background image

 

30307848 

                               

                                                                                                  Issue 1.01

 

Specification 

Operating 

Voltage 

loop 24V (16V~28V) 

Standby 

Current 

0.8mA 

Alarm Current 

≤5.0

mA 

Indicator 

Red.  Flashes  in  normal,  and 

illuminates in alarm 

Remote 

Indicator 

Output 

Directly connecting with indicator 

(built-in 5.1

kΩ resistor, maximum 

output current is 5.0mA). Quiet in 

normal 

condition. 

Illuminates 

steadily in alarm. 

Alarm 

Temperature   

58

 

Class 

A2R 

Rate 

of 

Response 

3

/min 

Programming 

Method 

Electronically programming 

Code Range 

one address within 1

242. 

Wiring 

Non-polarized 2-core for loop. 

Polarized  2-core  for  remote 

indicator. 

Ingress 

Protection 

Rating 

IP22 

Environment 

Temperature 

-

10

℃~+

50

 

Relative 

Humidity 

95%, non condensing 

Material 

of 

Enclosure 

ABS 

Dimensions 

Diameter: 100mm   

Height: 56mm(base) 

Mounting  Hole 

Distance 

45mm

75mm 

Weight 

About 120g 

 

 

 

 

 

 

 

 

 

 

Maintenance   

 

The  detector  should  be  installed  just  before           
commission  and  kept  well  before  installation. 
Corresponding  measures  should  be  taken  for 
dust-proof, damp-proof and corrosion-proof. 

    Dust covers are an effective way to limit the entry 

of  dust  into  smoke  detector  sensing  chambers. 
Therefore, the dust cover should not be  removed 
until the building starts to be used. 

 

Clean the detector at least once 1 year to ensure     
normal operation of the system. 

 

If unwanted alarms are often found of the detector 
on  site,  the  sensing  chamber  should  be  cleaned. 
Power must be removed from the detector before 
cleaning. 

 

Before  cleaning  the  detector,  notify  the  proper 
authorities  that  the  system  is  undergoing 
maintenance and will be temporarily out of service. 
Disable 

the 

zone 

or 

system 

undergoing 

maintenance to avoid any unwanted alarms. 

 

The detector should be tested again after cleaning 
and  re-installing.  Notify  the  proper  authorities 
when the system is back in service. 

 

Fire simulation test should be done to the detector 
at least once 6 months. 

Accessories and Tools 

Model 

Name 

Remark 

P-9910B 

Hand  held 
programmer 

Order separately 

DZ-03 

Base 

Order separately 

Limited Warranty 

GST

  warrants  that  the  product  will  be  free  of  charge 

for  repairing  or  replacing  from  defects  in  design, 
materials and workmanship during the warranty period. 
This warranty doesn

’t cover any product that is found 

to have been improperly installed or used in any way 
not  in  accordance  with  the  instructions  supplied  with 
the 

product. 

Anybody, 

including 

the 

agents, 

distributors  or  employees,  is  not  in  the  position  to 
amend  the  contents  of  this  warranty.  Please  contact 
your  local  distributor  for  products  not  covered  by  this 
warranty. 

 

 

 

 

 

 
 

GST TURKEY 

Turkish Distributor:- Alfa Elektronik 

Yapi Donanimlari LTD STI, Gersan 

Sanayi Sitesi 2308, Sokak No. 87, 

06770 Ergazi, Ankara-Turkey 

www.alfamax.com.tr 

GST CHINA 

Global System Technology PLC 

No. 80, Changjiang East Road, 

QETDZ, Qinhuangdao, Hebei, 

P. R. China 066004 

Tel: +86 (0) 335 8502528 
 

GST UK 
Global System Technology PLC 

Lion Court, Melbourne Road, 
Leicestershire, LE651RT,   
United Kingdom 
Tel: +44 1283 225 478 
Fax: +44 1283 220 690 
[email protected]   
www.gst.uk.com 
 
 
 

This document is subject to change without notice. Please contact GST for more information or questions. 