GST-FT40N 
Fire Telephone Panel     

                                                                                               

The Intelligent Solution

 

Page 7

 

5.5 System 

Commissioning 

 

Please Make Sure the Correct Wiring before Commissioning. 

Set panel address 

¾

  For standalone fire telephone system, the address can be assigned 1 or keep the 

default setting. 

¾

  There must be one panel assigned 1 in the network fire telephone system and register 

other panels. 

¾

 Addressing 

step

  Press a key between 1-8 key of front surface, then power on, press 

the key over 2s, the number will become the network address of the panel. The 
address will not be lost when the panel is switched off. The address will not be changed 
unless 1-8 key is pressed when the panel is powered on.       

   

Note: The panel addresses can not be repeated in same network. 

Register the Network Panels 

After assigning the addresses, power on the sub-panels first. Then power on the main panel. 
The main panel will register all networked sub-panels automatically. Subsequently, the first 
digit of the digitron will show the number of networked panels (including the main panel). 
Check whether all panels have been registered according to the shown number. If no 
consistency, check the wiring and repeat the above-mentioned process. 
 
The registration information is saved in non-volatile memory, will not loss on power off. The 
registration should be carried out again in case adding or removing network panels. 
Not necessary for registration on sub-panel. 

Test Functions 

Test the other functions according to Operation Manual after commissioning.   

6 User Guide 

6.1 

Panel Call Handset 

Press a key of zone 1 to 40, the corresponded zone will be called with “Call” LED 
slow-flashing. The conversation will be set when handset picked-up, with “Call” LED lit 
showing status. During the conversation, press the key again will stop the call. The “call” 
LED won’t go out until hanging up the handset. If the handset is hung up first, the 
conversation will stop immediately with “Call” goes out. 
 

Содержание GST-FT40N

Страница 1: ...GST FT40N Fire Telephone Panel Installation and Operation Manual ...

Страница 2: ...FIRE TELEPHONE SYSTEM 4 4 2 NETWORKED FIRE TELEPHONE SYSTEM 4 5 MOUNTING COMMISSION 5 5 1 INITIAL CHECK 5 5 2 WIRING REQUIREMENT 5 5 3 INSTALLING DIMENSION 5 5 4 TERMINALS ON THE PANEL 6 5 5 SYSTEM COMMISSIONING 7 Set panel address 7 Register the Network Panels 7 Test Functions 7 6 USER GUIDE 7 6 1 PANEL CALL HANDSET 7 6 2 HANDSET CALL PANEL 8 6 3 CALL PANELS IN NETWORK 8 6 4 PANEL TO PANEL CALL 8...

Страница 3: ...one zone will not effect on other zones The network communication is monitored When sub panel fails to communicate with the main panel the main panel will get the failure message and broadcast to other networked sub panels both main panel and sub panels will indicate by sound and light indication When the fault happens on main panel all sub panels will show the fault message and meanwhile the netw...

Страница 4: ... Handset Field device which can communicate with fire control center such as P 9911 F and P 9911 M Main panel The No 1 panel in the fire telephone panel network Sub panel Panels other than No 1 in the fire telephone panel network 3 Panel Instruction 3 1 Appearance and Structure GST FT40N fire telephone panel is rack mount type the appearance is shown in Fig 3 1 GST FT40N FIRE TELEPHONE PANEL Fig 3...

Страница 5: ...iption Call LED 1 40 Red indicating the conversation status between panel and corresponding zone Flashing in the process of connection On under conversation Off no conversation Ring In LED Red fast flash when there is call in from network or zone Fault LED 1 40 Yellow lit on when corresponding zone in Fault condition Network Fault LED Yellow lit on when there is network fault Power LED Green lit b...

Страница 6: ...nversation The sample at the left shows the conversation state between No 1 panel and No 2 panel The others will show BUSY Network Failure The first digit indicates the address of failed panel The E means Error 4 Fire Telephone System Design 4 1 Stand Alone Fire Telephone System Fig 4 1 shows a standalone fire telephone system The panel can connect maximum 40 zones with each zone maximum 5 handset...

Страница 7: ... state 5 2 Wiring Requirement Cross section area of the power cable not less than 1 5mm2 Twisted pair cable connecting panel and handset with SA not less than 1 0 mm2 Twisted pair cable for the network with SA not less than 1 0 mm2 The cable selection must comply with local code Note the impedance of single line not more than 20Ω 5 3 Installing dimension Installing dimension 482 5mm 177mm 225mm ...

Страница 8: ... Page 6 5 4 Terminals on the panel Fig 5 1 Power 24 GND 24VDC power in polarized E GND Network Network polarized Audio Output Audio signal output Zn Zn Zone Terminals connecting with handsets a 10KΩ 0 5KΩ resistor is required to the last point of each zone ...

Страница 9: ...el will register all networked sub panels automatically Subsequently the first digit of the digitron will show the number of networked panels including the main panel Check whether all panels have been registered according to the shown number If no consistency check the wiring and repeat the above mentioned process The registration information is saved in non volatile memory will not loss on power...

Страница 10: ...available press Network Call will send the call to entire network with the LED indicator fast flashing Meanwhile the digitron on other networked panels will show by flashing X C X The calling panel the Ring In and Network Call LED will fast flash with ringing sound Press Network Call button and then start the conversation The digitron of the panels not attending conversation will show BUSY and the...

Страница 11: ...0N Fire Telephone Panel The Intelligent Solution Page 9 7 2 Network Fault The panel shows network fault when there is any of the panels powered off or network cable fault Check the malfunction panel and wiring ...

Страница 12: ...com cn GST UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk com www gst uk com GST Dubai Global System Technology PLC PO Box 17998 Unit ZA04 JEBEL ALI Free Zone Dubai UAE Tel 971 0 4 8833050 Fax 971 0 4 8833053 Email info gst uk com www gst uk com ...

Отзывы: