I-9106
Intelligent Linear Cable Heat Detector
Installation and Operation Manual
The Intelligent Solution
Page 2
2
Linear Heat Cable
(1) Response
time
≤
20s
(
heat within 1m
)
(2) Operating Environment Temperature: T:
-
40
℃≤
T
≤
Rated action temperature
falling down 30
%
(3) Insulated
resistance
≥
500M
Ω
(4) Maximum curve radius: 150mm
(5) Anti-voltage ability: 500VAC, for 1 minutes
(6) Relative error: Action temperature error
±
10
%
IV
Structure and Operation Principle
1 Dimension
a) Fig. 1 shows the interface with 172mm
×
246mm
×
77mm.
I-9106
Intelligent LinearCable Heat
DetectorInterface
Loop1
Loop2
Fig. 1 Dimension of the interface
b) Fig. 2 shows the terminal with 105mm
×
109mm
×
54mm.