background image

 

petroleum gas should be mounted within 30cm 
to the floor.  

Fig. 2 

¾

 

The detector should be within 1.5m ~4m 

to the gas resource or the gas stove. 

To correctly use the detector and avoid any 
possible fault, please do not mount the 
detector at following locations:  

a.   Where affected by exhaust, steam or 

oil smoke from the stove.  

b. Where near strong airflow, such as 

1.5m<L<4m

Kitchen Ventilator

Gas Stove

cm

Detector detecting 
liquefied petroleum gas

Floor

Ceiling

Within 30cm

Detector detecting 
natural gas or coal gas

 

Содержание C-9101

Страница 1: ...Alarm Panels using Zone monitor module Detector Installation It is installed onto a standard one gang electrical box with a mounting hole that have 6 5cm spacing Point the detector in the base by the...

Страница 2: ...l and GST Intelligent Fire Alarm Panels using Zone monitor module Detector Installation It is installed onto a standard one gang electrical box with a mounting hole that have 6 5cm spacing Point the d...

Страница 3: ...design Technical Specifications Protection Rating IP55 Operating Voltage 24VDC Operating current Standby Current 0 Alarm Current 30mA Operating Environment Temperature 10 50 C Relative Humidity 95 Con...

Страница 4: ...al Specifications Operating voltage 24Vdc non polarized Operating Current 24Vdc Standby current 10mA Action current 160mA Operating temp 10 C to 50 C Flashing Frequency 20x180 per min Alarm Volume SPL...

Страница 5: ...the power supply as well as the cathode of next detector 4 connects with the cathode of remote indicator Recommended Wiring 1 0mm2 or above fire cable for all terminals laid through metal conduit or...

Страница 6: ...in Fig 10 b Clean the sensing chamber by alcohol cotton swab clipped by tweezers and also by clear water and brush Please note not to leave any cotton in the chamber c Install the sensing chamber and...

Страница 7: ...l and GST Intelligent Fire Alarm Panels using Zone monitor module Technical Specifications Standard EN54 part 11 Approval LPCB CE Protection rating IP 40 Operating voltage 24Vdc Loop Operating current...

Страница 8: ......

Страница 9: ...Panels using Zone monitor module Detector Installation It is installed onto a standard one gang electrical box with a mounting hole that have 6 5cm spacing Point the detector in the base by the mark...

Страница 10: ...imensions diameter 10cm height 3 5cm w o cover 4 5cm w cover Sounder Installation The sounder base should be installed in compliance with all local codes or NFPA 72 National Fire Alarm Code NFPA 70 Na...

Страница 11: ...zone monitor unit is powered up and in normal operation the unit is acting as a load to produce periodic plus minus alternating differential pulse signals Due to the voltage dividing of current limiti...

Страница 12: ...stem is back in operation 7 If a unit fails in testing check its connection and test again If it still fails return for repair VII Troubleshooting 1 The system alarms fault after power up Check power...

Страница 13: ...eration and suitable for 92 MCP series The C 92FC constructed of high plastic quality with a modern pleasing appearance Technical Specifications Material and colour transparent flexi glass Dimensions...

Страница 14: ...eration and suitable for 92 MCP series The C 92FC constructed of high plastic quality with a modern pleasing appearance Technical Specifications Material and colour transparent flexi glass Dimensions...

Страница 15: ...the detector directly Otherwise the detector may be damaged for lack of current limit resistor The default class of the detector is A1R and polling LED status is ON which can be modified using a handh...

Страница 16: ...e metal component on the PCB against damp and improper distortion Do fire simulation test at least once every 6 months Specification Operating Voltage 24VDC 16VDC 28VDC Standby Current 60 A Alarm Curr...

Страница 17: ...her alarms in a common alarm network up to 30 alarms or can be interfaced to other systems Technical Specifications Power Supply PP3 H6F22 DC9V battery Indicator Red flashes in every 50 seconds in nor...

Страница 18: ......

Страница 19: ...CONTENTS I Description 1 II Specification 1 III Structure 2 IV Mounting and Wiring 3 V Application 6 VI Troubleshooting 7 VII Maintenance 8 VIII Cautions 8 IX Warranty Limited 9...

Страница 20: ...Alarm State 5 0 W 3 Output capacity and control mode Voltage contact For 12VDC one way pulse solenoid whose driving capability is 1000 F capacitance discharge Volt free contact Volt free normally open...

Страница 21: ...st the LEDs will flash in turn and the buzzer will sound three times 8 Life of Sensor 5 years 9 Operating Environment Temperature 10 50 Relative Humidity 95 non condensing 10 Dimension 121mm 87mm 47mm...

Страница 22: ...depends on where the gas stove is There are still some principles to follow The detector and the gas stove should be placed in the same room The detector detecting natural gas or coal gas should be mo...

Страница 23: ...use the detector and avoid any possible fault please do not mount the detector at following locations a Where affected by exhaust steam or oil smoke from the stove b Where near strong airflow such as...

Страница 24: ...d g Where the detector is partitioned with the gas devices 2 Terminals are shown in Fig 3 Fig 3 K1 K2 Volt free normally open contact it is closed when alarming V V Connects with pipe solenoid or mech...

Страница 25: ...Applying power supply to the detector after wiring and checking the green LED flashes 3 6 minutes for warm up and then it will light constantly for normal monitoring 2 Alarming When the monitored gas...

Страница 26: ...ull it open manually 3 Fire Alarm Treatment When the detector alarms please immediately open the windows for ventilation Put out any fire do not make new fires Avoid switching on or off any electric a...

Страница 27: ...ominated on its label 2 Don t install the detector at locations with high temperature near stoves or too much oil smoke near kitchen ventilator Keep environment around the detector clean 3 The detecto...

Страница 28: ...e normal work after more than 5 hours with power on IX Warranty Limited GST warrants that the product will be free from defects in design materials and workmanship during the warranty period This warr...

Страница 29: ...com cn GST UK Global System Technology PLC Lion Court Staunton Harold Hall Melbourne Road Ashby de la Zouch Leicestershire England LE65 1RT Tel 44 1283 225 478 Fax 44 1283 220 690 Email info gst uk co...

Страница 30: ...solenoid valve driving ability 1000 F capacitance discharge Passive Contact Passive normally open contact capacitance 220V 1A for controlling connected devices Alarm Density Natural Gas 5500ppm 11 LEL...

Страница 31: ...cording to the wire diagram K1 K2 Normally open passive contact which will be closed when the detector alarms V V Connects with pipe solenoid If the detector had alarmed for 3 to 7 seconds there would...

Страница 32: ...ator Red not lit in normal operation and constantly lit when alarming Monitoring Area When space height is 6m 12m the monitoring area of a detector is 80m2 for normal protection area When space height...

Страница 33: ...DZ 03 DZ 03D...

Страница 34: ...i wire fire alarm developed from SCM Those with signal output interface board has a passive normally open alarm output contacts and fault output contact on each zone They have two external control out...

Страница 35: ...d Of Line resistor 4 7K or AEOL Active End Of Line No of Sounder Output 2 Sounder Output Current 1 Ampere 500mA per output Sounder Output Voltage 20Vdc to 28 Vdc Aux Power Output 20Vdc to 28 Vdc Appli...

Страница 36: ...d has a passive normally open alarm output contacts and fault output contact on each zone The two kind panels have six control output points through which it can control some devices such as sounder s...

Страница 37: ...A Fire Alarm Output Output voltage 20Vdc 28Vdc Output current 0 5 A Fault Output Capacity Passive contact output 24vdc 1 A Aux Power Output 20Vdc to 28 Vdc 0 5A Repeater Panel Outpt 10mA Zone Capacity...

Страница 38: ...ons diameter 10cm height 5cm Selection of compatible Control Panels Compatible with all GST Conventional panel and GST Intelligent Fire Alarm Panels using Zone monitor module Detector Installation The...

Страница 39: ...ce from the detector With built in intelligent microprocessor the detector has strong ability of analysis and judgment The detector is ideally suited to historical buildings warehouses large storages...

Страница 40: ...e cable must be fire rated and the size depends on the distance and application The minimum size gauge 1 0mm Selection of compatible Control Panels Compatible with all GST Intelligent Fire Alarm Panel...

Страница 41: ...GST Conventional panels Wiring and Connection Connect as per the marking on the base Technical Specifications Standard EN54 part 11 Approval CE Protection rating IP 40 Operating voltage 24Vdc Loop Ope...

Страница 42: ...retardant base with two taping screws Then align A on the bottom of the detector to B of the base and rotate the detector clockwise to mark C Refer to Fig 1 and Fig 2 for mark A B C Mounting of the d...

Страница 43: ...also by clear water and brush Please note not to leave any cotton in the chamber c Install the sensing chamber and top cover back 5 Before cleaning notify the proper authorities that the system is und...

Страница 44: ...e checking for short circuit or broken circuit It can also identify the location of detecting zone Installation and operation of the panel are very simple All control functions are realized through a...

Страница 45: ...rol Mode Passive normally open closes and self locks after alarming and contact rated capacitance 1A 30VDC Indicator Red not lit in normal operation and constantly lit when alarming Operating Environm...

Отзывы: