAMA...

Отзывы: