GST303 /GST306
Extinguishing Control Panel
Installation and Operation Manual
Page 1
1 General
GST303/GST306 Extinguishing Control Panel (hereinafter called the control panel) is
designed for driving the executing units of a fixed extinguishing system.
Except for 3 extinguishing zones less, and some minor differences in appearance and
structure, GST303 is the same as GST306 in operation. We
’ll take GST306 as an
example.
2 Features
The control panel can be directly connected to the loop of GST intelligent fire alarm
control panels (FACP) that are able to control associated fire suppression equipment to
achieve automatic control of gas release.
It can also control gas release devices independent of the FACP. When the FACP is
not working properly, it can still control extinguishing devices through emergency gas
override control in field or
Start
and
Stop
keys on the control panel.
This control panel is also able to monitor and alarm on short circuit or open circuit with
externals cables
3 Technical Specifications
1) Capacity:
GST303: Controlling maximum 3 extinguishing zones (3 control units)
GST306: Controlling maximum 6 extinguishing zones (6 control units)
2) Delay Time: 0s
~
45s, adjustable by every 5s
3) Wiring:
a 2-core connection with FACP.
b Two-wire connection with the solenoid of cylinder, pressure switch
and gas extinguishing warning indicator.
c Three-wire connection with emergency gas override control.
d Two-wire connection with sounder strobe.
4) Power supply: Powered by external 20VDC~28VDC from intelligent PSU.
Total length from PSU to the control panel and from the control panel to
solenoid should not be over 100m, cross section not less than 2.5mm
2
.
5) Solenoid Interface:
Start output: By pulse or electric level mode. 5s for pulse mode; Voltage range:
18VDC
~
26VDC; Maximum current: 2A
6) Gas Extinguishing Warning Indicator Interface:
Start output: Voltage range: 18VDC
~
26VDC; Maximum current: 300mA
Load: Maximum 5 for each zone.
7) C-9316 Gas Stop Indicator Interface:
Start Output: Voltage: 18VDC~26VDC; Maximum Current: 100mA
Load: Maximum 3 for each zone.
8) Sounder Strobe Interface: