Conventional Optical
Smoke Detector
R-6601
F
eatures and Benefits
1.
12 Vdc power conventional detector
2.
Built-in N/O contact
3.
Sensing chamber for exceptional dust
proof ability
4.
Single LED
5.
Low profile design
Description
With the technique of scattering, the
detector's reliability, stability and consistency
are improved. The special chamber design
ensures the insert-defend, dirt-defend and
anti-light disturbance.
The detector is non-addressable and can start
operation by applying DC power. It has a
pair of output contact, which is broken in
normal and closes and remains closed after
alarming, and the indicator on the detector is
lit. It can be reset after power cut. The
detector adopts orientation base, with only
one mounting mode.
Technical Specifications
•
Operating Voltage:9.6VDC~14.4VDC
•
Operating Current:
Standby Current<1mA
Alarm Current<20mA
•
Alarm Reset: Instantaneous Cut-out
(5s MAX, 2.5VDC MAX)
•
Power-up Time
≤
10s
•
Response Threshold: 0.10dB/m-
0.21dB/m
•
Output Control Mode: Passive
normally open, closes and self-locks
after alarming, and contact rated
capacitance (1A, 30VDC)
•
Indicator: Red, not lit in normal
operation, and constantly lit when
alarming.
•
Monitoring Area: When space
height is 6m 12m, the monitoring
area of a detector is 80m
2
for
normal protection area; When
space height is less than 6m, it is
60m
2
.
•
Operating Environment:
Temperature: -10°C+50°C@95%
•
Ingress Protection Rating: IP22
•
Material and Color of Enclosure:
ABS, ivory white
•
Weight: 119g
•
Mounting Hole Distance:
45mm~75mm
•
Wiring: 2 pair polarized
•
Dimensions:
diameter 10cm;
height 5cm
Detector Installation
It is installed onto a standard one gang
electrical box with a mounting hole that
have 6.5cm spacing. Point the detector in
the base by the mark-line and secure the
detector in that position by rotates it
clockwise until it reaches the next mark line.
EMBEDDED BOX
CONCRETE PAD OR
HOLDING PAD
LED INDICATOR
MARK−LINE
ROTATE CLOCKWISE
2ND MARK−LINE
Wiring and Connection
Connect the wires to the required terminal
according to the wiring diagram. The cable
must be fire rated type and the size
depends on the distance and application.
Minimum size gauge 1.0mm²(18 AWG).
Ordering Information:
Part
No
Description Weight/
Kg
Pack Qty
per Box
R-6601 Conventional
Optical Detector,
12-28VDC Power,
N/O Relay Output
0.123 120
MANUFACTURED IN ACCORDANCE WITH