39

THERMOSTAT POST VENTILATION FUNCTION

In order to prevent an overheat stress, in 

case at the end of a DHW intake the heat 

exchanger temperature is too high, a heat 

disposal function by fan ignition is activated.

This function remains active until the 

temperature values decrease and the heat 

exchanger returns to its normal temperature.

Содержание IVY 24 MR/MN

Страница 1: ...ITALIAN DESIGN INSTALLATION COMMISSIONING USE AND MAINTENANCE MANUAL Wall mounted boiler with plate heat exchanger Monothermal A brand by G20 ENGINEERING...

Страница 2: ......

Страница 3: ...IVY 24 28 32 KW MR MN MONOTHERMAL BOILER MANUAL VERS 11 2017 REV 3...

Страница 4: ...nual supplied with every boiler should be considered as an integral component as it contains instructions for the correct safe and appropriate installation use and maintenance of the system The manual...

Страница 5: ...of boilers is also increased by the possibility to configure the management program of the microprocessor fitted to the system This allows to pass from a reduced number of functions and configurations...

Страница 6: ...lative values to be displayed is extremely simple It is composed of a large backlit LCD which displays all symbols necessary for communicating the boiler s status in a simple and immediate way togethe...

Страница 7: ...with transducer and it is possible to turn the boiler on by pressing BUTTON 1 at the MAIN MENU page In order to go back to the first page stand by press again BUTTON 1 Pic 5 2 By pressing BUTTON 4 th...

Страница 8: ...are installed the following are displayed respectively the pressure of the central heating circuit with relative symbol the external sensor present symbol and the OT timer thermostat present symbol P...

Страница 9: ...onal mode i e ready to supply the only service which it has been manufactured for Pict 7 3 SEASON SELECTION TEMPERATURE REGULATION Pic 7 1 Pic 7 2 Pic 7 3 Boilers for domestic hot water production It...

Страница 10: ...ice for modifying the CH temperature is disabled Boilers for central heating only Only the temperature value for the single option which can be viewed on the display can be adjusted in central heating...

Страница 11: ...e automatically based on the temperature measured by the suitably located sensor on the outside of the building Adjustments are made automatically to the central heating circuit temperature using a pr...

Страница 12: ...transitory faults are possible Many of these are recognized and cause a temporary block which is automatically reset once the condition causing the fault has stopped Some of these provide for the poss...

Страница 13: ...ter temperature too high Boiler locked Degas CH system Check CH system pressure Check CH system circulation Check combustion adjustmen E10 Central heating system pressure too HIGH 2 7 bar Boiler locke...

Страница 14: ...heat exchanger 2 Burner 3 Gas valve 4 Three way valve 5 Safety valve 6 Filling loop cock 7 Hot water priority turbine 8 Secondary heat exchanger 9 Circulator unit 10 Expansion tank 1 Primary heat exc...

Страница 15: ...UMP LIVE PUMP NEUT FAN LIVE FAN NEUTRAL NEUTRAL LIVE GND SIGN 5VDC PRESSURE SENSOR 3WAY VALVE MOTOR 1 6 3 4 M0900 M0901 M0100 M0101 M0904 M0902 M5 M3 1 1 1 1 1 1 EA EA TERRA M0900 M0901 M0100 M0101 M0...

Страница 16: ...d maintenance manuals and observing the general inspection and maintenance conditions General requirements Installation must only be performed by qualified and licensed personnel They also assume resp...

Страница 17: ...ly prepared holes then hang the boiler inserting the hooks of the plugs in the specific holes Fasten the template so that its axis coincides perfectly with that of the boiler 750 MURO WALL DIMENSIONE...

Страница 18: ...Pic 20 Pic 21 LAYOUT OF CONNECTIONS 24 KW 28 32 KW...

Страница 19: ...ORPROPERTY DUE TO OPERATION OF THE SAFETY VALVE DO NOT USE THE PLUMBING PIPEWORK CONNECTIONS AS EARTH POINTS FOR ELECTRICAL EQUIPMENT CONNECTING FILLING COCK FOR CENTRAL HEATING ONLY BOILERS In order...

Страница 20: ...ore connecting the boiler to the mains gas check that it is designed to function with the available type of gas Thoroughly flush all the gas pipes to remove any residues which could compromise correct...

Страница 21: ...witch installed before it Remove the lower cover by removing the four screws turn the instrument panel to the open position Remove the rear case cover by unscrewing the 4 screws Identify the terminals...

Страница 22: ...isted on the technical data plate and summarised below C12 concentric wall flue The pipes may also be split but the outlets must be exposed to similar wind conditions C32 concentric vertical flue with...

Страница 23: ...it flue system is composed of one pipe for combustion gas evacuation connected to the fan outlet and one for the air intake connected to the hole on the roof of the sealed chamber The system provides...

Страница 24: ...lar gasket d 60 12 Gasket d 80 The maximum possible length therefore depends on the components used to create the line and can be determined by adding the Equivalent lengths for each individual compon...

Страница 25: ...fan and flue duct for systems of minimum or intermediate length The size of the diaphragm depends on the The detected value shall not be less than shown in the table EXHAUST TECHNICAL FEATURES SUMMARY...

Страница 26: ...NG FROM APPLICABLE LEGISLATION AND REGULATIONS TO THE LETTER ONLY USE APPROVED COMPONENTS FOR AIR INTAKE AND COMBUSTION GAS EVACUATION SYSTEMS WHICH ARE OF THE CORRECT DIMENSIONS AND PURPOSELY DESIGNE...

Страница 27: ...burner Check that the boiler ignites turns off and functions correctly Visual check for leaks in gas and water pipes and unions Check that the safety devices are operational This function allows the b...

Страница 28: ...LER HAVE BEEN OBSERVED If the function remains activated for long periods of time an increase in pressure may occur in correspondence with the system s terminals All safety measures are active when in...

Страница 29: ...plicable legislation and regulations in particular That a gas shut off valve is installed immediately before the device This must have a YELLOW valve handle and must be placed in a position which allo...

Страница 30: ...connect it with silicone tubing to the input of a differential manometer with an appropriate range at least 0 Check that all preliminary indications and checks specified have been carried out Activate...

Страница 31: ...ine which could lead to excessive pressure drops e g too many bends changes of direction excessively long or countersloping sections etc Consult the gas company on the specified minimum supply pressur...

Страница 32: ...LET SCREW UNTIL IT SEALS Press the gas valve regulation screws cover closed Return the instrument panel to its operating position fastening if necessary Refit the lower cover fastening it with the scr...

Страница 33: ...rews together with any previously removed deflectors and conveyors Replace and close the combustion chamber cover Reconnect the ignition electrode cable located in the front Replace and close the seal...

Страница 34: ...alue of the parameter referred to by that page is displayed normally In this mode it is possible to scroll through the pages for all parameters and read the relative values but without the possibility...

Страница 35: ...te curve parameter 20 10 0 P9 Type of system pressure measurement device 0 none 1 0 5 2 5 V transducer B type 2 0 5 3 5 V transducer A type 3 pressure switch 4 flow switch P10 ALL PARAMETER MODIFICATI...

Страница 36: ...2 Low temperature 1 A3 Plate heat exchanger preheating 0 not enabled 1 enabled 0 A4 Storage tank preparation temperature Spboll sp sani a4 5 20 15 A5 DHW storage tank hysteresis temp for burner igniti...

Страница 37: ...or the EASY CONTROL Open Therm see wire scheme at page 15 Connection x13 Whenever necessary replace the TA cable and connect it directly to the slot present in the PCB case as follows Power the boiler...

Страница 38: ...slots Pict 41 Run the cable and hold it in position with the cable grip at the edge of the case Position the cable running it under the cable gripping tabs on the side of the case Close the case cover...

Страница 39: ...me comfort to be maintained while making significant savings in gas consumption It is possible to adapt the boiler s response based on the climatic conditions present by configuring the slope of the c...

Страница 40: ...low circuit is 6 C circulation is activated the diverter valve when present switched to the CH circuit and the burner lit at minimum power When the temperature measured by the sensor reaches 30 C the...

Страница 41: ...at stress in case at the end of a DHW intake the heat exchanger temperature is too high a heat disposal function by fan ignition is activated This function remains active until the temperature values...

Страница 42: ...head mwc 5 0 6 0 6 5 DOMESTIC HOT WATER Continuous draw T 25 C l min 13 5 14 5 16 6 Max DHW pressure bar 10 0 10 0 10 0 Min DHW pressure bar 0 5 0 5 0 5 Min max DHW temp adjustment C 30 60 30 60 30 60...

Страница 43: ......

Страница 44: ...MADE IN ITALY G20 ENGINEERING SRL Loc Campogrande 13 29013 CARPANETO PIACENTINO PC Italy phone 39 0523 850513 fax 39 0523 850712 www aircontrol pc com www g20engineering com A brand by G20 ENGINEERING...