3.2 Mechanical installation
3.2.1 Tank inlets
We recommend that you connect the inlet pipes to the
top inlets of the tank. This prevents backflow and
deposits in the inlet pipe, and enables a high start
level of the pump. A high start level increases the
effective tank volume and reduces the number of
start/stops of the pumps.
3.2.2 Location
Install the lifting station in a properly lit and vented
room with 60 cm free space around all parts to be
serviced and operated.
The tank must not be exposed to direct sunlight. UV
light can affect the properties of its composite
material, resulting in a shorter life.
The product is designed for indoor operation. If
installed outside, the lifting station must be placed in
a closed pit.
The tank can be flooded and may be installed in a
basement with risk of penetrating groundwater.
6
2
3
4
5
1
7
TM065789
Installation example with a tank in a sump and with a controller.
The diaphragm pump is not shown.
Pos. Designation
1
Isolating valve, inlet
2
Controller
3
Drainage pump
4
Non-return valve, outlet
5
Isolating valve, outlet
6
Vent pipe
7
Backflow loop
1
6
3
4
5
7
TM065790
Installation example with a tank on the basement floor. The
diaphragm pump is not shown.
Pos. Designation
1
Isolating valve, inlet
3
Drainage pump
4
Non-return valve, outlet
5
Isolating valve, outlet
6
Vent pipe
7
Backflow loop
13
English (GB)
Содержание UNOLIFT
Страница 1: ...UNOLIFT DUOLIFT Installation and operating instructions GRUNDFOS INSTRUCTIONS ...
Страница 2: ......
Страница 18: ...TM059633 UNILIFT AP35B AP50B TM059630 UNILIFT CC KP 18 English GB ...
Страница 19: ...x4 TM082793 UNILIFT APG x4 TM059632 SEG 19 English GB ...
Страница 20: ...x4 TM078303 DUOLIFT SEG 20 English GB ...
Страница 21: ...x4 TM082794 DUOLIFT UNILIFT APG 21 English GB ...
Страница 36: ...Appendix A A 1 Appendix TM061067 Unolift 270 Duolift 270 678 Appendix A ...
Страница 37: ...TM061066 Duolift 540 679 Appendix A ...