6.2 Fault codes reset

When a fault appears and the RSI stops, examine 
the cause of fault, perform the actions advised in 
section 6.1 and reset the fault as instructed below.
1. With a long (1 s) press on the Reset button on 

the keypad or

2. By entering the Diagnostics Menu (M4), entering 

Reset faults (M4.2) and selecting Reset faults 
parameter.

3. For keypad with LCD display only: By selecting 

value Yes for the parameter and clicking OK.

6.3 Fault history

The inverter will record the forty most recent fault 
codes. Searching this information will help 
investigate the fault cause. Fault information is 
stored together with additional informationsin the 
fault history menu.

7. Service and maintenance

7.1 Routine inspection

To ensure the inverter runs stably, carry out an 
annual inspection.

7.1.1 Inspection and maintenance requirements

1. If it is necessary to conduct an insulation test on 

the inverter, all input and output terminals must 
have a proper short-circuit. Insulation tests must 
not be performed on a single terminal. Use a 500 
V mega ohm meter to conduct the test.

2. When conducting an insulation test on the motor, 

dismantle the connection between motor and 
inverter.

Caution

Check the fault cause thoroughly and 
remedy it before resetting. If it cannot be 
reset or persists after resetting, check the 
cause again as continuous resetting will 
damage the inverter.

Caution

In case of overload and overheat 
protection, delay the resetting for 5 
minutes.

Warning
Maintenance and inspection must be 
performed by a qualified electrician.
Do not dismantle the inverter when it is 
running. The inverter must be powered off 
at least 5 minutes before conducting 
maintenance and inspection.
It is absolutely forbidden for unauthorised 
persons to repair the inverter as this can 
cause personal injury or equipment 
damage.

Note

Any service performed on the inverter by 
unqualified staff will void the warranty.

Warning
The inspection must be performed by 
trained and qualified technical staff. 
Disconnect the power supply to the 
inverter before starting inspection

Caution

Do not use the mega ohm meter to test the 
control circuit.

Содержание RSI Series

Страница 1: ...RSI 1 5 37 kW Installation and operating instructions GRUNDFOS INSTRUCTIONS...

Страница 2: ...ctions Installation and operation must comply with local regulations and accepted codes of good practice Advanced IO http net grundfos com Appl ccmsservices public literature filedata Grundfosliteratu...

Страница 3: ...5 5 5 kW TM06 6526 1813 E W W2 L1 L L2 H H2 H1 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame A 8 8 5 9 143 5 191 0 297 0 293 0 315 0 188 0 197 0 214 0 Frame...

Страница 4: ...W2 H H2 H1 L1 L L2 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame B 14 9 6 1 180 0 233 0 349 0 345 2 368 0 204 0 214 0 231 0 Frame Size Package Gross weight...

Страница 5: ...W2 H H2 H1 L1 L L2 Frame Size Product Net weight kg E mm W mm W2 mm L mm L1 mm L2 mm H mm H1 mm H2 mm Frame C 31 5 8 2 322 0 350 0 385 0 382 5 500 0 230 0 236 0 254 0 Frame Size Package Gross weight...

Страница 6: ...age VAC 220 380 Enclosure class IP66 IP66 Power kW Product number Electrical Data Frame size Max P2 kW Rated Output Current A 1 5 99090622 1 5 8 A 2 2 99090633 2 2 11 A 3 0 99090634 3 0 12 5 A 4 0 990...

Страница 7: ...he control panel and select min Frequency Caution To ensure a good convective cooling effect install the inverter vertically with at least 10 cm free space at the top and bottom To be installed indoor...

Страница 8: ...Can be isolated from ground see chap 12 24Vout 24V aux voltage 13 GND I O ground 14 DI4 Digital input 4 15 DI5 Digital input 5 16 DI6 Digital input 6 17 CM Common for DI1 DI6 18 AO1 Analogue output v...

Страница 9: ...every 1500 m increase in altitude Note Adjust control parameters according to the steps indicated in this manual before the first start TM05 4446 2412 Digital display control panel Operating keys The...

Страница 10: ...ntrol panel and edit parameter values Down key Navigate control panel and edit parameter values Right key Navigate control panel and edit parameter values Left key Navigate control panel and edit para...

Страница 11: ...lay Directions Notes Select Language Select Start up Wizard Verify or adjust the rated motor voltage Verify or adjust the rated frequency Verify or adjust the nominal speed Verify or adjust the rated...

Страница 12: ...Select pump type or Other and adjust parameters Select solar modules or other and adjust Vmp maximum power voltage Select the number of solar modules Select if sinus filter is used or not Display Dir...

Страница 13: ...req Reference Target frequency 50 Acceleration time Initial ramp time 3 Deceleration time Final ramp time 3 PV modules type Solar panel type sw260 Module MP Voltage Vmp Maximum power point voltage 31...

Страница 14: ...n time longer Use brake chopper or brake resistor available as options Activate overvoltage controller Check input voltage 11 Overvoltage software fault 3 20 Earth fault hardware fault Current measure...

Страница 15: ...o you 609 Memory access has failed For example retain variables could not be restored 610 Necessary device properties cannot be read 614 Configuration error 647 Software error Update software Should t...

Страница 16: ...ure Motor is overloaded Decrease motor load If no motor overload exists check the temperature model parameters 17 160 Motor underload Motor is underloaded Check load 19 180 Power overload short time s...

Страница 17: ...l Time Clock RTC battery voltage level is low and the battery should be changed Replace the battery 47 663 Software updated Software of the drive has been updated either the whole software package or...

Страница 18: ...limit Carry out the needed maintenance and reset counter 69 1310 Fieldbus mapping error Non existing ID number is used for mapping values to Fieldbus Process Data Out Check parameters in Fieldbus Dat...

Страница 19: ...ched the alarm limit Find the cause of temperature raise Check the temperature sensor and connections Check that the temperature input is hardwired if no sensor is connected See option board manual fo...

Страница 20: ...circuit Insulation tests must not be performed on a single terminal Use a 500 V mega ohm meter to conduct the test 2 When conducting an insulation test on the motor dismantle the connection between mo...

Страница 21: ...on environment 2 Radiator 3 Fan 1 Good ventilation in installation environment 2 Radiator air duct not blocked 3 Fan should be running smoothly if equipped Inverter cabinet 1 Vibration 2 Temperature r...

Страница 22: ...ong period of time It is thus necessary to start up the equipment every two years to restore the performance of the capacitor and inspect the inverter function at the same time The voltage must be inc...

Страница 23: ...23...

Страница 24: ...Tallinn Tel 372 606 1690 Fax 372 606 1691 Finland OY GRUNDFOS Pumput AB Trukkikuja 1 FI 01360 Vantaa Phone 358 0 207 889 500 Telefax 358 0 207 889 550 France Pompes GRUNDFOS Distribution S A Parc d A...

Страница 25: ...5020 1426 sk grundfos com Slovenia GRUNDFOS LJUBLJANA d o o Lesko kova 9e 1122 Ljubljana Phone 386 0 1 568 06 10 Telefax 386 0 1 568 06 19 E mail tehnika si grundfos com South Africa GRUNDFOS PTY LTD...

Страница 26: ...4145 0516 ECM 1184037 The name Grundfos the Grundfos logo and be think innovate are registered trademarks owned by Grundfos Holding A S or Grundfos A S Denmark All rights reserved worldwide Copyright...

Отзывы: