GST-FT40N Fire Telephone Panel   

  Installation and Operation Manual 

 

 

 

Содержание GST-FT40N

Страница 1: ...GST FT40N Fire Telephone Panel Installation and Operation Manual ...

Страница 2: ...FIRE TELEPHONE SYSTEM 4 4 2 NETWORKED FIRE TELEPHONE SYSTEM 4 5 MOUNTING COMMISSION 5 5 1 INITIAL CHECK 5 5 2 WIRING REQUIREMENT 5 5 3 INSTALLING DIMENSION 5 5 4 TERMINALS ON THE PANEL 6 5 5 SYSTEM COMMISSIONING 7 Set panel address 7 Register the Network Panels 7 Test Functions 7 6 USER GUIDE 7 6 1 PANEL CALL HANDSET 7 6 2 HANDSET CALL PANEL 8 6 3 CALL PANELS IN NETWORK 8 6 4 PANEL TO PANEL CALL 8...

Страница 3: ...one zone will not effect on other zones The network communication is monitored When sub panel fails to communicate with the main panel the main panel will get the failure message and broadcast to other networked sub panels both main panel and sub panels will indicate by sound and light indication When the fault happens on main panel all sub panels will show the fault message and meanwhile the netw...

Страница 4: ... Handset Field device which can communicate with fire control center such as P 9911 F and P 9911 M Main panel The No 1 panel in the fire telephone panel network Sub panel Panels other than No 1 in the fire telephone panel network 3 Panel Instruction 3 1 Appearance and Structure GST FT40N fire telephone panel is rack mount type the appearance is shown in Fig 3 1 GST FT40N FIRE TELEPHONE PANEL Fig 3...

Страница 5: ...iption Call LED 1 40 Red indicating the conversation status between panel and corresponding zone Flashing in the process of connection On under conversation Off no conversation Ring In LED Red fast flash when there is call in from network or zone Fault LED 1 40 Yellow lit on when corresponding zone in Fault condition Network Fault LED Yellow lit on when there is network fault Power LED Green lit b...

Страница 6: ...nversation The sample at the left shows the conversation state between No 1 panel and No 2 panel The others will show BUSY Network Failure The first digit indicates the address of failed panel The E means Error 4 Fire Telephone System Design 4 1 Stand Alone Fire Telephone System Fig 4 1 shows a standalone fire telephone system The panel can connect maximum 40 zones with each zone maximum 5 handset...

Страница 7: ... state 5 2 Wiring Requirement Cross section area of the power cable not less than 1 5mm2 Twisted pair cable connecting panel and handset with SA not less than 1 0 mm2 Twisted pair cable for the network with SA not less than 1 0 mm2 The cable selection must comply with local code Note the impedance of single line not more than 20Ω 5 3 Installing dimension Installing dimension 482 5mm 177mm 225mm ...

Страница 8: ... Page 6 5 4 Terminals on the panel Fig 5 1 Power 24 GND 24VDC power in polarized E GND Network Network polarized Audio Output Audio signal output Zn Zn Zone Terminals connecting with handsets a 10KΩ 0 5KΩ resistor is required to the last point of each zone ...

Страница 9: ...el will register all networked sub panels automatically Subsequently the first digit of the digitron will show the number of networked panels including the main panel Check whether all panels have been registered according to the shown number If no consistency check the wiring and repeat the above mentioned process The registration information is saved in non volatile memory will not loss on power...

Страница 10: ...available press Network Call will send the call to entire network with the LED indicator fast flashing Meanwhile the digitron on other networked panels will show by flashing X C X The calling panel the Ring In and Network Call LED will fast flash with ringing sound Press Network Call button and then start the conversation The digitron of the panels not attending conversation will show BUSY and the...

Страница 11: ...0N Fire Telephone Panel The Intelligent Solution Page 9 7 2 Network Fault The panel shows network fault when there is any of the panels powered off or network cable fault Check the malfunction panel and wiring ...

Страница 12: ...com cn GST UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk com www gst uk com GST Dubai Global System Technology PLC PO Box 17998 Unit ZA04 JEBEL ALI Free Zone Dubai UAE Tel 971 0 4 8833050 Fax 971 0 4 8833053 Email info gst uk com www gst uk com ...