30307848
Issue 1.01
Specification
Operating
Voltage
loop 24V (16V~28V)
Standby
Current
≤
0.8mA
Alarm Current
≤5.0
mA
Indicator
Red. Flashes in normal, and
illuminates in alarm
Remote
Indicator
Output
Directly connecting with indicator
(built-in 5.1
kΩ resistor, maximum
output current is 5.0mA). Quiet in
normal
condition.
Illuminates
steadily in alarm.
Alarm
Temperature
58
℃
Class
A2R
Rate
of
Response
3
℃
/min
Programming
Method
Electronically programming
Code Range
one address within 1
~
242.
Wiring
Non-polarized 2-core for loop.
Polarized 2-core for remote
indicator.
Ingress
Protection
Rating
IP22
Environment
Temperature
-
10
℃~+
50
℃
Relative
Humidity
≤
95%, non condensing
Material
of
Enclosure
ABS
Dimensions
Diameter: 100mm
Height: 56mm(base)
Mounting Hole
Distance
45mm
~
75mm
Weight
About 120g
Maintenance
The detector should be installed just before
commission and kept well before installation.
Corresponding measures should be taken for
dust-proof, damp-proof and corrosion-proof.
Dust covers are an effective way to limit the entry
of dust into smoke detector sensing chambers.
Therefore, the dust cover should not be removed
until the building starts to be used.
Clean the detector at least once 1 year to ensure
normal operation of the system.
If unwanted alarms are often found of the detector
on site, the sensing chamber should be cleaned.
Power must be removed from the detector before
cleaning.
Before cleaning the detector, notify the proper
authorities that the system is undergoing
maintenance and will be temporarily out of service.
Disable
the
zone
or
system
undergoing
maintenance to avoid any unwanted alarms.
The detector should be tested again after cleaning
and re-installing. Notify the proper authorities
when the system is back in service.
Fire simulation test should be done to the detector
at least once 6 months.
Accessories and Tools
Model
Name
Remark
P-9910B
Hand held
programmer
Order separately
DZ-03
Base
Order separately
Limited Warranty
GST
warrants that the product will be free of charge
for repairing or replacing from defects in design,
materials and workmanship during the warranty period.
This warranty doesn
’t cover any product that is found
to have been improperly installed or used in any way
not in accordance with the instructions supplied with
the
product.
Anybody,
including
the
agents,
distributors or employees, is not in the position to
amend the contents of this warranty. Please contact
your local distributor for products not covered by this
warranty.
GST TURKEY
Turkish Distributor:- Alfa Elektronik
Yapi Donanimlari LTD STI, Gersan
Sanayi Sitesi 2308, Sokak No. 87,
06770 Ergazi, Ankara-Turkey
www.alfamax.com.tr
GST CHINA
Global System Technology PLC
No. 80, Changjiang East Road,
QETDZ, Qinhuangdao, Hebei,
P. R. China 066004
Tel: +86 (0) 335 8502528
GST UK
Global System Technology PLC
Lion Court, Melbourne Road,
Leicestershire, LE651RT,
United Kingdom
Tel: +44 1283 225 478
Fax: +44 1283 220 690
[email protected]
www.gst.uk.com
This document is subject to change without notice. Please contact GST for more information or questions.