CONTROLLO ZONE FZ4B
90
cod. FZ4B - 06/2011 (Rev. 00)
EN
7
Pump phase (RY1)
Mixed zone 1
8
Pump neutral (RY1)
Mixed zone 1
9
Mixing Valve Opening phase (RY2)
Mixed zone 1
10
Mixing Valve neutral (RY2)
Mixed zone 1
11
Mixing Valve Closing phase (RY3)
Mixed zone 1
12
Pump phase (RY4)
Direct zone 1
13
Pump phase (RY5)
Direct zone 2
14
Pump neutral (RY5)
Direct zone 1
14
Pump neutral (RY5)
Direct zone 2
19
On/Off Thermostat or Remote Control (RT1)
Mixed zone 1
20
On/Off Thermostat or Remote Control (RT1)
Mixed zone 1
21
On/Off Thermostat or Remote Control (RT2)
Direct zone 1
22
On/Off Thermostat or Remote Control (RT2)
Direct zone 1
23
On/Off Thermostat or Remote Control (RT2)
Direct zone 1
24
On/Off Thermostat or Remote Control (RT2)
Direct zone 1
25
NTC sensor (T1)
Mixed zone 1 delivery
26
NTC sensor (T1)
Mixed zone 1 delivery
X15
Card SK connected
The algorithm of Direct Zone1 remains the same as the con
fi
guration: 5.1 “ONE Direct Zone – No External Sensor”.
The algorithm of Direct Zone2 remains the same as the con
fi
guration: 5.1 “ONE Direct Zone – No External Sensor”.
The algorithm of the Mixed Zone remains the same as the con
fi
guration: 5.7 “ONE Mixed Zone – No External Sensor”.
What changes is:
a. The calculation of Zone card Heating Setpoint
In case of simultaneous request, the Zone card Heating Setpoint is equal to the highest of the three: Zone1 Heating Setpoint, Zone2 Heating Setpoint and Zone3
Heating Setpoint.
If the zone that ends the request has the highest Heating Setpoint, the Zone card Heating Setpoint must be immediately decreased until it is equal to the Heating
Setpoint of the zone still in request status.
If the zone that starts the request has a higher Heating Setpoint than the zone already in request status, the Zone card Heating Setpoint must be immediately increased
until it is equal to the higher Heating Setpoint of the zone in request status.
b. Each zone has its own adjustment sensors and parameters.
c. Post-circulation time
This must be carried out only on the last zone that ends the request.
Also, if the last zone in request status is doing post-circulation and another zone starts its own request, post-circulation must be stopped whereas the mixing valve
must be closed for the entire duration of the Mixing valve closing Time timer (TSP31): so that there is always and only a single zone in post-circulation.
5.14 “ONE MIXED ZONE AND TWO DIRECT ZONES – WITH EXTERNAL SENSOR”
Autocon
fi
guration:
Connection
Description
7
Pump phase (RY1)
Mixed zone 1
8
Pump neutral (RY1)
Mixed zone 1
9
Mixing Valve Opening phase (RY2)
Mixed zone 1
10
Mixing Valve neutral (RY2)
Mixed zone 1
11
Mixing Valve Closing phase (RY3)
Mixed zone 1
12
Pump phase (RY4)
Direct zone 1
13
Pump phase (RY5)
Direct zone 2
14
Pump neutral (RY5)
Direct zone 1
14
Pump neutral (RY5)
Direct zone 2
19
On/Off Thermostat or Remote Control (RT1)
Mixed zone 1
20
On/Off Thermostat or Remote Control (RT1)
Mixed zone 1
21
On/Off Thermostat or Remote Control (RT2)
Direct zone 1
22
On/Off Thermostat or Remote Control (RT2)
Direct zone 1
23
On/Off Thermostat or Remote Control (RT2)
Direct zone 1
24
On/Off Thermostat or Remote Control (RT2)
Direct zone 1
25
NTC sensor (T1)
Mixed zone 1 delivery
26
NTC sensor (T1)
Mixed zone 1 delivery
30
NTC sensor (T4)
External probe
31
NTC sensor (T4)
External probe
X15
Card SK connected
The algorithm remains the same as the con
fi
guration: 5.13 “ONE Mixed Zone and TWO Direct Zones – No External Sensor”.
What changes is only the calculation of Zone1 Heating Setpoint, Zone2 Heating Setpoint and Zone3 Heating Setpoint if the sliding temperature was activated in one or
more zones.
5.15 “TWO MIXED ZONES AND ONE DIRECT ZONE – NO EXTERNAL SENSOR”
Autocon
fi
guration:
Connection
Description
7
Pump phase (RY1)
Mixed zone 1
8
Pump neutral (RY1)
Mixed zone 1
8
Pump neutral (RY4)
Mixed zone 2
Содержание FZ4B