Page 9
Using the Inputs
Inputs 1,2, & 3 - Automatically Reset
Inputs 1,2 & 3 are triggered by a negative pulse eg: pulled to the ground for a period of not less
than 1 second. The image (at bottom of page) is a typical application of how to connect the unit
to an alarm panel.
Input 1 and Input 2 are constantly monitored by the Auto Dialler Plus and will react immediately
when an input is pulled to the ground. The inputs will automatically reset when the input
triggers are cleared/reset. The Auto Dialler will the be ready for the next trigger input.
Alarm Input - Manual Reset
Alarm Input
This is triggered by a negative pulse eg: pulled to the ground for a period of not less than 1
second. Before this can be triggered you must activate the alarm input by sending the text
message command as follows. The unit will need manually activating again once triggered by
a text message.
#
ALARM
=
ON
#
- This will activate the alarm if the input is pulled to ground. You will
receive the text acknowledgement “ALARM TRIGGERED”
#
ALARM
=
OFF
#
- This will deactivate the alarm. Pulling the input to the ground will mean
you will receive NO notifications.
Auto Relay Trigger Input (Relay 2)
Relay 2 can be set to automatically pulse for 17 seconds when an input has been triggered.
Please be aware of any conflicts this may cause if you are already using relay 2 as an
independently activated relay. To turn this function on, please send the text command:
#
AUTO
=
ON
#
- This will turn the auto function on for relay 2 only
#
AUTO
=
OFF
#
- This will turn the auto function OFF for relay 2 only (default setting is off)