GST303 /GST306
Extinguishing Control Panel
Installation and Operation Manual
Page 16
dump” fault.
h) Disconnect any cable between control panel and protection door, the FACP
reports
“Gas dump” fault.
5.8 Installation of Protective Cover
After mounting and commission, install the protective cover for start key and stop key.
Refer to Appendix 2 for installation method.
6 Operation
6.1 Powering-up, Self-test and Switching off
(1) Check the settings of the control panel according to Section 5.
(2) Power up the unit as follows:
Turn on the primary and standby power.
Turn on the power of the control panel. After the above operation, the control
panel starts self-test on sound and LEDs. After self-test, it enters standby
state.
Turn on primary/standby power switch and
Run
switch of the FACP. It will
register the address of the control panel. The quantity of address points
occupied by gas extinguishing devices = the greatest zone number x 4 +1.
Turn off the switches in reverse procedure of turning on.
6.2 Basic Operation
6.2.1 Start
Important: Because extinguishing device will finish gas extinguishing
instantaneously on receiving valid start command, so improper operation will
result in great losses beyond remedy, even loss of life; On the other hand, it will
affect fire protective ability of some important places in a certain period. Be very
careful when starting these devices!
Besides conditions of starting ordinary devices, starting extinguishing devices should
also meet the following conditions:
①
The personnel to start extinguishing devices must be well trained of the relative
knowledge.
②
Confirming the fire condition that extinguishing devices has to be started.
③
Confirming that people in the protected zone have been evacuated.
After extinguishing devices have been started, field pressure switch will feed back
answer signal of device action, and gas extinguishing warning indicator is lit. The
control panel reports action of extinguishing devices to the FACP.
There are two modes of starting extinguishing devices: immediate start and delay start.
a) Immediate Start
When personnel on duty have confirmed fire and people have been evacuated,
extinguishing devices can be started immediately. The command can be given from the
control panel or from the FACP.