GST-FT8WN
Fire Telephone Panel
The Intelligent Solution
Page 7
5.5
System Commissioning
Please Make Sure the Correct Wiring before Commissioning.
Set panel address
For standalone fire telephone system, the address can be assigned 1 or keep the
default setting
There must be one panel assigned 1 in the network fire telephone system
Opening the door of the panel, the red PIN switch in the left corner is using for panel
address setting. The addresses’ range is from 1 to 8. Please refer to Fig. 5-3.
Fig. 5-3
Note: The panel addresses can not be repeated in same network.
Register the Network Panels
After assigning the addresses, power on the sub-panels first.
Press and hold the “Network Call” button on the main panel and power on. The main panel
will register all networked sub-panels automatically. Subsequently, the first digit of the
digitron will show the number of networked panels (including the main panel). Check
whether all panels have been registered according to the shown number. If no consistency,
check the wiring and repeat the above-mentioned process.
The registration information is saved in non-volatile memory, will not loss on power off. The
registration should be carried out again in case adding or removing network panels.
Not necessary for registration on sub-panel.
Test Functions
Test the other functions according to Operation Manual after commissioning.